Klimawent
– the warranty of highest quality at attractive price
6 z 8
Reel Exhaust Extractor
ALAN-U/C-HD-N
23.05.2019
Having installed the extractor under the ceiling or to the wall, fasten the connection fitting piece of the reel
(application without the fan) with the ventilation conduit, discharging the exhaust volume outside the building.
When the extractor is equipped with a fan type FA, connect the fan outlet with the ventilation discharging ductwork,
using a short section of flexible hose. Depending on the diameter of the fan connection, the ventilation conduit
must have diameter Ø160 mm or Ø200 mm.
After all the connections are carried out and the fan is started up with the three phase motor
– necessarily
check the fan impeller rotation sense with reference to the arrow on the housing
.
OPERATIONAL USE
F
For safety reasons, in order to use the Reel Exhaust Extractor correctly
– follow subsequent steps:
1
.
Operate the extraction fan with a pushbutton
“
START
”.
2
.
Pull the nozzle with hose to the requested operational length and connect the nozzle at the exhaust pipe of the
serviced vehicle.
Start the vehicle engine
. In application with a non-typical exhaust pipe construction, use the
nozzle with a suction stand.
3
.
After the completed service,
stop the vehicle engine
and disconnect the nozzle from the exhaust pipe.
4
.
To wind up the hose, pull it gently
– the spring mechanism shall recoil the hose onto the reel. Pay attention that
the hose is being wound evenly on the reel.
5
.
Having recoiled the hose,
switch off the extraction fan with a button
“
STOP
”.
ADJUSTMENT OF THE LIFT HEIGHT OF THE NOZZLE
:
1
.
Having installed the extractor under the ceiling or at the wall, turn the reel and block it with the ratchet gear so
that the suction nozzle is in the level of the floor.
2
.
Release the clamp of the rubber stopper and choose its appropriate fixing position on the hose
– according to the
installing height of the extractor.
3
.
After the rubber stopper is fastened in a new fixing point (i.e. clamp tightening), pull slightly the hose to start the
spring retracting mechanism and check the reeling operation.
ADJUSTMENT OF THE BAND BRAKE
:
●
To increase the braking force turn the adjustment screw to the right.
●
To reduce the braking force turn the adjustment screw to the left.
●
Remember to lock the above mentioned screw with a counter-nut.
Fig. No.5
– Band brake
REMARKS REGARDING THE OPERATIONAL USE
●
Any use of the extractor with the improperly functioning extraction fan is not acceptable. This could contribute
to overheating and damage of the hose assembly.
●
Any servicing, repairs and adjustment ought to be executed by an authorized person only.
●
For safety reason, during winding the hose onto the reel, operator has to guide the hose end with hand.
●
Protect the hose from mechanical damage and from getting polluted with oil and solid lubricants.