3.11.4.1 Internal Engine Components
If you have access to a fogging agent or SAE 10 oil prepare the pistons and cylinders for storage as follows:
1. While the engine is running, spray a fogging agent or SAE 10 engine oil into the air intake for about two minutes until
the engine stops.
2. Place the generator set master switch in the OFF/RESET position.
If a fogging agent is not available perform the following:
1. Remove the spark plugs.
2. Pour 15 cc (0.5 oz.) of engine oil into each spark plug hole.
Ignition System Damage.
Refer to the engine operation manual for ignition system precautions before cranking the engine
while the spark plug wires are disconnected.
3. Toggle the generator set master switch to crank the engine two or three revolutions to lubricate the cylinders.
4. Reinstall the spark plugs and torque them to specifications.
3.11.5 Exterior
1. Clean the exterior surface of the generator set.
2. Seal all engine openings except for the air intake with non absorbent adhesive tape.
3. To prevent impurities from entering the air intake and to allow moisture to escape from the engine, secure a cloth over
the air intake.
4. Mask electrical connections.
5. Spread a light film of oil over unpainted metallic surfaces to inhibit rust and corrosion.
3.11.6 Alternator
WARNING
Risk of fire.
Can cause severe injury or death.
Do not smoke or permit flames or sparks near fuels or the fuel system.
Combustible materials. A fire can cause severe injury or death.
If using generator heaters during storage, remove
combustible materials such as covers from contact with the heater or from areas where heat could potentially cause a fire.
Humidity, moisture, and dust can damage the alternator during storage. Store the generator set in a clean, dry area and protect
the alternator from inclement weather. Keep room temperatures relatively constant to prevent condensation on the windings.
Cover ventilation and other entry points to prevent damage by rodents, birds, and insects.
Before returning the alternator to service, have an authorized service distributor/dealer, perform the following alternator service:
Clean the ventilation circuit.
Blow dust off the windings.
Check the rotor and stator winding insulation.
Check the rotor and stator winding resistance and continuity.
On units with regreasable bearings, grease the bearings and rotate the shaft to distribute grease on the bearings.
Содержание APM402
Страница 6: ...6 TP 6694 9 20 ...
Страница 16: ...16 TP 6694 9 20 ...
Страница 42: ...42 TP 6694 9 20 ...
Страница 78: ...78 TP 6694 9 20 ...
Страница 112: ...112 TP 6694 9 20 ...
Страница 120: ...120 TP 6694 9 20 ...
Страница 124: ...124 TP 6694 9 20 Figure 54 20 150 kW Permanent Magnet Single Phase Alternators ADV 5875AB 1 ...
Страница 125: ...TP 6694 9 20 125 Figure 55 20 300 kW Permanent Magnet Alternators ADV 5875AB 2 ...
Страница 126: ...126 TP 6694 9 20 Figure 56 60 IMS 300 kW Wound Exciter Field 20 300 kW 600 V Perm Magnet Alternators ADV 5875AB 3 ...
Страница 127: ...TP 6694 9 20 127 Figure 57 300 kW and Larger Pilot Excited Permanent Magnet 4M 5M 7M 10M Alternators ADV 5875AB 4 ...
Страница 128: ...128 TP 6694 9 20 ...
Страница 131: ...TP 6694 9 20 131 Figure 61 Battery Charger to Controller Connections DEC 3000 Controller ...
Страница 153: ...TP 6694 9 20 153 Figure 90 Controller Wiring Connections GM78246G 1 ...
Страница 154: ...154 TP 6694 9 20 Figure 91 Controller Wiring Connections GM78246G 2 ...
Страница 171: ......