KMB SML 133 230 X/5A Скачать руководство пользователя страница 1

                                                                                                                         KMB systems, s.r.o.

                                                                                     Dr. M. Horákové 559, 460 06 Liberec 7, Czech Republic
                                                                                              tel. +420 485 130 314, fax +420 482 736 896
                                                                                              email : 

[email protected]

, internet : www.kmb.cz

SML 133 

Multifunctional Meter

Operating Manual

Firmware 2.0.32

The instrument measures line and phase voltages, currents, active, reactive and apparent powers, 
power factors, THD and harmonics of voltages and currents, as well as frequency in single-phase and 
three-phase low, medium and high voltage power systems.
Built-in electricity meter measures electric energy in four quadrants (both active and reactive 
energies), as well maximum active power demand.
The instrument further allows informative measurement of temperatures within a switchboard cabinet 
using an inbuilt temperature sensor.
Besides actual values, average values during preset time window are evaluated too. Maximum and 
minimum values of them are registered.
The instrument feature three voltage and three fully isolated current measuring inputs.
Nominal range of the voltage inputs can be in range from 57.7/100 up to 400/690 V

AC

,optionally.

The current inputs are designed for indirect measurement only - they must be connected via external 
current transformers. The models with current-type inputs are available as either the „X/5A“, i.e. with 5 
A

AC

 nominal range (for standard CTs), or the „X/100mA“ with nominal range of 0.1 A

AC

. The „X/333mV“ 

models are determined either for CTs with output nominal voltage of 333 millivolts or for flexible 
current sensors (Rogowski coils) with embedded integrator and appropriate output voltage. Such 
models are equipped with auxiliary power supply of 5V for the sensors.
The instrument can be optionally equipped with two relays with programmable function or solid-state 
outputs that can be used as electricity meter impulse outputs and one digital input for general state 
monitoring.
Power supply of standard instrument models has universal range 85 ÷ 275 V

AC

 or 80 ÷ 350 V

DC. 

Optional power supply range is 12 ÷ 48 V

DC.

The instruments can be equipped with an RS 485, Ethernet or M-Bus communication interface. Then 
the ENVIS software allows remotely viewing data measured. For custom design systems, the Modbus 
communication protocol can be used too.

5 / 2016

Содержание SML 133 230 X/5A

Страница 1: ...be in range from 57 7 100 up to 400 690 VAC optionally The current inputs are designed for indirect measurement only they must be connected via external current transformers The models with current t...

Страница 2: ...ing positions however must be clearly marked In case of DC supply voltage the polarity of connection is generally free but for maximum electromagnetic compatibility the grounded pole should be connect...

Страница 3: ...n with current transformers with output nominal voltage of 333 millivolts They can be also used with flexible current sensors Rogowski coils with embedded integrator of appropriate voltage output sign...

Страница 4: ...0 1 A First off all it is necessary to switch display from measured data branch the ULN screen on the example below to the parameter branch with the button The branch is indicated with the symbol Para...

Страница 5: ...Only actual values of harmonics and electrical energy are available These values are arranged in different way see further below If any of actual values of voltages or currents flashes corresponding...

Страница 6: ...ctrum Values Branch PF PF P P Q Q Fundamental Harmonic Values Branch cos tan cos tan act values only Pfh Pfh Qfh Qfh see the next figure for details fundamental harmonic branch indicated with the H ch...

Страница 7: ...H symbol is displayed for the fundamental harmonic branch Exception Actual values only of fundamental harmonic power factor the cos are evaluated no average values available Next this fundamental harm...

Страница 8: ...easured Data Navigation Chart When you scroll to one of this rows THD values of all measured phases are displayed as default Symbols THD V LN or THD A indicate phase voltage or current THD values resp...

Страница 9: ...ss of the method of standard average values described above The quantity is marked with the E letter to distinguish from the standard maximum average quantities Similarly as the energies the value can...

Страница 10: ...ress the key As default parameter group 01 is displayed and symbol wrench indicates that setup data are displayed now The parameters are arranged in groups numbered from 00 up The number of group is d...

Страница 11: ...od for PavgmaxE line 3 Electricity meter display mode 0 01 60 1 sec 60 mins 4E Pmax 8E 15 min 4E Pmax floating window type averaging method applied 09 fund harmonic PF display format cos tan fi cos 10...

Страница 12: ...ndard average maximums minimums electricity meter energies EP EP etc and electricity meter maximum power demand PavgmaxE can be cleared After being put in operation such operations can be locked disab...

Страница 13: ...3 4 6 3 4 5 so the same value is shown at the end as at the beginning 4 Press the The flashing number is replaced with O P n indicating unlocked state The digit shown while entering the unlocking key...

Страница 14: ...y and evaluated every 10 seconds The fundamental frequency output is the ratio of the number of integral mains cycles counted during the 10 second time clock interval divided by the cumulative duratio...

Страница 15: ...2 as harmonic sub groups Hsg Following quantities are evaluated Harmonic components of voltage and current up to 50th order Uih1 Iih1 i order of harmonic component Absolute angle of voltage harmonic...

Страница 16: ...3 2 1 Qfh Qfh Qfh Qfh Fundamental harmonic three phase power factor cos cos Pfh Qfh arctg Powers and power factors of the fundamental harmonic component cos are evaluated in 4 quadrants in compliance...

Страница 17: ...luation is used to obtain values for displaying and recording 2 3 1 Actual Values Evaluation and Aggregation Actual instantaneous values of measured quantities that can be viewed on instrument s displ...

Страница 18: ...xE in the Electricity Meter group separate parameter is used see below 2 3 3 Embedded Electricity Meter For the electric energy measurement a stand alone functional unit an electricity meter is implem...

Страница 19: ...maximum PavgmaxE is The averaging method if fixed the floating window type The averaging period can be set in range from 1 to 60 minutes The maximums can be cleared independently of standard average m...

Страница 20: ...same way as at standard digital outputs The behaviour of digital outputs can be programmed according to requirements as pulse output transmitting electricity meter standard output e g as a simple two...

Страница 21: ...signal polarity for the V models must be kept accordng the table above and for the RR RI II models it is free If the voltage exceeds declared level the input is activated value 1 If the first input is...

Страница 22: ...2 5 pulses kvarh energy EQL due to symbol By setting any of the O1 02 outputs from the instrument panel corresponding alarm light A1 A2 is set in the same way automatically too Then the O1 O2 activity...

Страница 23: ...with which you can add conditions or actions into the clause Even if no I O action is set the I O Management folder contains one empty clause template with the buttons prepared for new clause definit...

Страница 24: ...s not any counter but a frequency controlled quantity Select an empty clause and add the Frequency Counter action In the Properties field below you can set name of the quantity for example Vwind unit...

Страница 25: ...o the output switches on off depending on the polarity setup temporary for preset pulse width only when the condition result changes from false 0 to true 1 I O Setup Standard Digital Output Action Pro...

Страница 26: ...on part of target clause and choose the Digital Input option Then you must set desired Digital Input Direct or Inverted if the Direct the condition gets value true logical 1 when the input is activate...

Страница 27: ...e device monitors and evaluates the digital input and controls all of outputs 3 4 1 Pulse Output After the pulse function mode is set every 200 milliseconds the instrument executes evaluation of the m...

Страница 28: ...special shielded communication cable with twisted pairs and a defined wave impedance usually about 100 Ohm Use one pair for the A and B signals and the second pair for the G signal 4 1 1 2 Terminating...

Страница 29: ...cription can be found in the Description of Communication Protocol manual available on www kmbsystems eu 4 2 3 M Bus Communications Protocol Standard setup for this interface is address 1 communicatio...

Страница 30: ...rograms is used to set up the instruments downloading actual measured data and to data visualization and archiving on a supervising PC Detailed operation description can be found in manuals of the pro...

Страница 31: ...33 Operating Manual 5 Examples of Connections SML133 U 230 X 5A Connection with 5A Nominal Output CTs TN Network Direct Star 3Y Connection SML133 U 230 X 333mV Connection with 333 mV Nominal Output CT...

Страница 32: ...30 X 333mV Connection with 333 mV Nominal Output Rogowski Current Sensors Equipped with Embedded Integrators SML133 X 5A Measured Signal Connection Examples 32 TN Network Direct Star 3Y Connection IT...

Страница 33: ...3 TN Network Star 3Y Connection via VT IT Network Delta 3D Connection via VT VT to Line to Neutral Primary Voltage IT Network Delta 3D Connection via VT VT to Line to Line Primary Voltage IT Network D...

Страница 34: ...Manual SML133 Power Supply Options SML133 RI Digital I O Connection Example 34 Line to Neutral Voltage AC Power Supply Line to Line Voltage AC Power Supply DC Power Supply NOTE MAXIMUM AVAILABLE VOLTA...

Страница 35: ...SML133 Operating Manual SML133 V Digital I O Connection Example SML133 4 RS 485 Communication Link Connection 35...

Страница 36: ...tive pole of 5V aux supply for current sensors valid for X 333mV models Numbering of Terminals I O RR RI II models V models signal terminal No signal terminal No O1A 15 O1 41 O1B 16 O2 42 O2A 17 12 43...

Страница 37: ...SML133 Operating Manual 6 Manufactured Models and Marking 37...

Страница 38: ...8 AAC 2 ULN line to neutral voltage 0 2 40 280 VAC ULL line to line voltage 0 2 70 480 VAC PFA PFV power factor 0 5 0 1 Pst Plt flicker Udip voltage dips Uswl voltage swells Utr transients overvoltage...

Страница 39: ...0 2 0 005 18 AAC 2 ULN line to neutral voltage 0 2 0 2 1 2 UNOM ULL line to line voltage 0 2 0 2 1 2 UNOM v3 PFA PFV power factor 0 5 0 1 Pst Plt flicker Udip voltage dips Uswl voltage swells Utr tran...

Страница 40: ...ed 0 2 0 001 0 36 AAC 2 ULN line to neutral voltage 0 2 0 2 1 2 UNOM ULL line to line voltage 0 2 0 2 1 2 UNOM v3 PFA PFV power factor 0 5 0 1 Pst Plt flicker Udip voltage dips Uswl voltage swells Utr...

Страница 41: ...I 600V CATII permanent overload 300 VAC 600 VAC 1000 VAC peak overload UL N 1 sec 600 VAC 1200 VAC 2000 VAC burden power impedance 0 013 VA Ri 1 8 M 0 025 VA Ri 3 6 M 0 05 VA Ri 6 M Voltage Unbalance...

Страница 42: ...AAC 15 VAC peak overload for 1 second max repetition frequency 5 minutes 70 AAC 10 AAC 15 VAC burden power impedance 0 5 VA Ri 10 m 0 01 VA Ri 40 m 3 uVA Ri 100k Current Unbalance measuring range 0 1...

Страница 43: ...ers for both active and reactive energies active energy uncertainty class 0 5S acc to EN 62053 22 reactive energy uncertainty class 2 acc to EN 62053 23 Instrument Characteristics according to IEC 615...

Страница 44: ...Type Outputs solid state opto MOS RR RI II Models V Models typ Opto MOS bipolar Opto MOS unipolar load rating 60 VAC 100 VDC 100 mA dynamic param pulse output pulse duration gap duration maximum freq...

Страница 45: ...N 61000 4 6 3 V EN 61000 4 11 5 periods EMC emissions EN 55011 class A EN 55022 class A not for home use remote communication port option RS 485 2400 460800 Bd protocols KMB Modbus RTU or Ethernet 100...

Страница 46: ...the product If a warranty repair is claimed the warranty certificate must be sent in In case of an out of warranty repair you must enclose an order for the repair Warranty Certificate Warranty period...

Отзывы: