BACnet Broadcast Management Device routing
Either of the two IP ports can be configured as a BACnet Broadcast Management Device
(BBMD). When configuring an IP port as a BBMD, keep in mind the following rules.
l
Configure only one BBMD for a single IP subnetwork.
l
Assign the same BACnet network number to all BBMDs on the internetwork.
l
The BBMD can accept registration from foreign devices or perform BBMD-to-BBMD
routing.
For the log in procedure, see the topic
.
To set up the router as a BBMD, do the following:
1
Use an Internet browser to log in.
2
Click
Routing
and then
Configuration
.
3
Select
Enable
for the port.
4
From the port list box, choose
BBMD
.
5
Click
Table
and then add entries to the Broadcast Distribution Table (BDT).
6
Set other properties as needed and then click
Save
.
Note:
The router will restart. For additional changes, log in again.
Enable
Select to enable the network. The port block turns green when enabled.
Net
Designates the BACnet network number for the port. Assign network numbers in the
range from 1 to 65534.
Port
Assign a unique UDP port number to each of the enabled IP networks. The default port
number is 47808.
Section 3: Setting up routing
KMC Controls, Inc.
30
Revision J