39
CIRCUIT BOARD PARAMETERS
THE PARAMETERS MEMORISED ON THE CIRCUIT BOARD ARE FUNDAMENTAL FOR THE CORRECT
FUNCTIONING OF THE BOILER.
THE PARAMETERS GIVEN BELOW ARE ALREADY MEMORISED IN THE BOILER INSPECTION PHASE
DIRECTLY IN THE FACTORY.
THESE PARAMETERS ARE THE RESULT OF CAREFUL TESTS WITH VARIOUS TYPES OF
PELLETS AND MUST NOT BE CHANGED WITHOUT THE AUTHORISATION OF KLOVER srl, SO
AS NOT TO JEOPARDISE BOILER FUNCTIONING.
ALL RESPONSIBILITIES ARE DECLINED FOR DAMAGE CAUSED BY INCORRECT
INTRODUCTION OF THE PARAMETERS.
“Various calibrations” (Menu M – 9 – 4)
Parameter
Menu level
Description
Display writing
Measurement
Value field
Database o0
Pr38
M
– 9 – 4 – 01
Re-ignition block
RE-IGNIT BLOCK
Minutes
0
– 10
6
Pr39
M
– 9 – 4 – 02
Flue gas intake device switch-off time
MIN-INT OFF
Minutes
0
– 20
10
Pr40
M
– 9 – 4 – 03
Pre-load time in ignition
IGNIT- PRE-LOAD
Seconds
0
– 225
85
Pr41
M
– 9 – 4 – 04
Stand-by time after pre-load
AFTER-PRE STAND-BY
Seconds
0
– 255
190
Pr42
M
– 9 – 4 – 05
Intake device speed in pre-load phase
PRELOAD FLUE GAS-
INTAKE DEVICE
Revs/min
350
– 2800
2100
Pr43
M
– 9 – 4 – 06
ON/OFF Temperature hysteresis on
“SET H2O”
and
“SET DHW”
DELTA ON OFF AUTO
°C
0
– 20
5
Pr44
M
– 9 – 4 – 07
Delay to economy switch-off (timer after
reaching
“SET H2O”
)
DELAY-OFF AUTO
Minutes
2
– 120
30
Pr45
M
– 9 – 4 – 08
Power change delay
POWER CHANGE
Seconds
0
– 60
20
Pr46
M
– 9 – 4 – 09
ON/OFF Temperature hysteresis on
“SET ROOM”
DELTA ON AUTO
°C
0
– 15
2
Pr47
M
– 9 – 4 – 10
Keypad block enabling
KEYS BLOCK-EN
On
– off
On
– off
Off
Pr48
M
– 9 – 4 – 11
Automatic re-ignition after black-out
BLACK OUT RE-
IGNITION
Seconds
0
– 60
30
Pr49
M
– 9 – 4 – 12
Pellet level sensor enabling
PELLET RESERVE
On
– off
On
– off
On
Pr50
M
– 9 – 4 – 13
Pump ignition for over-temperature
safety
PUMP SAFETY
°C
60 - 90
83