STRONA 1 

Automatyka: sterownik automatyki do central EVO-T i EVO-T COMPACT

DOKUMENTACJA 

TECHNICZNO 

-RUCHOWA

OPERATION AND 

MAINTENANCE 

MANUAL

PAGE 55 

Automation: controller for EVO-T and EVO-T COMPACT units

EVO -T;  EVO -T  COMPACT

AUTOMATYKA:  STEROWNIK

ТЕХНИКО 

-ЭКСПЛУАТАЦИОННАЯ 

ДОКУМЕНТАЦИЯ 

СТР. 95 

Автоматизация: контроллер для 

УСТАНОВОК

 EVO-T и EVO-T COMPACT

DTR EVO-T_CTRL-061.0.0    2021

KLIMOR zastrzega sobie prawo do wprowadzania zmian      KLIMOR reserves the rights to introduce alteration without prior 
notice     KLIMOR оставляет за собой право на внесение изменений   

Содержание HMI Compact

Страница 1: ...ION AND MAINTENANCE MANUAL PAGE 55 Automation controller for EVO T and EVO T COMPACT units EVO T EVO TCOMPACT AUTOMATYKA STEROWNIK 95 EVO T EVO T COMPACT DTR EVO T_CTRL 061 0 0 2021 KLIMOR zastrzega s...

Страница 2: ...azowieckie dzkie 48 58 700 94 69 48 58 700 94 69 48 781 300 714 48 781 300 714 Serwis Klimor Region Serwis Klimor Region IV IV wojew dztwa wielkopolskie dolno l skie opolskie l skie wojew dztwa wielko...

Страница 3: ...RL Sterownik automatyki do central EVO T i EVO T COMPACT DOKUMENTACJA TECHNICZNO RUCHOWA WERSJA POLSKA KLIMOR zastrzega sobie prawo do wprowadzania zmian zaawansowane rozwi zania klimatyzacyjne iwenty...

Страница 4: ...acja Bacnet MS TP z systemem BMS 32 5 3 Sterowanie przez stron www 32 5 4 Lista adres w falownik w EVO T 33 6 PANEL STERUJ CY HMI 34 6 1 Panel steruj cy HMI COMPACT 34 6 1 1 Dane techniczne 34 6 1 2 O...

Страница 5: ...odzielnego do o enia karty 1 6 7 8 9 10 2 3 4 5 Rys Nr 1 Widok sterownika 1 Wyj cie RS485 Master do komunikacji z BMS 2 Wyj cie RS485 Slave do komunikacji z falownikami 3 Wyj cia analogowe Aou1 3 0 10...

Страница 6: ...4 AUTOMATYKA STEROWNIK AUTOMATYKI DO CENTRAL EVO T EVO T COMPACT DOKUMENTACJA TECHNICZNO RUCHOWA 1 2 Przyk adowepod czeniewej wyj sterownika Rys Nr 2 Przyk adowe pod czanie urz dze do sterownika...

Страница 7: ...ka wentylatora nawiewu went EC EBM zwarty A_SupFC Din 10 Alarm falownika wentylatora wywiewu went EC EBM zwarty A_ExhFC Din 11 Presostat filtra dodatkowego elektro statycznego nawiewu opcja zwarty A_S...

Страница 8: ...SECS 36 0 0 0 4 32 Nazwa Funkcja EH WH WC DX MX KOD Numer SECS 34 34 0 2 0 0 32 SECS 36 0 0 0 4 32 SECS 37 1 0 0 4 32 SECS 38 0 2 0 4 32 SECS 40 0 0 8 0 32 SECS 41 1 0 8 0 32 SECS 42 0 2 8 0 32 PRCS P...

Страница 9: ...r Ti Odpowiednio wykonany dob r nastaw regulator w PI praca centrali na wydajno ci okre lonej w karcie tech nicznej centrali odpowiedni dob r element w centrali zalecane sterowanie analogowe ka dego z...

Страница 10: ...yst puje aden z alarm w blokuj cych prac uk adu jest zwarty sygna S1 stop serwisowy na wej ciu DIN12 sterownika jest zwarty sygna S1F ppo na wej ciu DIN1 sterownika oraz parametr Ustaw tryb pracy na z...

Страница 11: ...do Menu Alar m w i na wybranym alarmie przytrzyma d u ej klawisz OK Je eli r d o alarmu nadal wyst puje to alarm si utrzyma a przy jego opisie pojawi si symbol co oznacza e alarm zosta potwierdzony J...

Страница 12: ...ny zabrudzenie dopuszczalne r nica ci nie przed i za filtrem jest poni ej nastawionej na presostacie na wej ciu cyfrowym nie ma sygna u 24VAC Stanalarmowy zabrudzenie niedopuszczalne r nica ci nie prz...

Страница 13: ...n b du po usuni ciu przyczyny nale y potwierdzi alarm i uruchomi uk ad Wej cieczujnikowePT1 A_Texh Blokuj cy Badanieprawid owejpracyczujnikatemperaturywywiewu Stannormalny niewyst pujealarm czujnikpod...

Страница 14: ...n alarmowy sterownik nie reaguje na fizyczne zmiany wej cia emulowanego uk ad pracuje z warto ci z emu latora w menu serwisowym A_Out Force Zanikaj cy Forsowaniewyj Stannormalny nie wyst puje alarm ad...

Страница 15: ...a PONIEDZIA EK PONIEDZIA EK NOWY NOWY OK OK OK STRZA KA W PRAWO C C C C CZAS OD 08 00 00 CZAS OD 16 00 00 USTAW TRYB PRACY 3 BIEG USTAW TRYB PRACY STOP ZAPISZ ZAPISZ Rys Nr 7 Ustawienie trybu pracy PO...

Страница 16: ...regulacja temperatury nast puje wg czujnika temperatury wiod cej i nastawy temperatury z menu g wnego Czujnik wiod cy czuwania HMI CON Wywiew za czenie uk adu do pracy wzgl dem czujnika temperatury wy...

Страница 17: ...iczony z ci nienia i wsp czynnika K Przep yw zadany 3 bieg zadana warto przep ywu powietrza panuj cego w cz ci wywiewnej dla pracy na 3 biegu prze liczony z ci nienia i wsp czynnika K Parametr K wsp c...

Страница 18: ...alniania wzmocnienie regulatora funkcji przeciwoszronieniowej 30s Ti_zwalniania sta a ca kowania regulatora funkcji przeciwoszronieniowej Odszranianie wymiennika obrotowego 50 Nawiew stopie wysterowan...

Страница 19: ...Styk alarmowy mo liwo wyboru typu styku alarmowego agregatu ch odniczego NO NC Nieaktywny II stopie mo liwo aktywacji II stopnia ch odzenia Nieaktywna Kaskada mo liwo aktywacji kaskadowego sterowania...

Страница 20: ...CS SCS centrale wentylacyjne nawiewne SECS centrale wentylacyjne nawiewno wywiewne RGCS centrale wentylacyjne nawiewno wywiewne z odzyskiem glikolowym PRCS centrale wentylacyjne nawiewno wywiewne z od...

Страница 21: ...lny adres 1 Nawiew 0 10V Nieaktywne Nieaktywne wyj cia analogowe spe niaj funkcje opisane w pkt 1 2 Aout1 na wyj ciu analogowym Aout1 jest sygna 0 10V wentylatora nawiewu Aout2 na wyj ciu analogowym A...

Страница 22: ...i wy wietlenie alarmu A_StopS1 u ywane gdy funkcj wej cia DIN12 jest stop serwisowy ON OFF rozwarcie wej cia DIN12 spowoduje zatrzymanie uk adu bez wy wietlenie alarmu A_StopS1 u ywane gdy funkcj wej...

Страница 23: ...na zworkach pod spodem sterow nika Domy lne parametry komunikacji pr dko transmisji 9600 bps mo liwo zmiany z pozio mu nabudowanego lub zewn trznego HMI 8 bit w ramki 2 bity stopu brak parzysto ci Ws...

Страница 24: ...apisu pojedynczego rejestru 16 bitowego w prze strzeniach adresowych 0x1000 0x4000 W tym wypadku nale y zapisywa rejestry parami komend Preset Multiple Registers 0x10 na kt r sk ada si pe na warto 32...

Страница 25: ...RS485 Obroty silnika EC wentylatora nawiewu 2 1rpm 256 22rpm 22 256 5632 0x1600 AV Register R 40 80 Usup2 RS485 Napi cie wyj cia falownika lub napi cie DC silnika EC wentylatora nawiewu 2 1V 256 22V...

Страница 26: ...ienie za czenia went wzgl dem przepustnic 1s 256 22s 22 256 5632 0x1600 AV Register R W 84 168 DelThr Op nienie wy aczenia przepustnic 1s 256 22s 22 256 5632 0x1600 AV Register R W 85 170 PresDel Op n...

Страница 27: ...Xproc Udzia w regulacji temperatury komory mieszania 1 256 22 22 256 5632 0x1600 AV Register R W 128 256 h_c_proc Udzia w regulacji temperatury nagrzewnicy ch odnicy 1 256 22 22 256 5632 0x1600 AV Reg...

Страница 28: ...regulatora temperatury wody powrotnej nagrzewnicy 1 256 22 22 256 5632 0x1600 AV Register R W 166 332 TiBack Sta aca kowaniaregulatoratemperaturywodypowrotnejnagrzewnicy 1s 256 22s 22 256 5632 0x1600...

Страница 29: ...nastawy temperatury zadanej dotyczy zmiany Tset z menu lub kalendarza 1s 256 22s 22 256 5632 0x1600 AV Register R W 207 414 AirRegSensor Czujnik jako ci powietrza 0 nieaktywny 1 CO2 2 LZO 4 PM2 5 8 PM...

Страница 30: ...Psup1 Wysterowanie min wentylatora nawiewu skala 1 256 22 22 256 5632 0x1600 AV Register R W 248 496 Phe1 Moc minimalna NE dla Psup1 skala 1 256 22 22 256 5632 0x1600 AV Register R W 249 498 Psup2 Wy...

Страница 31: ...go 4 0 rozwarte 1 zwarte MSV Coil 9408 R 295 590 _DIN5 Odczyt stanu wej cia cyfrowego 5 0 rozwarte 1 zwarte MSV Coil 9440 R 296 592 _DIN6 Odczyt stanu wej cia cyfrowego 6 0 rozwarte 1 zwarte MSV Coil...

Страница 32: ...1 C 256 22 C 22 256 5632 0x1600 AV Register R W 347 694 Em_PT3 Emulacja wej cia czujnika PT1000 3 0 nieaktywna 1 aktywna MSV Coil 11104 R W 348 696 E_PT3 Warto emulowana wej cia czujnika PT1000 3 1 C...

Страница 33: ...brak alarmu 1 wyst puje alarm BV Coil 12416 R 389 778 A_SupFilterES Alarm brudnego filtra elektrostatycznego 0 brak alarmu 1 wyst puje alarm BV Coil 12448 R 390 780 A_ExhFilter Alarm brudnego filtra...

Страница 34: ...komputera dla protoko uTCP4 2 Nast pnie uruchomi przegl dark internetow i wpisa domy lny adres sterownika 192 168 0 8 Poka e si okno gdzie nale y wpisa domy lny login admin i has o admin Rys Nr 11 Okn...

Страница 35: ...ze z routera WIFI ste rownika port 80 z ip 10 10 10 31 na zewn trzny ip port 80 ip 83 100 100 1 Rys Nr 17 W czenie sterownika do lokalnej sieciWIFI z udost pnieniem na zewn trz Router z przekierowanie...

Страница 36: ...sp praca ze sterownikami z serii ELP protok BACnet MS TP lub Modbus wbudowany czujnik temperatury temperatura przechowywania 20 70 C stopie ochrony IP 30 Rys Nr 18 6 1 2 Opis z cza Rys Nr 19 6 1 3 Mon...

Страница 37: ...undy na li cie alarm w 6 1 6 Ekrany HMI Compact Rys Nr 22 6 1 7 Menu HMI G wne strony HMI wyst puj w zale no ci od typu sterow nika oraz jego aplikacji S to domy lne ekrany pojawiaj ce si jako pierwsz...

Страница 38: ...zawiera dwa typy element w w ze oraz parametr W z y s punktami wej cia w zag bienie menu Parametry zawieraj warto ci kt re mo na odczytywa a niekt re z nich r wnie modyfikowa Wej cie w zag bienie menu...

Страница 39: ...tings HMI COM SETTINGS ustawienia zadajnika HMI MAC address Adres zadajnika HMI Instance Unikalny numer urz dzenia w sieci Bus mode Tryb pracy magistrali Mo liwo wyboru sposobu komunikacji ze sterowni...

Страница 40: ...zechowywania 20 70 C Stopie ochrony IP 30 Wymiary 126 x 87 x 16 mm 6 2 2 Schemat pod czenia panelu HMI TP do sterownika Rys Nr 28 HMI TP7 Napi cie zasilania 24 V AC DC 10 Pob r mocy max 3W Pob r mocy...

Страница 41: ...na praw Panel HMI TP posiada swoje wewn trzne ustawienia Aby w nie wej nale y jednocze nie wcisn dowolne 3 punkty na ekranie i przytrzyma przez czas oko o 3s 6 2 5 Menu HMI TP Przej cie z ekranu g wn...

Страница 42: ...na odczytywa a niekt re z nich r wnie modyfikowa Wej cie w zag bienie menu lub przej cie do edycji parame tru dokonuje si naciskaj c klawisz OK Naci ni cie klawisza C powoduje wycofanie si z zag bieni...

Страница 43: ...budowany czujnik Menu skin Sk rka menu Mo liwo wybrania jednego z kilku wygl d w menu Ustawienia komunikacji Communication settings HMI COM SETTINGS ustawienia zadajnika HMI MAC address Adres zadajnik...

Страница 44: ...skali sy gna u 0 10V Dzi ki takiemu rozwi zaniu jeden sygna 0 10V mo e s u y np do sterowania dwoma wielostopniowymi nagrzewnicami elektrycznymi R nica N P2 P1 nie mo e by mniejsza ni 10 na ka dy wyb...

Страница 45: ...terownicy centrali wentylacyjnej oraz modu u HE Na sterowniku modu u HE ustawi ilo stopni nagrzew nicy Sprawdzi funkcjonowanie uk adu Uruchomienie nagrzewnicy jest bezwzgl d nie blokowane przez termos...

Страница 46: ...COMPACT DOKUMENTACJA TECHNICZNO RUCHOWA 8 PROTOK URUCHOMIENIA DATA MIEJSCOWO IMI I NAZWISKO URUCHAMIAJ CEGO NUMER FABRYCZNY URZ DZENIA FIRMA URUCHAMIAJ CA PIECZ CZYNNO CI INSTALACYJNE OPIS UWAGI POTWI...

Страница 47: ...45 NOTATKI...

Страница 48: ...SERWIS SERVICE 48 587839954 48 500087227 serwis klimor com...

Страница 49: ...ON AND CONTROLLER FOR UNITS EVO T EVO T COMPACT OPERATION AND MAINTENANCE MANUAL ENGLISH VERSION KLIMOR reserves the rights to introduce alteration without prior notice advanced airconditioning andven...

Страница 50: ...m 65 5 2 Bacnet MS TP communication with the BMS system 79 5 3 Control via WWW 79 5 4 List of EVO T inverter addresses 80 6 CONTROL PANEL 81 6 1 HMI COMPACT Control Panel 81 6 1 1 Technical data 81 6...

Страница 51: ...e card on your own Fig1 Controller view 1 6 7 8 9 10 2 3 4 5 11 1 RS485 Master output for communication with BMS 2 RS485 output Slave for communication with inverters 3 Analog outputs Aou1 3 0 10VDC 4...

Страница 52: ...50 AUTOMATION AND CONTROLLER FOR UNITS EVO T EVO T COMPACT OPERATION AND MAINTENANCE MANUAL 1 2 ExampleofcontrollerIN OUTconnection Fig 2 Example of controller IN OUT connection...

Страница 53: ...in 8 Defrost signal from the reversing unit shorted A_ DefFunc Din 9 Supply fan inverter fan EC EBM alarm shorted A_SupFC Din10 Exhaust fan inverter fan EC EBM alarm shorted A_ExhFC Din11 Additional e...

Страница 54: ...Name function WH EH WC DX MX Code No SECS 36 0 0 0 4 32 SECS 37 1 0 0 4 32 SECS 38 0 2 0 4 32 SECS 40 0 0 8 0 32 SECS 41 1 0 8 0 32 SECS 42 0 2 8 0 32 PRCS PRCS 0 0 0 0 0 0 0 0 0 0 0 0 PRCS PRCS 1 1...

Страница 55: ...o performance determined in the AHU specification sheet appropriate selection of AHU components recommended analog control of each heat cool exchanger system operation at a premise with no sudden temp...

Страница 56: ...on air quality If you change your app be sure to restore the sys tem to the factory state Service Menu Factory Reset in advance The system is started if There is no alarm blocking system operation S1...

Страница 57: ...he control system In order to reset an alarm access the Alarm menu and hold OK key at the selected alarm If an alarm source is still present then the alarm will be preserved and the symbol appears at...

Страница 58: ...level pressure difference downstream and upstream the filter is lower than the one set on the pressure gauge no 24VAC signal at digital input Alarm condition unacceptable contamination level pressure...

Страница 59: ...or after removing the cause confirm the alarm and start the system Sensor input PT1 A_Texh Blocking Air exhaust temperature sensor operation inspection Normalcondition no alarm sensor connected Alarmc...

Страница 60: ...ding the allowed operating time of UV lamps Normalcondition noalarm UVlampruntimeislowerthantheli mit set in Service Menu RunningTimer A_UV_LampTime Limit Alarmcondition alarm occurs UV lamp operating...

Страница 61: ...yout number for the HMI Multi function which allows you to manage multiple EVO_T from a single HMI touch panel Main menu Selection of the AHU operation mode requested temperature of the master sensor...

Страница 62: ...e is the air supply sensor and the HPM module can operate in heating mode Standby mode Temperature setting 22 C Temperaturesetting settemperaturesetttingofthestandbymodemastersensor howevertemperature...

Страница 63: ...in 1 gear converted from pressure and K factor Airflow setpoint 2 gear setpoint value of airflow in the exhaust part for operation in 2 gear converted from pressure and K factor Airflow setpoint 3 gea...

Страница 64: ...temperature and the water return temperature if B8 sensor is activated Active Drop ramp possibility to activate deactivate the drop ramp for valve opening stage after primary heating 30s Drop time aft...

Страница 65: ...rding to the refrigerating unit OMM 30s Min operation time minimal operation time of the refrigerating unit Enter set point according to the refrigerating unit OMM 10 C Min external operation temp min...

Страница 66: ...r supply temperature setting low temperature alarm triggers delay setting Active Air exhaust sensor Active operation of the system with an air exhaust temperature sensor Inactive operation of the syst...

Страница 67: ...the inverter can be freely chosen when the settings are loaded Pressure guage Recovery sensor Pressure guage protection against freezing of recovery by means of a pressure switch placed in the recover...

Страница 68: ...ce in the HMI multi function the maximum number of controllers operated from one referencing device is 16pcs the controllers and the panel should be connected in the serial topology RS485 with a high...

Страница 69: ...0 67 is shown as 2067 0x4000 0x5000 similar to the area 0x0000 0x1000 but the variables are treated as 16 bit values This means that older 16 bits are not taken into account Addresses should be divide...

Страница 70: ...temperature 1 C 256 22 C 22 256 5632 0x1600 AV Register R 15 30 B3 Outdoor temperature 1 C 256 22 C 22 256 5632 0x1600 AV Register R 16 32 B4 Exhaust air temperature behind recovery 1 C 256 22 C 22 2...

Страница 71: ...requency of the exhaust fan inverter 2 1Hz 256 22Hz 22 256 5632 0x1600 AV Register R 51 102 RPMexh2 RS485 Exhaust EC fan motor speed 2 1rpm 256 22rpm 22 256 5632 0x1600 AV Register R 52 104 Uexh2 RS48...

Страница 72: ...V Register R W 88 176 ExhCooling Exhaust airflow rate cooling 1 256 22 22 256 5632 0x1600 AV Register R W 89 178 Kp_CP Constant fan airflow control ler amplification 1 256 22 22 256 5632 0x1600 AV Reg...

Страница 73: ...2s 22 256 5632 0x1600 AV Register R W 124 248 TdecVent Inverterstoppingtime 1s 256 22s 22 256 5632 0x1600 AV Register R W 125 250 RECproc Participationincrossrecoverytemperaturecon trol 1 256 22 22 25...

Страница 74: ...th an outside temperature lower than this parameter 1 C 256 22 C 22 256 5632 0x1600 AV Register R W 161 322 TbStopFrost Return temperature threshold setting below which the system enters into a warm u...

Страница 75: ...ster R W 193 386 AplCode Setting the application code 1 1 22 22 AV Register R W 194 388 CodeOK Information about the compatibility of the inserted application code with the available codes described i...

Страница 76: ...448 LZOmin LZO value setting for 0V signal 1 256 22 22 256 5632 0x1600 MSV Register R W 225 450 LZOmax LZO value setting for 10V signal 1 256 22 22 256 5632 0x1600 MSV Register R W 226 452 PM2_5min PM...

Страница 77: ...gue output scaling Aout1 0 0 10VDC 1 2 10VDC MSV Coil 8320 R W 261 522 Ao2scale Analogue output scaling Aout2 0 0 10VDC 1 2 10VDC MSV Coil 8352 R W 262 524 Ao3scale Analogue output scaling Aout3 0 0 1...

Страница 78: ...2 _DIN6 Digital input status reading 6 0 open 1 shorted MSV Coil 9472 R 297 594 _DIN7 Digital input status reading 7 0 open 1 shorted MSV Coil 9504 R 298 596 _DIN8 Digital input status reading 8 0 ope...

Страница 79: ...338 676 E_Ai1 Analogue input emulated value 1 1V 256 10V 10 256 2560 0xA00 AV Register R W 339 678 Em_Ai2 Analogue input emulation 2 0 inactive 1 active MSV Coil10848 R W 340 680 E_Ai2 Analogue input...

Страница 80: ...g alarms 0 no deletion 1 deletion MSV Coil11936 R W 374 748 A_Code Alarm for incorrectly set application code 0 no alarm 1 alarm present BV Coil11968 R 375 750 A_AF Fire alarm 0 no alarm 1 alarm prese...

Страница 81: ...806 A_Tmain Leading temperature sensor alarm 0 no alarm 1 alarm present BV Coil12896 R 404 808 A_UV_ LampTime UV lamp operating time overrun alarm 0 no alarm 1 alarm present BV Coil12928 R 405 810 A_I...

Страница 82: ...ternal address 10 10 10 31 so that we can see the ELP controller in the localWIFI network Access to the controller is provided via http 10 10 10 31 2 DirectcommunicationwiththecontrollerviatheWIFIRout...

Страница 83: ...x 320 px communication link RS 485 supporting ELP series controllers BACnet MS TP or Modbus protocol embedded temperature sensor storage temperature 20 70 C IP protection class 30 Fig 18 6 1 2 Connect...

Страница 84: ...confirm the alarm hold down for 3 seconds on the alarm list 6 1 6 HMI screens Fig 22 TITLE SCREEM Main HMI pages HMI menu Settings menu Alarms menu t w o l e f t k e y s 3 s p r e v n e x t 3 s r i g...

Страница 85: ...by the user The menu contains two types of elements node and parameter Nodes are entry points into the menu Parameters contain values that can be read and some of them can also be mo dified To enter...

Страница 86: ...e main page or the first page of the main menu T sensor offset temperature sensor offset Offset of the temperature measurement carried out by the embedded sensor Menu skin menu skin Possibility to sel...

Страница 87: ...ption max 3W Power consumption in stand by mode 1 2W Display resolution 800x480 px Colour depth 18 bit Touch panel capacitive multitoutch Communication connection RS 485 Cooperation with ELP series co...

Страница 88: ...iption Exiting the submenu is possible after moving the screen from left to right TP HMI panel has its internal settings To enter it press any 3 points on the screen at the same time and hold them for...

Страница 89: ...u or cancel the edition of the parame ter Alarm status is indicated by red background colour of HMI menu To check the alarm status go to the Alarm menu 6 2 7 Alarm menu You can access the alarm menu b...

Страница 90: ...ifting the temperature measurement made by the built in sensor Menu skin Menu skin Possibility to select one of several menu designs Communication Settings HMI COM SETTINGS HMI settings MAC address HM...

Страница 91: ...ference is lower than the required value then the system triggers an alarm Fig 39 Workflow of heating adjustment Sample module setting The 3 stages P 36kW 12kW stage electric heater is fitted The rate...

Страница 92: ...nnected to the HE module and by the signal from the fan pressure gauge connected to the HE module which have to be connected in accordance with the wiring diagram Reaction of the ventilation system in...

Страница 93: ...ATE PLACE FORENAME AND SURNAME OF PERSON PERFORMING START UP SERIAL NUMBER OF UNIT COMPANY PERFORMING START UP STAMP INSTALLATION OPERATIONS DESCRIPTION COMMENTS CONFIRMATION OF PERFORMED OPERATIONS B...

Страница 94: ...92 AUTOMATION AND CONTROLLER FOR UNITS EVO T EVO T COMPACT OPERATION AND MAINTENANCE MANUAL NOTES...

Страница 95: ...93 NOTES...

Страница 96: ...SERWIS SERVICE 48 587839954 48 500087227 serwis klimor com...

Страница 97: ...EVO T EVO T COMPACT KLIMOR EVO T_CS...

Страница 98: ...Bacnet MS TP BMS 130 5 3 WWW 130 5 4 EVO T 131 6 HMI 132 6 1 HMI Compact 132 6 1 1 132 6 1 2 132 6 1 3 132 6 1 4 a 132 6 1 5 133 6 1 6 HMI 133 6 1 7 Menu HMI 133 6 1 8 HMI 134 6 1 9 134 6 1 10 135 6...

Страница 99: ...485 Master ELP11R32L Bac IP BASIC BMS BACnet IP Modbus TCP IP RJ45 Ethernet ETH ETH 1 1 6 7 8 9 10 2 3 4 5 11 1 RS485 BMS 2 RS485 3 Aou1 3 0 10 4 3 AC1 5 24 6 HMI CON HMI 7 8 ETH ETH RJ45 BMS 9 PT1 5...

Страница 100: ...98 EVO T EVO T COMPACT 1 2 2...

Страница 101: ...6 A_ExhFilter Din 7 A_SupPres Din 8 defrost A_ DefFunc Din 9 EC EBM A_SupFC Din 10 EC EBM A_ExhFC Din 11 A_SupFilter2 lub A_SupFilterES Din 12 A_StopS1 2 0 10VDC Ain 1 Ain 2 Ain 3 CO2 LZO PM2 5 PM10...

Страница 102: ...S PRCS 4 4 0 0 0 0 4 4 0 0 0 0 PRCS PRCS 5 5 1 1 0 0 4 4 0 0 0 0 PRCS PRCS 6 6 0 0 2 2 4 4 0 0 0 0 PRCS PRCS 8 8 0 0 0 0 0 0 8 8 0 0 PRCS PRCS 9 9 1 1 0 0 0 0 8 8 0 0 PRCS PRCS 10 10 0 0 2 2 0 0 8 8 0...

Страница 103: ...101 3 3 1 Q1M 1 ON 03 a b c d 4 4 e 4 4 f g EBM EBM EBM h modbus RTU EBM i j k 4 3 l 3 4 m point 3 1 n 3 4 o Kp Ti PI AHU AHU AHU 15 15 AHU PI K...

Страница 104: ...OMPACT 9 Pl Kp 1 Ti 60 Pl Kp 1 Ti 60 Pl Tmin Tmax Kp 1 Ti 90 Pl Pl PI Tmin Tmax Ti 10 120 I O 1 2 PI Fixed Expenditure CO2 PM2 5 PM10 Service Menu Factory Reset S1 DIN12 S1F din1 inflictor Stop 3 2 04...

Страница 105: ...103 3 3 4 3 I II Tsup 22 C III IV Troom 4 C TsetStdby 20 C Tsup V t Troom TsetStdby PT5 5 3 4 Re8 C 3 OK...

Страница 106: ..._3xThHWair 24VAC 24VAC 100 3 A_ThHWair A_3xThHWair Din2 A_ThHE A_3xThHE HE 24 24 A_ThHE 3 1 A_3 ThHE Din2 A_DX 24VAC 24VAC NO NC Din3 A_FX 24VAC 24VAC NO NC Din3 A_Cold Rec 24VAC 24VAC Din4 PT4 A_Sup...

Страница 107: ...105 A_Sup Pres 30 24VAC 30 24VAC Din7 A_Sup FC EC 24VAC 24VAC Din9 A_Exh FC EC 24VAC 24VAC Din10 A_Sup Filter2 24VAC 24VAC Din11 1S2H A_ StopS1 24VAC 24VAC Din12 Din12 PT1000 A_Tsup PT1 A_Texh PT2...

Страница 108: ...VO T EVO T COMPACT PT1000 A_Tout PT3 A_Trec PT4 A_Tma in A_Com SupFC EC EC A_Com SupFC2 EC 2 EC A_Com ExhFC EC EC A_Com ExhFC2 EC 2 EC A_Low Temp A_UV_ LampTime A_UV_ LampTime A_UV_LampTime A_Code Tab...

Страница 109: ...107 A_In_ Emul PT1000 A_Out Force push push push push outputs 4 4 1 No 11 1 Multi EVO_T CO2 VOC PM2 5 PM10 4 2 4 3 PL RU...

Страница 110: ...108 EVO T EVO T COMPACT 4 2 FR 03 05 11 21 57 00 6 7 OK OK OK C C C C 08 00 00 16 00 00 24 0oC STOP 8 OK OK OK C C C C 08 00 00 16 00 00 3 STOP...

Страница 111: ...109 4 3 1111 12 HMI CON HMI CON HMI RS485 RS485 PT5 PT5 PT5 15 C 600 5 C H C 20 C HPM CM H C 4 C HPM 22 C HMI CON HMI CON HMI CON HMIRS485 RS485 PT5 PT5 PT5 4 C 10 s 30 s 30 s 1 2 3 dtr...

Страница 112: ...110 EVO T EVO T COMPACT 10 15 30 30 1 2 3 100 100 PI 0 1 Kp_ 30 Ti_ B18 1 1 2 2 3 3 1 1 K 2 2 K 3 3 K K B19 1 1 2 2 3 3 1 1 K 2 2 K 3 3 K K RS485 70 1 85 2 100 3...

Страница 113: ...C 2 21 EC 1 22 2 EC 2 RS485 70 1 85 2 100 3 RS485 EC 1 RS485 2 EC 2 31 EC 1 32 2 EC 2 60 60 20 20 HPM CM 20 1 Kp_ 60 Ti_ 1 Kp_ 60 Ti_ PI 30 1 Kp_ 45 Ti_ 40 C Tmax 15 C Tmin C TsetBlowAct 450 100 1 C d...

Страница 114: ...COMPACT 50 50 180 15 100 100 T zewn 30 B8 30 0 C T zewn 75 T zewn T zewn 10 C T zewn 15 T zewn T zewn 5 C 0 10 Frost B8 10 C frost Frost 15 C Frost A_ThHWwater 20 C Frost A_ThHWwater 25 C 30 C 1 Kp 3...

Страница 115: ...113 30 30 10 C NO NC II II 2 1 I 2 II 3 I II 50 II II 75 III III 0 10VDC 0 10VDC II 30s 30s 30 C NO NC defrost defrost defrost 1 2 3 1 2 3 30 100 5 C Tlim 2 C Tlim...

Страница 116: ...f on off on off 1 2 3 off 1 2 3 T off 1 2 3 S T TP4 3 TP7 off 1 2 3 S T SCS SCS SECS RGCS PRCS RRCS 0 2 A_Code Offset A_LowTemp 20 Tset CO2 PM2 5 PM10 0 1 Kp 90 Ti 100 750ppm CO2 CO2 50 LZO 36 3 PM2 5...

Страница 117: ...M EBM Ok OK 2 EBM EBM EBM 1 0 10 2 1 Aout1 0 10 Aout1 Aout2 0 10 Aout2 Aout3 0 10 Aout3 0 10 2 1 Aout1 0 10 Aout1 Aout2 0 10 Aout2 Aout3 0 10 Aout3 C OJ DV OJ DV NS OJ DV OJ DV A_ColdRec A_ColdRec A_C...

Страница 118: ...A_StopS1 DIN12 ON OFF DIN12 A_StopS1 DIN12 1S2H 24V DIN8 A_SupFilter2 24V DIN8 A_SupFilterES ES 0 10VDC 2 10VDC 0 3 Tcom Modbus SLAVE 3 Twait Modbus 9 Modbus Twait Modbus xTcom 0 3 1 AHU HMI Multi HMI...

Страница 119: ...ding Register InputRegister BMS 0x0000 0x1000 Multistate Decimal 32 Fixed 8 24 1 256 1 256 0 00390625 0x1000 0x2000 0x2000 0x3000 20 67 206 0x3000 0x4000 20 67 2067 0x4000 0x5000 0x0000 0x1000 16 16 0...

Страница 120: ...GearTP 4 0 1 2 MSV Register R W 3 6 SetGearTP 4 1 1 IV Register R W 4 8 UnitState 0 1 1 2 2 4 3 8 16 32 64 128 MSV Register R 5 10 AHUnumbe rActual 1 1 IV Register R 6 12 WorkMode1 1 0 1 MSV Register...

Страница 121: ...ww el piast com alarms decoder AV Register R 36 72 ComSup RS485 Modbus ELP 1 256 22 22 256 5632 0x1600 AV Register R 37 74 Isup2 RS485 2 1A 256 22A 22 256 5632 0x1600 AV Register R 38 76 Fsup2 RS485 2...

Страница 122: ...0x1600 AV Register R 70 140 FHEn 0 1 MSV Register R W 16 DEC R W BacNet Modbus BacNet Modbus 71 142 Ch_Tmain 1 HMI CON 2 HMI RS485 4 8 16 PT5 32 MSV Register R W 72 144 EcoDiff ECO 1 C 256 22 C 22 256...

Страница 123: ...ter R W 99 198 VentSu pQuant 1 256 22 22 256 5632 0x1600 AV Register R W 100 200 PaEZ1 1 1 256 22 22 256 5632 0x1600 AV Register R W 101 202 PaEZ2 2 1 256 22 22 256 5632 0x1600 AV Register R W 102 204...

Страница 124: ...1600 AV Register R W 132 264 Ti_Cool 1 256 22 22 256 5632 0x1600 AV Register R W 133 266 PIcoolingAct PI 0 1 MSV Coil 4256 R W 134 268 DelOnPIcool PI 1 256 22 22 256 5632 0x1600 AV Register R W 135 27...

Страница 125: ...328 TbStartReg 1 C 256 22 C 22 256 5632 0x1600 AV Register R W 165 330 KpBack 1 256 22 22 256 5632 0x1600 AV Register R W 166 332 TiBack 1 256 22 22 256 5632 0x1600 AV Register R W 167 334 HW_Sec 0 1...

Страница 126: ...Register R W 194 388 CodeOK 0 1 MSV Coil 6208 R 195 390 OfsPT1 PT1 1 C 256 22 C 22 256 5632 0x1600 AV Register R W 196 392 OfsPT2 PT2 1 C 256 22 C 22 256 5632 0x1600 AV Register R W 197 394 OfsPT3 PT...

Страница 127: ...ister R W 226 452 PM2_5min PM2 5 0V 1 3 256 22 3 22 256 5632 0x1600 MSV Register R W 227 454 PM2_5max PM2 5 10V 1 3 256 22 3 22 256 5632 0x1600 MSV Register R W 228 456 PM10min PM10 0V 1 3 256 22 3 22...

Страница 128: ...256 5632 0x1600 AV Register R W 265 530 Twait Tcom x 1 256 22 22 256 5632 0x1600 AV Register R W 266 532 AHUnumber 1 IV Register R W 267 534 HMImulti multi 0 1 MSV Coil 8544 R W 268 536 WorkTime 1 25...

Страница 129: ...614 PT_2 PT1000 2 1 C 256 22 C 22 256 5632 0x1600 AV Register R 308 616 PT_3 PT1000 3 1 C 256 22 C 22 256 5632 0x1600 AV Register R 309 618 PT_4 PT1000 4 1 C 256 22 C 22 256 5632 0x1600 AV Register R...

Страница 130: ...1 MSV Coil 11040 R W 346 692 E_PT2 PT1000 2 1 C 256 22 C 22 256 5632 0x1600 AV Register R W 347 694 Em_PT3 PT1000 3 0 1 MSV Coil 11104 R W 348 696 E_PT3 PT1000 3 1 C 256 22 C 22 256 5632 0x1600 AV Reg...

Страница 131: ...water 0 1 BV Coil 12128 R 380 760 A_ThHWwa ter 0 1 BV Coil 12160 R 381 762 A_3xTh HWwater 3 A_ThHWwater 0 1 BV Coil 12192 R 382 764 A_ThHE 0 1 BV Coil 12224 R 383 766 A_3xThHE 3 0 1 BV Coil 12256 R 38...

Страница 132: ..._Tmain 0 1 BV Coil 12896 R 404 808 A_UV_ LampTime 0 1 BV Coil 12928 R 405 810 A_InEmul 0 1 BV Coil 12960 R 406 812 A_OutForce 0 1 BV Coil 12992 R 407 814 Alarm 0 1 BV Coil 13024 R 5 2 Bacnet MS TP BMS...

Страница 133: ...0 10 31 2 WIFI ROUTER 192 168 0 8 192 168 0 1 16 80 192 168 0 8 80 192 168 0 1 WIFI http 192 168 0 8 3 WIFI WIFI 80 IP 10 10 10 31 IP 80 IP 83 100 100 1 WIFI e g 10 10 10 1 ROUTER 192 168 0 8 ISP IP 8...

Страница 134: ...EVO T EVO T COMPACT 6 HMI 6 1 HMI Compact 6 1 1 86 86 19 24 10 TFT 240 x 320 RS 485 ELP BACnet MS TP Modbus 20 70 C IP 30 18 6 1 2 19 6 1 4 a 21 6 1 3 20 60 6 4 HMI VAC 24 V AC DC GND 0V A RS485 B RS...

Страница 135: ...133 6 1 5 20 Select 3 Next Prev Edit Back 3 Confirm Cancel Conf 3s 3 6 1 6 HMI 22 HMI HMI 3 p r e v n e x t 3 s 3 select select black b a c k 3 s 6 1 7 Menu HMI HMI HMI OK 3 C 3...

Страница 136: ...134 EVO T EVO T COMPACT 1 2 3 23 6 1 8 HMI HMI OK C HMI 6 1 9 HMI 3 C Alarms history 24 25...

Страница 137: ...HMI T sensor offset Menu skin Communication Settings HMI COM SETTINGS HMI MAC address MAC HMI Instance Bus mode PLC Com speed HMI HMI Com parity PLC Com stop bits PLC RS485 MASTER COM SETTINGS RS 485...

Страница 138: ...30 126 x 87 x 16 HMI TP7 24 V AC DC 10 3W 1 2W 800x480 px 18 bit multitoutch RS 485 ELP BACnet MS TP Modbus 10 40 C 20 70 C IP 30 193 x 125 x 16 1 24 Vac 2 GND 3 RS485 A 4 RS485 B 24 VAC GND A B VAC...

Страница 139: ...137 6 2 3 HMI TP4 3 29 HMITP 4 3 HMI TP7 30 HMITP 7 6 2 4 HMI TP HMI TOUCH PANEL TP JPG PNG SLIDEBAR HMI SLIDEBAR SLIDEBAR MAIN MENU CALENDAR ALARMS GRAPH HMI TP 3 3 6 2 5 HMI HMI HMI HMI HMI HMI...

Страница 140: ...138 EVO T EVO T COMPACT 32 Panel HMI 6 2 6 HMI HMI HMI HMI HMI OK C HMI 6 2 7 SLIDEBAR ALARMS Alarms history 33 34 ON OFF...

Страница 141: ...st page HMI HMI T sensor offset Menu skin HMI COM SETTINGS HMI MAC address MAC HMI Instance Bus mode PLC Com speed HMI HMI Com parity PLC Com stop bits PLC RS485 MASTER COM SETTINGS RS 485 MASTER MAC...

Страница 142: ...140 EVO T EVO T COMPACT 7 HE 36 HE DIP PCB 37 PWM SSR P3 38 P1 P2 0 10 0 10 N P2 P1 10 1 N 10 6 N 60 N 39 3 P 36 12 Pn 20 Pn 2 DIP 2 PWM P3 PWM N P1st Pn P3 66...

Страница 143: ...141 HE HE HE HE HE HE 3 4 UniAppEVO T...

Страница 144: ...142 EVO T EVO T COMPACT 8...

Страница 145: ...143...