MCP-1060 Series    

Installation Guide

Installation Guide

6" Pneumatic Damper Actuator

MCP-1060 Series

 

 

 

Mounting

The MCP-1160 series actuator 

MUST 

be mounted on 

a rigid surface due to the force generated at, or near, 

maximum air pressure.
1.  Align the actuator with the controlled device. The 

mounting joint allows the actuator to be located 

in a different plane from the controlled device.

2.  Attach the actuator to the rigid surface.

3.  Adjust the crank arm assembly length (see the 

chart) to provide the (minimum 60° to maximum 

120°) rotation as required.

4. Do 

NOT

 tighten the universal joint. The actuator 

must be free to swivel as it operates.

5.  See the Connection section on the next page.

All dimension are in inches (mm)

 CAUTION

Pneumatic devices must be supplied with clean, dry 
control air. Any other medium (e.g., oil or moisture 
contamination) will cause the device to fail.

CLEVIS

FEEDBACK SPRING

ALTERNATE

FEEDBACK

SPRING

CRANK ARM

BRACKET

MOUNTING POST

(Not Included)