KMC Controls BAC-1xx63 Series Скачать руководство пользователя страница 3

BAC-1xx63 Series (6 Relays, 3 Analog Outputs)   

Installation Guide

Input Connections

Passive input devices require pull-up resistors in 

the circuit. For 

passive

 input devices (e.g., switch 

contacts and Type III 10K ohm thermistors) on IN2 

through IN4, set the pull-up switches on the back 

of the circuit board to the 

10K

 position. For 

active

 

voltage devices, set the switches to the 

0–12 VDC

 

position. (See Illustrations 3 and 4.)

NOTE:  Unlike the EOL switch pairs (1-2), the 

INPUT switch pairs (3-4, 5-6, and 7-8) 

must NOT have both switches set to the 

left or both set to the right

—if switch 3 is 

set to the left, for example, switch 4 must 

be set to the right (or vice versa).

 

ALL the 

input pull-up resistor switch pairs must 

be fully latched in either 10K Ohm or 

0–12 VDC positions even if a switch pair 

has no input connected!

 A single incorrect 

switch position may cause errors in mul-

tiple inputs.

NOTE: 

For 

more information on wiring specific 

applications (AHU, FCU, HPU, RTU), see 

the Applications section starting on page 

4.

 (These applications are the packaged 

programs selectable from the Advanced > 

Application menu in the BAC-1xx63C mod-

els.) See also the FlexStat Application Guide 

on 

www.kmccontrols.com

.

NOTE:  FlexStat inputs do not support 1K ohm 

RTDs. To use a 4–20 current loop input or 

map analog inputs as binary values, see the 

FlexStat Application Guide.

Output Connections

Connect the device under control between the desired 

output terminal and the related 

SC (Switched Com-

mon for relays) or GND (Ground for analog outputs)

 

terminal. (See Illustration 4). For the bank of three 

relays, there is one Switched (relay) Common connec-

tion (in place of the GND terminal used with analog 

outputs). (See Illustration 5).

  

Relay 3 

(or 6)

SC 1–3 

(or 4–6)

  Relay 2 

(or 5)

  Relay 1 

(or 4)

One Switched 
Common 
Connection 
Per Bank of 
Three 
Normally 
Open Relays

Illustration 5—Switched (Relay) Common and Relays

 CAUTION

Do not mistakenly connect 24 VAC to an analog 
output ground. This is not the same as a relay’s 
switched common. See the backplate’s terminal 
label for the correct terminal.

 CAUTION

Relays are for Class-2 voltages (24 VAC) only. Do not 
connect line voltage to the relays!

Do not attach a device that draws current exceeding 

the FlexStat’s output capacity:
•  Maximum output current

 for individual 

ANA-

LOG outputs (7–9) is 20 mA @ 12 VDC (each).

•  Max. output current is 1 A for individual 

RELAYS @ 24 VAC/VDC or a total of 1.5 A per 

bank of 3 relays

 (relays 1–3 and 4–6).

For example, KMC REE-3111/3112 relays could 

be connected to the analog outputs, but 

REE-

3211/3221/3213 relays would exceed the FlexStat’s 

analog output capacity

 (although the REE-3211 can 

be used with the FlexStat’s internal relays 1–6 as 

shown in the following applications pages).
FlexStat relays 1–6 are 

NO, SPST (Form “A”)

. (To 

emulate binary outputs with the analog outputs, set 

the output voltage to be either 0 or 12 VDC

 in Control 

Basic

.)

Содержание BAC-1xx63 Series

Страница 1: ...t windows air vents and air circulation obstructions e g curtains furniture See the Application Guide for more information Additionally for a model with an occupancy sen sor option be sure to install it where it will have unobstructed view of the most typical traffic area see the Application Guide for more information If replacing an existing thermostat label wires as needed for reference when rem...

Страница 2: ...six conductor and outputs e g 12 conduc tor is recommended Grounds for all the inputs can be combined on one wire CAUTION To avoid damage from ground loops and other communication issues in networked FlexStats correct phasing on MS TP network and power connections on ALL the networked controllers is critically important MS TP Wiring Connect the A terminals in parallel with all other A terminals on...

Страница 3: ...plication Guide Output Connections Connect the device under control between the desired output terminal and the related SC Switched Com mon for relays or GND Ground for analog outputs terminal See Illustration 4 For the bank of three relays there is one Switched relay Common connec tion in place of the GND terminal used with analog outputs See Illustration 5 Relay 3 or 6 SC 1 3 or 4 6 Relay 2 or 5...

Страница 4: ...ower Connection The FlexStat requires an external 24 volt AC power source Use a KMC Controls Class 2 transformer to supply power Connect the transformer s neutral lead to the 24 VAC Common C terminal and the AC phase lead to the 24 VAC Phase R terminal See Illustration 4 Power is applied to the FlexStat when the transformer is plugged in KMC Controls recommends powering only one con troller thermo...

Страница 5: ...lso have MAT OAT inputs typically 10K Type III thermistors Ensure pull up resistor switch positions are set properly see Illustration 3 on page 2 Fan Status FST or Discharge Air Temperature DAT is an optional selectable input Ensure pull up resistor switch positions are set properly 10K position for the relay switch or Type III thermistor Output Terminals AHU Output Connections Modulating BACnet O...

Страница 6: ...inals 1 3 Relay 2 O B Reversing Valve see O B Note in schematic BO2 Relay 1 G Fan BO1 If optional Outside Air Damper is used must also have MAT OAT inputs Input Terminals HPU Input Connections BACnet Objects IN4 Opt Outside Air Temp OAT AI4 IN3 Opt Mixed Air Temp MAT AI3 GND Ground IN2 Optional FST or DAT AI2 When using optional Outside Air Damper must also have MAT OAT inputs typically 10K Type I...

Страница 7: ...AT inputs typically 10K Type III thermistors Ensure pull up resistor switch positions are set properly see Illustration 3 on page 2 Fan Status FST or Discharge Air Temperature DAT is an optional selectable input Ensure pull up resistor switch positions are set properly 10K position for the relay switch or Type III thermistor Output Terminals Typical Terminal Codes RTU Output Connections 1 or 2 H a...

Страница 8: ...DAT is an optional selectable input Ensure pull up resistor switch positions are set properly 10K position for the relay switch or Type III thermistor Output Terminals BAC 1xxx63C FCU Output Connections BACnet Objects 2 Pipe 4 Pipe Analog 9 AO9 GND Ground for analog output terminals 7 9 Analog 8 Heat Valve Proportional HTV AO8 Analog 7 Valve Proportional VLV Cool Valve Proportional CLV AO7 Relay 6...

Страница 9: ... 6311 050 Transformer STE 1454 Temp Sensor 2 PIPE 2 POSITION FCU OPTION XEE 6311 050 Transformer VEP 1xxx0186 VEZ 4xxxxMBx Valve with 24 VAC Actuator BRN VEPSeries or RED VEZ Series BLU VEPSeries or BLK VEZ Series STE 1454 Temp Sensor NOTE See the FCU Overview section on the previous page for the 4 Pipe Modulating option and the general schematic Additional Resources The latest support files are a...

Отзывы: