7

WARNING

GENERAL

• Connect the plug-in connectors from the Emergency Kit as follows:
- connector labelled “DRIVER OUTPUT” to the LED downlight 
- connector labelled “DRIVER INPUT” to the LED driver
•  If using this kit with the VFRIC8xx range, remove the terminal cover on the end of the emergency kit and replace the two 

plug-in leads with the ICEMC leads (not included): brown (+), blue (-) (see Fig. 2). Replace the terminal cover and plug 
these into the downlight and driver as above

•  If non-maintained operation is required, the Switched Live and Neutral feed to the LED driver can simply be omitted
• Connect the battery pack to the Emergency Kit ensuring correct polarity is observed, red (+), black (-)
•  Refit the terminal covers and insert into ceiling making sure the inverter and battery are not in contact with the 

downlighter, and are not preventing the downlighter from dissipating heat

•  A choice of two LED indicator holders are provided with this accessory. To install, mark the location of the LED indicator 

holder and drill a 6.5mm/18mm hole ensuring not to infringe with any joists, gas/water pipes or electrical cables. Insert 
the LED indicator into the holder and push into the ceiling 

Note

 - the LED indicator should be visible

• Switch on and check for correct operation, ensuring the green LED indicator is illuminated
•  On commissioning the installation a full 3 hour duration check should be completed, a minimum charge period of 24 hours 

is required before initiating this test

•  If the batteries have been left in a discharged state for an extended period, we recommend that one or more charge and 

discharge cycles are completed which should help to restore the battery capacity

This product must be disconnected from the circuit if subjected to any high voltage or insulation resistance testing. 
Irreparable damage will occur if this instruction is not followed.

This product should be recycled in the correct manner when it reaches the end of its life. Check local authorities for where 
facilities exist. 
The batteries in this luminaire are Nickel Cadmium and must be disposed of correctly. Please contact the local authorities for 
the disposal of this toxic waste.
Clean with a soft dry cloth only, do not use aggressive cleaning products or solvents which may damage the product.
The maximum constant ambient temperature at the point of installation should not exceed 50°C
The downlighters used with this emergency kit can be dimmed in the usual way. 

 

Connect the plug-in connectors from the Emergency Kit as follows: 

-

 

connector labelled 

“DRIVER OUTPUT”

 to the LED downlight  

-

 

connector labelled “DRIVER INPUT”

 to the LED driver 

 

If using this kit with the VFRIC8xx range, remove the terminal cover on the end of the emergency kit 

and replace the two plug-in leads with the ICEMC leads (not included): brown (+), blue (-) (see Fig. 2). 

Replace the terminal cover and plug these into the downlight and driver as above 

 

Fig. 2 

 

If non-maintained operation is required, the Switched Live and Neutral feed to the LED driver can 

simply be omitted 

 

Connect the battery pack to the Emergency Kit ensuring correct polarity is observed, red (+), black (-) 

 

Refit the terminal covers and insert into ceiling making sure the inverter and battery are not in contact 

with the downlighter, and are not preventing the downlighter from dissipating heat 

 

A choice of two LED indicator holders are provided with this accessory. To install, mark the location of 

the LED indicator holder and drill a 6.5mm/18mm hole ensuring not to infringe with any joists, 

gas/water pipes or electrical cables. Insert the LED indicator into the holder and push into the ceiling.  

Note -

 the LED indicator should be visible 

 

Switch on and check for correct operation, ensuring the green LED indicator is illuminated 

 

We recommend, on commissioning the installation, a minimum charge period of 24 hours before 

carrying out an emergency duration test 

 

If the batteries have been left in a discharged state for an extended period, we recommend that one or 

more charge and discharge cycles are completed which should help to restore the battery capacity 

WARNING 

This product must be disconnected from the circuit if subjected to any high voltage or insulation resistance 

testing. Irreparable damage will occur if this instruction is not followed. 

GENERAL 

This product should be recycled in the correct manner when it reaches the end of its life. Check local authorities 

for where facilities exist.  

The batteries in this luminaire are Nickel Cadmium and must be disposed of correctly. Please contact the local 

authorities for the disposal of this toxic waste. 

Clean with a soft dry cloth only, do not use aggressive cleaning products or solvents which may damage the 

product. 

The maximum constant ambient temperature at the point of installation should not exceed 50°C 

The downlighters used with this emergency kit can be dimmed in the usual way.  

WARRANTY

 

This product has a warranty of 3 years (excluding battery) from date of purchase. Failure to install this product 

in accordance with the current edition of the IEE Wiring Regulations (BS7671), improper use, or removal of the 

batch code will invalidate the warranty. If this product should fail within its warranty period it should be returned 

to the place of purchase for a free of charge replacement. ML Accessories does not accept responsibility for 

any installation costs associated with the replacement product. Your statutory rights are not affected. ML 

Accessories reserve the right to alter product specification without prior notice. 

 