Set roof top unit
system options
The items in the system menu control application specific functions for roof
top units. Entering the system options requires entering Password 2 which is
described in the topic
Procedure
Steps
Display
1
Starting display.
1.
Start at the temperature display.
2.
Enter Password 2. The display changes to the
MAIN menu display.
F
°
70
AUTO
AUTO
SECURITY
ADMIN LEVEL
0
0 0 0
2
Choose and set the
roof top system
options.
1.
From the MAIN menu , press either the
or
button to select SYSTEM.
2.
Press
Enter
. The SYSTEM menu opens.
3.
Choose any of the following items.
LOCAL OVRD TIME
FAN OFF DELAY
OCCUPIED FAN
MIN OFF TIME
STAGE DELAY
ECON ENABLE
MIN ECON DAMPER
ECON ENABLE TEM
MIN DAT
HEATING FAN
MAIN
SETPOINT
SCHEDULE
SYSTEM
COMM
ADVANCED
Back
Enter
Exit
Back
Enter
Exit
SYSTEM
LOCAL OVRD TIME
FAN OFF DELAY
OCCUPIED FAN
MIN OFF TIME
STAGE DELAY
ECON ENABLE
MIN ECON DAMPER
SYSTEM
STAGE DELAY
ECON ENABLE
MIN ECON DAMPER
ECON ENABLE TEM
MIN DAT
DEHUM ENABLE
HEATING FAN
Back
Enter
Exit
3
Set the local override
time.
From the SYSTEM menu choose LOCAL OVRD
TIME to set the time the AppStat will hold an
override temperature setpoint as the active
setpoint. At the end of the period, the AppStat
will use either an occupied or unoccupied
setpoint as the active setpoint.
Back
Enter
Cncl
LOCAL OVRD TIME
2 60 mins
Set up roof top unit system options
Installation, Operation, and Application Guide for AppStat
Section 4: Commissioning functions
Revision G
53
Содержание BAC-4000 series
Страница 6: ...Contents KMC Controls Inc 6 Revision G ...
Страница 30: ...Section 2 Installing the AppStat KMC Controls Inc 30 Revision G ...
Страница 64: ...Section 4 Commissioning functions KMC Controls Inc 64 Revision G ...
Страница 112: ...Section 6 Application drawings KMC Controls Inc 112 Revision G ...
Страница 124: ...Section 7 System integration KMC Controls Inc 124 Revision G ...
Страница 128: ...power 28 roof top unit 98 rough in 18 Index KMC Controls Inc 128 Revision G ...