Dimming actuator, 4-gang

Dimming actuator, 4-gang Standard
Order no.: 2015 00
Dimming actuator, 4-gang Komfort
Order no.: 2025 00

Operating instructions

1

Safety instructions

Electrical devices may only be mounted and connected by electrically skilled persons.

Serious injuries, fire or property damage possible. Please read and follow manual fully.

Danger of electric shock. Always disconnect before carrying out work on the device or load.

Danger of electric shock. Device is not suitable for disconnection from supply voltage. The load
is not electrically isolated from the mains even when the output is switched off.

Risk of destruction of the dimmer and load if the set operating mode and load type do not
match. Set the correct dimming principle before connecting or exchanging the load.

Fire hazard. For operation with inductive transformers, each transformer must be fused on the
primary side in accordance with the manufacturer's instructions. Only safety transformers ac-
cording to EN 61558-2-6 may be used.

These instructions are an integral part of the product, and must remain with the end customer.

2

Device components

Figure 1: Device components

(1)

Button field for manual operation

(2)

Programming button and LED

(3)

KNX connection

(4)

Status LEDs for outputs

(5)

Load connections

3

 Function

System information

This device is a product of the KNX system and complies with the KNX directives. Detailed tech-
nical knowledge obtained in KNX training courses is a prerequisite to proper understanding.

1 / 11

82402712

10.07.2020

Содержание 2015 00

Страница 1: ...the set operating mode and load type do not match Set the correct dimming principle before connecting or exchanging the load Fire hazard For operation with inductive transformers each transformer must...

Страница 2: ...s are connected observe the data of the transformer manufacturer on loads and the dimming principle HV LED and compact fluorescent lamps generate high pulsed currents when they are operated in the lea...

Страница 3: ...ue switch 4 Operation Operating elements Figure 2 Operating elements 4 Status LEDs for outputs on output switched on 1 100 flashes at 1 Hz short circuit or manual mode flashes at 2 Hz overload mains v...

Страница 4: ...manual control the outputs depending on the programming switch to the active position e g forced position logic operation Switching on permanent manual control Operation using the button field is prog...

Страница 5: ...device and stored securely Connecting the device Connect bus line with KNX connecting terminal according to their correct polarity Attach the cover cap to the KNX connection as protection against haz...

Страница 6: ...mode stops the execution of the loaded application program Only the system software of the device is still functional ETS diagnosis functions and pro gramming of the device are possible Manual operati...

Страница 7: ...fter ap prox 5 s Restoring the device to factory settings Devices can be reset to factory settings with the Gira ETS Service App This function uses the firmware contained in the device that was active...

Страница 8: ...load is not permitted Power boosters See power booster instructions Connection single stranded 0 5 4 mm Finely stranded without conductor sleeve 0 5 4 mm Finely stranded with conductor sleeve 0 5 2 5...

Страница 9: ...mming principle does not optimally match the connected lamps Check operation in the HV LED leading edge phase control setting reduce connected load as well if necessary Exchange lamps for another type...

Страница 10: ...rect All outputs off and not possible to switch on Cause 1 bus voltage failure Check bus voltage Luminaires flicker or buzz proper dimming not possible device buzzes Cause wrong dimming principle set...

Страница 11: ...GmbH Co KG Elektro Installations Systeme Industriegebiet Mermbach Dahlienstra e 42477 Radevormwald Postfach 12 20 42461 Radevormwald Deutschland Tel 49 0 21 95 602 0 Fax 49 0 21 95 602 191 www gira de...