Multi station

Multi station

Art. No. : 23066REGHE

Operating instructions

1 Safety instructions

Electrical devices may only be mounted and connected by electrically skilled
persons.

Serious injuries, fire or property damage possible. Please read and follow manual fully.

Danger of electric shock. Device is not suitable for disconnection from supply voltage.

For parallel connection of several motors to an output it is essential to observe the
corresponding instructions of the manufacturers, and to use a cut-off relay if necessary.
The motors may be destroyed.

Use only venetian blind motors with mechanical or electronic limit switches. Check the
limit switches for correct adjustment. Observe the specifications of the motor
manufacturers. Device can be damaged.

Danger of electric shock on the SELV/PELV installation. Do not connect loads for mains
voltage and SELV/PELV together on a single switch actuator.

These instructions are an integral part of the product, and must remain with the end
customer.

2 Device components

Figure 1

(1) Keypad for local control
(2) Programming button and LEDs
(3) Bus connection
(4) Input terminals
(5) Status LED
(6) Output terminals

1/7

82596803
j0082596803

26.01.2017

Содержание JUNG 23066REGHE

Страница 1: ...o use a cut off relay if necessary The motors may be destroyed Use only venetian blind motors with mechanical or electronic limit switches Check the limit switches for correct adjustment Observe the specifications of the motor manufacturers Device can be damaged Danger of electric shock on the SELV PELV installation Do not connect loads for mains voltage and SELV PELV together on a single switch a...

Страница 2: ...grated push button interface with 6 inputs 2 inputs for temperature sensors Outputs can be operated manually Feedback in manual mode and in bus mode Scene function Disabling of individual outputs manually or by bus Switching function Max 6 switching outputs Operation as NO or NC contacts Logic and restraint function Feedback function Central switching function with collective feedback Time functio...

Страница 3: ...LED A1 flashes o Deactivate Press the c button for approx 5 s Short time manual operation o Activate Press the c button briefly Automatic return to bus operation 5 s after last operation Operating an output in manual mode o Keep pressing the c button until the LED 5 of the selected output flashes o Press the ON n or OFF o button Short Switch on switch off adjust slats or stop Long Move hanging upw...

Страница 4: ...orm a Venetian blind output In each case the left hand relay output A1 A3 A5 is intended for the up direction n and the right hand load output A2 A4 A6 for the down direction o o Connect electrothermal drives to relay outputs A1 A2 i Delivery state The outputs can be operated using a keypad Outputs are set as venetion blind outputs Switching inputs DANGER When the mains voltage is connected to the...

Страница 5: ... downwards operation time of the hanging o Measure slat adjusting time between Open and Closed o Enter the measured values in the parameter setting Downwards travel in minutes seconds and operation time extension in percent Load the address and the application software o Switch on the bus voltage o Press the programming button The programming LED lights up o Assign physical address The programming...

Страница 6: ...amps uncompensated 1000 W parallel compensated 1160 W 140 µF Electrothermal actuators Cycle time min 15 min Load connections Connection mode Screw terminal single stranded 0 5 4 mm Finely stranded without conductor sleeve 0 5 4 mm Finely stranded with conductor sleeve 0 5 2 5 mm Inputs Rated voltage DC 3 3 V SELV Signal duration min 100 ms NO contacts max 50 NC contacts max 50 Cable length max 30 ...

Страница 7: ...ALBRECHT JUNG GMBH CO KG Volmestraße 1 58579 Schalksmühle GERMANY Telefon 49 2355 806 0 Telefax 49 2355 806 204 kundencenter jung de www jung de 7 7 82596803 j0082596803 26 01 2017 Multi station ...

Отзывы: