background image

Four-way Cassette Type 

INSTALLATION    MANUAL 

Thank you very much for purchasing our air conditioner,   

Before using your air conditioner , please read this manual carefully and keep it for future reference. 

installation manual 

Be sure to be in conformity with the local, national and 
international laws and regulations. 

Read "PRECAUTIONS" carefully before installation. 

The following precautions include important safty items. 
Observe them and never forget. 

Keep this manual with the owner's manual in a handy place 
for future reference. 

1. PRECAUTIONS

The safty precautions listed here are divided into two categories. 

After  completing the  installation, make  sure  that  the  unit  operates  
properly during the start-up operation. Please instruct the customer  
on  how  to  operate the  unit  and  keep  it  maintained.Also,  inform  
customers that they should store this installation manual along with  
the owner's manual for future reference.   

Be sure only trained and qualified service personnel to 
install, repair or service the equipment. 

Improper  installation, repair,  and  maintenance may  result  in  
electric  shocks,  short-circuit,  leaks,  fire  or  other  damage to  
the equipment. 

Failure to observe a warning may result in death. 

Failure  to  observe  a  caution  may  result  in  injury  or  
damage to the equipment. 

CONTENTS

PAGE 

1. PRECAUTIONS...................................................................... 

2. INSTALLATION INFORMATION

3. ATTACHED FITTINGS
4. INSPECTING AND HANDLING THE UNIT........................ 
5. INDOOR UNIT INSTALLATION
6. OUTDOOR UNIT INSTALLATION....................................

8. INSTALL THE CONNECTING PIPE

7. REFRIGERANT PIPE

9. CONNECT THE DRAIN PIPE...........................................
10. WIRING
11. TEST OPERATION.........................................................

Install according to this installation instructions strictly.  

If  installation is  defective,  it  will  cause  water  leakage,  
electrical shock and fire. 

When installing the unit in a small room, take measures
against to keep refrigerant concentration from exceeding
allowable safety limits in the event of refrigerant leakage. 

Contact  the  place  of  purchase  for  more  information.  
Excessive refrigerant in a closed ambient can lead to oxygen
deficiency. 

Use the attached accessories parts and specified parts 
for installation.

otherwise,  it  will  cause  the  set  to  fall,  water

leakage,  

electrical shock and fire. 

Install at a strong and firm location which is able to
withstand the set' s weight.

If  the  strength  is  not  enough or  installation is  not  properly  
done, the set will drop to cause injury. 

The appliance must be installed 2.5m above floor. 

The appliance shall not be installed in the laundry. 

Before obtaining access to terminals, all supply circuits 
must be disconnected. 

The appliance must be positioned so that the plug is 
accessible.

The enclosure of the appliance shall be marked by word, 
or by symbols, with the direction of the fluid flow. 

For electrical work, follow the local national wiring
standard, regulation and this installation instructions. An 
independent circuit and single outlet must be used.

If  electrical  circuit  capacity  is  not  enough  or  defect  in  
electrical work, it will cause electrical shock or fire. 

Use the specified cable and connect tightly and clamp 
the cable so that no external force will be acted on the 
terminal.

If connection or fixing is not perfect, it will cause heat-up or  
fire at the connection. 

Wiring routing must be properly arranged so that control 
board cover is fixed properly.  

If  control  board  cover  is  not  fixed  perfectly,  it  will  cause  
heat-up  at  connection  point  of  terminal,  fire  or  electrical
shock. 

If the supply cord is damaged, it must be replaced by the 
manufacture or its service agent or a similarly qualified 
person in order to avoid a hazard. 

An  all-pole disconnection switch having a contact
separation of at least 3mm in all poles should  be  
connected in fixed wiring. 

When carrying out piping connection, take care not to let 
air substances go into refrigeration cycle.

Otherwise, it  will  cause  lower  capacity, abnormal  high
pressure in the refrigeration cycle, explosion and injury. 

Do not modify the length of the power supply cord or use 
of extension cord, and do not share the single outlet with 
other electrical appliances.

Otherwise, it will cause fire or electrical shock. 

Carry out the specified installation work after taking into 
account strong winds, typhoons or earthquakes. 

Improper installation work may result in the equipment falling  
and causing accidents. 

CAUTION

WARNING 

WARNING 

......................................... 

...................................................... 

................................................ 

..........................................................................

.................................

.......................................................






12 
14 
16 
17 
18 

installation manual 

To install properly, please read this "installation manual" at 
first.

The air conditioner must be installed by qualified persons. 

When installing the indoor unit or its tubing, please follow 
this manual as strictly as possible. 

If the air conditioner is installed on a metal part of the 
building, it must be electrically insulated according to the 
relevant standards to electrical appliances. 

When all the installation work is finished, please turn on 
the power only after a thorough check. 

Regret for no further announcement if there is any change 
of this manual caused by product improvement. 

2. INSTALLATION INFORMATION

Ground the air conditioner.

Do  not  connect  the  ground  wire  to  gas  or  water  pipes,  
lightning  rod  or  a  telephone  ground  wire.Incomplete
grounding may result in electric shocks. 

Be sure to install an earth leakage breaker.

Failure to install  an  earth  leakage  breaker  may  result  in  
electric shocks. 

Connect the outdoor unit wires , then connect the indoor 
unit wires. 

You are not allow to connect the air conditioner with the
power source  until  wiring and  piping the  air  conditioner is  
done. 

While following the instructions in  this installation
manual, install drain piping in order to ensure proper
drainage and insulate piping in  order to  prevent
condensation.

Improper  drain piping  may result in  water  leakage  and 
property damage. 

Install the indoor and outdoor units, power supply wiring
and connecting wires at  least 1 meter away from
televisions

or  radios in order to prevent

image

interference or noise. 

Depending on the radio waves, a distance of 1 meter may not
be sufficient enough to eliminate the noise. 

The appliance is not intended for use by young children 
or infirm persons without supervision. 

Don't install the air conditioner in the following locations: 

There is petrolatum existing. 

There is salty air surrounding (near the coast). 

There is caustic gas (the sulfide, for example) existing  

in the air (near a hot spring). 

The Volt vibrates violently (in the factories). 

In buses or cabinets. 

In kitchen where it is full of oil gas. 

There is strong electromagnetic wave existing. 

There are inflammable materials or gas. 

There is acid or alkaline liquid evaporating. 

Other special conditions. 

If the refrigerant leaks during installation, ventilate the 
area immediately. 

Toxic gas may be produced if the refrigerant comes into the  
place contacting with fire. 

The temperature of refrigerant circuit will be high, please 
keep the interconnection cable away from the copper
tube.

After completing the installation work, check that the
refrigerant does not leak. 

Toxic  gas  may  be  produced if  the  refrigerant leaks  into  the  
room and comes into contact with a source of fire, such as a  
fan heater, stove or cooker. 

INSTALLATION ORDER 

Select the location; 

Install the indoor unit; 

Install the outdoor unit; 

Install the connecting pipe ; 

Connect the drain pipe; 

Wiring; 

Test operation. 

CAUTION

installation manual 

3. ATTACHED FITTINGS

Please check whether the following fittings are of full scope. If there are some spare fittings , please restore them carefully .  

Fig.3-1

Never throw or beat the controller.

Before installation, operate the remote controller to determine its location in a
reception range.

Keep  the  remote  controller  at  least  1m  apart  from  the  nearest  TV  set  or  stereo 
equipment. (it is necessary to prevent image disturbances or noise interferences.)

Do not install the remote controller in a place exposed to direct sunlight or close to a 
heating source, such as a stove.

Note that the positive and negative poles are right positions when loading batteries.

This manual is subject to changes due to technological improvement without further 
notices.

The  appliance  shall  be  installed  in  accordance  with  national 
wiring regulations.

Do not operate your air conditioner in a wet room such as a 
bathroom or laundry room.

An all-pole disconnection device which has at least 3mm
clearances in all poles , and have a leakage current that may 
exceed  10mA,  the  residual  current  device  (RCD)  having  a 
rated  residual  operating  current  not  exceeding  30mA,  and 
disconnection must be incorporated in the fixed wiring in
accordance with the wiring rules.

Cautions on remote controller installation:

Remote

controller

Remote controller

holder

Mounting screw B

ST2.9x10-C-H

CANCEL 

LOCK 

SET TEMPERATURE(°C) 

AUTO 
COOL 
DRY 
HEAT 

FAN 
HIGH 
MED 
LOW 

TEMP 

MODE 

SWING 

TIMER 

RESET 

ON/OFF 

  FAN  
SPEED 

VENT 

ECONOMIC  
 RUNNING 

(depending on the models)

installation manual 

Keep indoor unit, outdoor unit, power supply wiring and
transmission wiring at least 1 meter away from televisions
and  radios.  This is  to  prevent  image interference  and 
noise  in  those  electrical  appliances.  (Noise  may be 
generated depending on the conditions under which the
electric wave is generated, even if 1 meter is kept.)

There is enough room for installation and maintenance. 

The ceiling is horizontal, and its structure can endure the  
weight of the indoor unit. 

The  outlet  and  the  inlet  are  not  impeded,  and  the  
influence of external air is the least. 

The air flow can reach throughout the room. 

The connecting pipe and drainpipe could be extracted out  
easily. 

There is no direct radiation from heaters. 

4. INSPECTING AND HANDLING THE UNIT

At delivery, the package should be checked and any damage should  
be reported immediately to the service agent. 

When handling the unit, take into account the following: 

5. INDOOR UNIT INSTALLATION

5.1   Installation place 

(Refer to Fig.5-1,Fig.5-2,Fig.5-3 and Table 5-1 for specification.) 

The indoor unit should be installed in a location that meets 
the following reauirements: 

          Fragile, handle the unit with care. 

Keep  the  unit  upright  in  order  to  avoid  compressor  

damage. 

Choose on before hand the path along which the unit is to be  
brought in. 

Move this unit as originally package as possible. 

When  lifting  the  unit  ,  always use  protectors  to  prevent  belt  
damage and pay attention to the position of the unit’s centre  
of gravity. 

CAUTION

Fig.5-2

Fig.5-1

MODEL

A

H

18

235 
235 

205 
205 

Table 5-1 

mm 

317 

287 

30-48

275 

245 

30

235  

205 

24

Fig.5-3

48-60

installation manual 

Fig.5-5

Fig.5-4

Fig.5-9

Fig.5-8

5.3   Install The Panel 

Remove the air-in grill. 

Never put the panel face down on floor or against the 
wall, or on bulgy objects. 

Never crash or strike it. 

Slide two grill switches toward the middle at the same time,  
and then pull them up.  

(Refer to Fig.5-7) 

Draw  the  grill up  to  an  angle of  about  45,  and  remove  it.  

(Refer to Fig.5-8) 

Remove the installation covers at the four corners 

Wrench off the bolts, loose the rope of the installation covers,  
and remove them.  

(Refer to Fig.5-9) 

1

2

CAUTION

Fig.5-6

Fig.5-7

5.2   Install the main body 

Cut  a  quadrangular  hole  of  880x880mm  in  the  ceiling  
according to the shape of the installation paper board.  

(Refer to  Fig.5-2) 

The center of the hole should be at the same position of  
that of the air conditioner body. 

Determine the lengths and outlets of the connecting pipe,  
drainpipe and cables. 

To balance  the  ceiling  and  to  avoid  vibration,  please
enforce the ceiling when necessary. 

Adjust  the  hexangular nuts  on  the  four  installation hooks  
evenly, to ensure the balance of the body. 

If  the  drainpipe is  awry,  leakage will be  caused by  the  
malfunction of the water-level switch. 

Adjust the position to ensure the gaps between the body  
and  the  four  sides  of  ceiling are  even.  The  body's  lower  
part  should sink  into  the  ceiling for  10~12 mm  

(Refer  to  

Fig.5-4)

In general, L is half of the screw length of the installation  
hook. 

(Refer to Fig.5-4) 

Locate  the  air  conditioner firmly  by  wrenching the  nuts  
after  having adjusted the  body's  position well. 

(Refer  to  

Fig.5-5)

Select  the  position of  installation hooks  according to  the  
hook holes on the installation board. 

Drill four holes of  

Ø 

12mm, 45~50mm deep at the selected

positions  on  the  ceiling.  Then  embed  the  expansible  
hooks (fittings). 

Face the concave side of the installation hooks toward the  
expansible hooks. Determine the length of the installation  
hooks  from  the  height  of  ceiling,  then  cut  off  the  
unnecessary part. 

If  the  ceiling  is  extremely  high,  please  determine  the  
length of the installation hook according to facts. 

New built houses and ceilings 

In the case of new built house, the hook can be embedded  
in  advance (refer  to  2  mentioned above).  But  it  should be  
strong  enough to  bear  the  indoor unit  and  will not  become  
loose because of concrete shrinking. 

After installing the body, please fasten the installation paper  
board  onto  the  air  conditioner  with  bolts(M6X12)  to  
determine in  advance the  sizes  and  positions of  the  hole  
opening on ceiling. 

(Refer to Fig.5-6) 

Refer to 3 above for  installation. 

Remove the installation paper board. 

Please first  guarantee  the  flatness  and  horizontal  of  
ceiling when installing it. 

Refer to 1 mentioned above for others. 

After installing the body, the four bolts(M6x12)must be 
fastened to the air conditioner onto ensure the body is 
grounded well. 

CAUTION

The existing ceiling (to be horizontal) 

installation manual 

Adjust  the  four  panel  hook  screws  to  keep  the  panel  
horizontal, and screw them up to the ceiling evenly.  

( Refer to   

Fig.5-10.3)

Regulate the panel in the direction of the arrow in  

Fig.5-10.4

slightly to  fit  the  panel's center  to  the  center  of  the  ceiling's  
opening. Guarantee that hooks of four corners are fixed well. 

Keep  fastening the  screws  under the  panel hooks,  until  the  
thickness  of  the  sponge between the  body  and  the  panel's  
outlet  has  been reduced to  about  4~6mm.  The  edge of  the  

panel should contact with the ceiling well. 

 (Refer to Fig.5-11) 

4

5

6

Fasten  the  rope  of  installation cover on the bolt of the
installation cover.  

(Refer to Fig.5-14-left)

Press  the  installation cover  into  the  panel slightly.  

(Refer  to  

Fig.5-14-right)

Malfunction  described  in  

Fig.5-12

can  be  caused  by  

inappropriate tightness the screw.  

If  the  gap  between the  panel and  ceiling still  exists  after  
fastening the screws, the height of the indoor unit should  
be modified again.  

( Refer to Fig.5-13-left) 

You  can  modify  the  height of  the  indoor unit  through the  
openings on the panel's four c orners, if the lift of the
indoor unit  and  the  drainpipe is  not  influenced  

(Refer  to  

Fig.5-13-right).

Hang the air-in grill to the panel, then connect the lead 
terminator of the swing motor and that of the control box 
with corresponding terminators on the body respectively. 

Relocate the air-in grill in the procedure of reversed order. 

Relocate the installation cover. 

Fig.5-10

Tubing joint 

Outlet joint 

Hook panel 

Water-receiver 

Swing Motor 

Hook-bolt 

Cross-screwdriver 

Do not coil the wiring of the swing motor into the seal 
sponge.

Install the panel 

Align the swing motor on the panel to the tubing joints of the  
body properly.  

( Refer to Fig.5-10) 

Fix hooks of the panel at swing motor and its opposite sides  
to  the  hooks  of  corresponding  water  receiver.  

( Refer  to   

Fig.5-10.1)

Then  hang  the  other  two  panel  hooks  onto  

corresponding hangers of the body.  

( Refer to Fig.5-10.2) 

3

CAUTION

<500mm 

m0 

5 7 

Lean over 1/50 

Pump-pipe clasp 

 (the fittings) 

panel sponge 

body 

Ceiling 

panel 

panel foam1  

air out 

Fan 

panel foam 2 

Loosen upper nut 

Adjust lower nut 

4-

m m 6 

outlet foam 

1-1.5m 

Fig.5-12

Fig.5-14

Fig.5-15

Fig.5-11

Fig.5-13

Fig.5-16

Installation cover’s rope 

Tap Screw 

Slide the four sliders 

in the corresponding 

channel when installing 

the cover 

All the pictures in this manual are for explanation purpose only.
They may be slightly different from the air conditioner you  

purchased(depend on model).The actual shape shall prevail. 

NOTE

installation manual 

Test cap

CLOSED

OP

EN

CL

O

SE

D

OPEN

model 18 to 30

Series A=160mm; Series  B=75mm 

model 36 to 60

Series A=160mm; Series  B=95mm 

The air volume in duct is around 300-360m3/h for model 18  
to 30 unit. 

The air volume in duct is around 400-640m3/h for model 36  
to 60 unit. 

The max. length of duct is 2m. 

The original air outlet with the same direction of duct should  
be sealed In case of two duct connection. 

The air volume in one duct is around 200-260m3/h for model  
18 to 30 unit. 

The air volume in one duct is around 300-500m3/h for model  
36 to 60 unit. 

The max. length of duct is 1.5m for one duct. 

The original air outlet with the same direction of duct should  
be sealed. 

Fig.5-19

Fig.5-18

One-way

Two- way

In case of one duct connection 

In case of two duct connection 

NOTE

Fig.5-17

5.4   Install the distribution duct 

Conditioned air can be distributes by means of a distribution duct. 

installation manual 

installation manual 

10 

installation manual 

6.1   Installation Place

6. OUTDOOR UNIT INSTALLATION

There is enough room for installation and maintenance. 

The  air  outlet  and  the  air  inlet  are  not  impeded,  and  can 
not be reached by strong wind. 

It must be a dry and well ventilating place. 

The support is flat and horizontal and can stand the
weight of the outdoor unit. And will no additional noise or 
vibration.

Your  neighborhood  will  not  feel  uncomfortable  with  the 
noise or expelled air. 

It is easy to install the connecting pipes or cables. 

Determine the air outlet direction where the discharged air 
is not blocked. 

There is no danger of fire due to leakage of inflammable 
gas. 

The piping length between the outdoor unit and the indoor 
unit may not exceed the allowable piping length. 

In the case that the installation place is exposed to strong 
wind  such  as  a  seaside,  make  sure  the  fan  operating 
properly  by  putting  the  unit  lengthwise  along  the  wall  or 
using a dust or shield.

(Refer to Fig.6-1)

If  possible,  do  not  install  the  unit  where  it  is  exposed  to 
direct sunlight.  

If necessary, install a blind that does not interfere with the 
air flow. 

During the heating mode, the water drained off the
outdoor unit ,The condensate should be well drained away 
by  the  drain  hole  to  an  appropriate  place,  so  as  not  to 
interfere other people.  

Select  the  position  where  it  will  not  be  subject  to  snow 
drifts, accumulation of leaves or other seasonal debris. If 
unavoidable, please cover it with a shelter. 

Locate  the  outdoor  unit  as  close  to  the  indoor  unit  as 
possible. 

If possible, please remove the obstacles nearby to prevent 
the  performance  from  being  impeded  by  too  little  of  air 
circulation. 

The minimum distance between the outdoor unit and
obstacles described in the installation chart does not
mean  that  the  same  is  applicable  to  the  situation  of  an 
airtight room. Leave open two of the three directions
(M,N,P) 

(Refer to Fig.6-5) 

tr 

o ng 

 w 

in 

d

The outdoor unit should be installed in the location that 
meets the following requiements: 

All the pictures in this manual are for explanation
purpose  only.  They  may  be  slightly  different  from  the 
air  conditioner  you  purchased(depend  on  model).The 
actual shape shall prevail. 

Fig.6-1

NOTE

11 

installation manual 

CAUTION

Fig.6-2

Fig.6-3

Fig.6-4

Fig.6-15

8. INSTALL THE CONNECTING PIPE

Check whether the height drop between the indoor unit
and outdoor unit, the length of refrigerant pipe, and the
number of the bends meet the following requirements: 

All field piping must be provided by a licensed
refrigeration technician and must comply with the
relevant local and national codes. 

Do not let air, dust, or other impurities fall in the pipe 
system during the time of installation. 

The connecting pipe should not be installed until the 
indoor and outdoor units have been fixed already. 

Keep the connecting pipe dry, and do not let moisture in 
during installation. 

   The Procedure of Connecting Pipes 

8.1

Table 6-1 

Table 6-3 

mm 

mm 

NOTE

All the pictures in this manual are for explanation
purpose  only.  They  may  be  slightly  different  from  the 
air  conditioner  you  purchased(depend  on  model).The 
actual shape shall prevail. 

Never  hold  the  inlet  of  the  outdoor  unit  to  prevent  it  from 
deforming. 

Do not touch the fan with hands or other objects. 

Do not lean it more than 45, and do not lay it sidelong. 

Make concrete foundation accoding to the sepecif-ications of 
the outdoor units.

(Refer to Fig.6-15) 

Fasten the feet of this unit with bolts firmly to prevent it from 
collapsing  in  case  of  earthquake  or  strong  wind.

(Refer to 

Fig.6-15)

6.5   Moving and installation 

Since the gravity center of the unit is not at its physical
center, so please be careful when lifting it with a sling. 

Table 8-1 

A

H

> 60 cm 

Fix with  bolt 

H

Model 

12K 

18K-24K 

30K-42K 

12K 

18K-24K 

30K-60K 

48K-60K 

<15K 

>15K~<24K 

>24K~<36K 

>36K~<60K 

50Hz T1 condition/R22 

Split type air conditioner

50Hz Vertical discharge air conditioner 

/60Hz T1 condition/R22 Split type air

conditioner and Vertical discharge air  

conditioner

The type of models

R410A inverter Split type air 

conditioner and Centrifugal 

fan outdoor unit 

50 

30  

15 

50 

30  

15 

30 

65 

30  

25 

50 

R410A Split type air conditioner 

and Centrifugal fan outdoor unit 

50Hz/60Hz T3 condition 

(outdoor unit down)

50Hz/60Hz T3 condition 

(outdoor unit up)

the unit with quick joint

12K 

48K-60K 

18K-30K 

36K 

18K-24K 

42K-60K 

30K 

36K 

18K-24K 

12K-18K 

48K-60K 

42K 

30K 

36K 

50 

25  

15 

30 

50 

30  

25 

30 

25 

50 

30  

30 

50 

15 

35 

25  

20 

30 

25 

15  

20 

25 

15  

10 

20 

30 

20  

10 

25 

25 

10  

20 

10  

20 

refrigerant pipe 

The length of

height drop 

The max

CAUTION

CAUTION

How to connect the pipes 

Drill  a  hole  in  the  wall  (suitable  just  for  the  size  of  the  wall 
conduit), then set on the fittings such as the wall conduit and 
its cover. 

Bind the connecting pipe and the cables together tightly with 
binding tapes. 
Pass  the  bound  connecting  pipe  through  the  wall  conduct 
from outside. Be careful of the pipe allocation to do on
damage to the tubing. 

Connect  the  pipes.  Refer  to  "How  to  Connect  the  pipes"  for 
details. 

Expel the air with a vacuum pump. Refer to "How to expel the 
air with a vacuum pump" for details. 

open the stop values of the outdoor unit to make the
refrigerant  pipe  connecting  the  indoor  unit  with  the  outdoor 
unit in fluent flow. 

Check the leakage. Check all the joints with the leak detector 
or soap water. 

Cover the joints of the connecting pipe with the soundproof / 
insulating  sheath  (fittings),  and  bind it  well  with  the  tapes  to 
prevent leakage. 

Execute heat insulation work completely on both sides of 
the gas piping and the liquid piping. Otherwise, this can 
sometimes result in water leakage.

Be sure to with insulating materials cover all the exposed 
parts  of  the  flare  pipe  joints  and  refrigerant  pipe  on  the 
liquid-side  and  the  gas-side.  Ensure  that  there  is  no  gap 
between them. 
Incomplete insulation may cause water condensation. 

Flaring

1

Cut a pipe with a pipe cutter. 

(refer to Fig.8-1) 

2

Bend the tubing in proper way. Do not harm to them. 

Connect the indoor unit at first, then the outdoor 
unit.

Too large torque will harm the bellmouthing and too small 
will cause leakage. Please determine the torque
according to Table 8-2.

After  the  connecting  work  is  finished,  be  sure  to  check 
that there is no gas leak. 

The bending angle should not exceed 90. 

Bending position is preferably in the middle of the
bendable pipe. The larger the bending radius the better it 
is. 

Do not bend the pipe more than three times. 

When connecting the flare nut, coat the flare both inside 
and outside with either oil or ester oil and initially tighten 
by hand 3 or 4 turns before tighting firmly. 

Be sure to use both a spanner and torque wrench 
together when connecting or disconnecting pipes to /from 
the unit. 

(Fig.8-4)

Tab le 8-2 

(mm) 

Ø6.4 

14.2

̚

17.2 N  m 

(144

̚

176 kgf  cm) 

8.3         8.3 

Ø9.5 

32.7

̚

39.9 N  m 

(333

̚

407 kgf   cm) 

12.0       12.4 

Ø12.7 

49.5

̚

60.3 N  m 

(504

̚

616 kgf  cm) 

15.4       15.8 

Ø15.9 

Ø19.1 

61.8

̚

75.4 N   m 

(630

̚

770 kgf   cm) 

97.2

̚

118.6 N  m 

(990

̚

1210 kgf  cm) 

18.6       19.0 

22.9       23.3 







Insert a flare nut into a pipe and flare the pipe. 

Refer to Table 8-2 for the dimension of flare nut spaces. 

Fig.8-1

min 

max 

Bend the pipe with thumb 

min-radius 100mm 

Fig.8-2

Fig.8-3

Fig.8-4

How to expel the air with a vacuum pump 

Stop valve operation intruduction 

1.

Opening stop valve

2.

Closing stop valve

1) 

2) 

1) 

2) 

3) 

Remove  the  cap  and  turn  the  valve 
counterclock-wise  with  the  hexagon  wrench. 

Turn it until the shaft stops.Do not apply excessive force 
to the stop valve. Doing so may breakthe valve body, as 
the valve is not a backseat type. Always use the special 
tool. 

Make sure to tighten the cap securely. 

Remove the cap and turn the valve clockwise with the 
hexagon wrench. 

Securely tighten the valve until the shaft contacts the 
main bodyseal. 

Pipe  gauge 

Tightening   torque 

Flare dimensin A

Flare     shape 

90

Lean     crude     burr 

12 

installation manual 

CAUTION

CAUTION

CAUTION

Tightening torque N.M (Turn clockwise to close) 

Stop

Valve size

Shaft (valve body)

Cap

(Valve lid) 

Ø6.4 

5.4

̚

6.6 

Hexagonal

wrench 4 mm 

13.5

̚

16.5 

11.5

̚

13.9 

Ø9.5 

Ø12.7 

8.1

̚

9.9 

18

̚

22 

Ø15.9 

13.5

̚

16.5 

Hexagonal

wrench 6 mm 

23

̚

27 

Ø22.2 

27

̚

33 

Hexagonal

wrench

10 mm 

36

̚

44 

Ø25.4 

Loosen  and  remove  the  maintenance  nuts  of  stop  valves A
and B, and connect the charge hose of the manifold valve to 
the service port of stop valve A. (Be sure that stop valves A
and B are both closed) 

Connect the joint of the charge hose with the vacuum pump. 

Open the Lo-lever of the manifold value completely. 

Turn  on  the  vacuum  pump.  At  the  beginning  of  pumping, 
loosen  the  maintenance  nut  of  stop  valve  B  a  little  to  check 
whether  the  air  comes  in  (the  sound  of  the  pump  changes, 
and the indicator of compound meter turns below zero). Then 
fasten the maintenace nut. 

-76 c mHg 

Lo-lev er 

Hi-leve r 

Charg e hos e 

Charg e hos e 

Vac uum p ump 

Lo-lev er 

Manifo ld valv e 

Multi-m eter  Pressu re  meter 

Fig.8-7

Additional Refrigerant Charge 

8.3

Refrigerant  cannot  be  charged  until  field  wiring  has  been 
completed.

Refrigerant  may  only  be  charged  after  performing  the  leak 
test  and the vacuum pumping.

When charging a system, care shall be taken that its
maximum  permissible  charge  is  never  exceeded,  in  view  of 
the danger of liquid hammer.

Charging with an unsuitable substance may cause
explosions and accidents, so always ensure that the
appropriate refrigerant is charged.

Refrigerant containers shall be opened slowly.

Always  use  protective  gloves  and  protect  your  eyes  when 
charging refrigerant.

Using the vacuum pump 

When  the  pumping  has  finished,  close  the  Lo-lever  of  the 
manifold valve completely and turn off the vacuum
pump.Make pumping for 15 minutes or more and check that 
the compound meter indicates -76cmHg(-1X10 Pa) 

Loosen and remove the cap of stop valves A and B to open 
stop valve A and B completely, then fasten the cap. 

Disassemble  the  charge  hose  from  the  service  port  of  stop 
valve A, and fasten the nut. 

Fig.8-6

Fig.8-5

Always use a charge hose for service port connection.

After tightening the cap, check that no refrigerant leaks
arepresent.

service port 

cap 

maintenance nut 

hexagon hole 

shaft 

seal 

Make sure to tighten the cap securely. 
For the tightening torque, refer to the table below. 

Outdoor 

unit 

Indoor 

unit 

Stop valv e

Ga s s ide 

Liq uid  si de 

Table 8-3 

Maintenance nut 

Ventilate the air if there was any refrigerant leakage 
during the installation.
Leaked refrigerant will generate poisonous gas if
meeting fire.

Make  sure  there  is  no  refrigerant  leakage  after  the 
installation.
Leaked refrigerant will generate poisonous gas if
meeting fire.

Allowed Lenght and Drop of Pipes

Requirements are different when installing the outdoor unit, 
please refer to outdoor unit installation manual for detailed 
information.

Material and Size of the Pipes

Three length(3m,5m,10m)of pipes are available to purchase. 

8.2.   Refrigerant pipe installation

13 

installation manual 

NOTE

NOTE

Drainage test 

Drainage test 

Install the drain joint of the outdoor unit 

Check whether the drainpipe is unhindered. 

New built house should have this test done before paving 
the ceiling. 

Remove the test cover, and stow water of about 2000ml to the 
water receiver through the stow tube.  

Turn  on  the  power,  and  operate  the  air  conditioner  under  the 
"COOLING" mode. Listen to the sound of the drain pump.
Check  whether  the  water  is  discharger  well  (a  lag  of  1min  is 
allowed before discharging, according to the length of the drain 
pipe), and check whether water leaks from the joints. 

Stop  the  air  conditioner,  turn  off  the  power,  and  reset  the  test 
cover to its original position. 

Fit the seal into the drain joint, then insert the drain joint into the 
base pan hole of outdoor, rotate 90° to securely assemble them. 
Connect  the  drain  joint  with  an  extension  drain  hose  (Locally 
purchased), in case of the condensate draining off the outdoor 
unit during the heating mode. 

The drain plug is used to empty the water-receiver for
maintenance of the air conditioner. Please stuff it imposition at 
all times during operation to avoid leakage. 

The body's pump pipe and the drainpipe (especially the
indoor  part)  should  be  covered  evenly  with  the  out-let  pipe 
sheath  (fittings)  and  be  bound  tightly  with  the  constrictor  to 
prevent condensation caused by entered air. 

To prevent water from flowing backwards into the air
conditioner  while  the  air  conditioner  stops,  please  lean  the 
drainpipe  down  toward  outdoor  (outlet-side)  at  a  degree  of 
over 1/ 50. And please avoid any bulge or water deposit.        

Do not drag the drainpipe violently when connecting to
prevent the body from being pulled. Meanwhile, one
supportpoint should be set every 1~1.5m to prevent the
drainpipe  from  yielding.Or  you  can  tie  the  drainpipe  with  the 
connecting pipe to fix it.

In the case of prolonged drainpipe, you had better tighten its 
indoor part with a protection tube to prevent it from loosing. 

If  the  outlet  of  the  drainpipe  is  higher  than  the  body's  pump 
joint,  the  pipe  should  be  arranged  as  vertically  as  possible. 
And the lift distance must be less than 200mm, otherwise the 
water will overflow when the air conditioner stops.

The  end  of  the  drainpipe  should  be  over  50mm  higher  than 
the  ground  or  the  bottom  of  the  drainage  chute,  and  do  not 
immerse  it  in  water.  If  you  discharge  the  water  directly  into 
sewage, be sure to make a U-form aquaseal by bending the 
pipe up to prevent the smelly gas entering the house through 
the drain pipe. 

Seal 

The base pan hole 

of outdoor unit 

Drain joint 

Seal 

The base pan  

of outdoor unit  

Drain  

joint 

Fig.9-1

All the pictures in this manual are for explanation
purpose  only.  They  may  be  slightly  different  from  the 
air  conditioner  you  purchased(depend  on  model).The 
actual shape shall prevail. 

9. CONNECT THE DRAIN PIPE

Install the drainpipe of the indoor unit

You can use a polyethylene tube as the drainpipe
(out-dia.37-39mm,  in-dia.32mm).  It  could  be  bought  at  local 
market or from your dealer. 

Set  the  mouth  of  the  drainpipe  onto  the  root  of  the  body's 
pump-pipe, and clip the drainpipe and the out-let pipe sheath 
(fittings) together firmly with the out-let pipe clasp (fitting). 

The outdoor unit is factory charged with refrigerant. Some
systems require additional charging of refrigerant depending
on pipe lengths. The additional refrigerant to be charged
can be calculated from the following formule: 

14 

installation manual 

R22: (Pipe length-5m)x30g/m 
R410A:

/LTXLGVLGHij3LSHOHQJWKP[JP

/LTXLGVLGHij3LSHOHQJWKP[JP

15 

installation manual 

The temperature of refrigerant circuit will be high, please
keep the interconnection cable away from the copper tube. 

Dissemble the  bolts  from  the  cover.(If  there  isn't  a  cover  on  
the outdoor unit, disassemble the bolts from the maintenance  
board, and pull it in the direction of the arrow to remove the  
protection board.) 

(Refer to Fig.10-1a

ǃ

Fig.10-1b

ǃ

Fig.10-1c)

Connect the  connective cables to  the  terminals as  identified  
with  their  respective mached numbers on  the  terminal block  
of indoor and outdoor units. 

Re-install the cover or the protection board. 

Connect the cable 

10.1

The  power connection for  the  air  conditioner has  to  be  
done at the main power distribution. The distribution has  
to  be  of  a  low  impedance,  normally  the  required  
impedance reaches at a 32 A fusing point. 

No other equipment has to be connected with this power  
line. 

For  detailed installation acceptance please refer  to  your  
power supplier,  if  restrictions  do  apply for  products  like  
washing machines, air conditioners or electrical ovens.  

For power details of the air conditioner refer to the rating  
plate of the product.  

For any question contact your local dealer. 

10. WIRING

The appliance shall be installed in accordance with
national wiring regulations.

The air conditioner should use separate power supply
with rated voltage.

The external power supply to the air conditioner should
have ground wiring, which is linked to the ground wiring
of the indoor and outdoor unit.

The wiring work should be done by qualified persons
according to circuit drawing.

An all-pole disconnection device which has at least 3mm
sepaaration distance in all pole and a residual current
device (RCD) with the rating of above 10mA shall be
incorporated in the fixed wiring according  to the national
rule.

Be sure to locate the power wiring and the signal wring
well to avoid cross-disturbance.

Do  not turn on the power until you have checked
carefully after wiring.

The power cord type designation is H07RN-F.

Remark per EMC Directive 2004/108/EC 
For  to  prevent  flicker  impressions  during  the  start  of  the  
compressor  (technical  process)  following  installation  
conditions do apply. 

NOTE

Fig.10-1a

NOTE

Protection board 

Cover 

All the pictures in this manual are for explanation
purpose  only.  They  may  be  slightly  different  from  the 
air  conditioner  you  purchased(depend  on  model).The 
actual shape shall prevail. 

10.4  Outdoor unit 

Wrong wiring connections may cause some electrical parts to 
malfunction. 

The wiring must be operated according to the wiring scheme,or it damages the unit. 

Before obtaining access to terminals, all supply circuits must be disconnected. 

(the figure is for the unit with the twins function) 

(the figure is for the unit with the new fan function) 

(the figure is for the unit with the new fan function) 

CAUTION

Remove the electric parts cover from the outdoor unit. 

Connect the connective cables to the terminals as identified 
with their respective matched numbers on the terminal block 
of indoor and outdoor units. (Connective cable sheath
length to be removed and insert into the terminal block.)

To prevent the ingress off water, from a loop of the
connective cable as illustrated in the installation diagram of 
indoor and outdoor units.

Insulate unused cords (conductors) with PVC-tape. Process 
them so they do not touch any electrical or metal parts.

1.  

2.  

3.  

4.  

Fig.10-2

Cord wire

40mm

10mm

16 

installation manual 

The Specification of Power 

10.2

Wiring figure 

10.3

(Refer to Table10-1~Table10-8)

(Refer to Fig.10-3  Fig.10-10)

11. TEST OPERATION

The test operation must be carried out after the entire
installation has been completed.

Please confirm the following points before the test operation:

According to the user's requirement, install the remote
controller frame where the remote controller's signal can
reach the indoor unit smoothly. 

Test operation 

The indoor unit and outdoor unit are installed properly. 
Tubing and wiring are correctly completed. 
The refrigerant pipe system is leakage-checked. 
The drainage is unimpeded. 
The heating insulation works well. 
The ground wiring is connected correctly. 
The  length  of  the  tubing  and  the  added  stow  capacity  of 
the refrigerant have been recorded. 
The power voltage fits the rated voltage of the air
conditioner. 
There is no obstacle at the outlet and inlet of the outdoor 
and indoor units. 
The gas-side and liquid-side stop valves are both opened. 
The air conditioner is pre-heated by turning on the power. 

Set the air conditioner under the mode of "COOLING" with the 
remote  controller,  and  check  the  following  points.  If  there  is 
any  malfunction,  please  resolve  it  according  to  the  chapter 
"Troubleshooting" in the "Owner's Manual".  

1) The indoor unit
a. Whether the switch on the remote controller works well.
b. Whether the buttons on the remote controller works

well.

c. Whether the air flow louver moves normally.
d. Whether the room temperature is adjusted well.
e. Whether the indicator lights normally.
f. Whether the temporary buttons works well.
g. Whether the drainage is normal.
h. Whether there is vibration or abnormal noise during
    operation 

2) The outdoor unit
a. Whether there is vibration or abnormal noise during

operation.

b. Whether the generated wind, noise, or condensed of by
    the air conditioner have influenced your neighborhood. 
c. Whether any of the refrigerant is leaked.

17 

installation manual 

I. Whether the air conditioner heats well in the case of the
    HEATING/COOLING type.

Circuit  breaker 

Power wiring  (indoor) 

Indoor unit 

Indoor unit 

(primary  
unit) 

(secondary  
 unit) 

Outdoor unit 

CENTRAL CONTROL 
MONITOR(CCM) 

COMPUTER 

Power supply 

Power supply 

Circuit  breaker 

Power wiring  (indoor) 

Power supply 

Communication Bus 

Communication Bus 

Power wiring  (outdoor) 

Circuit  breaker 

18 

installation manual 

20 

installation manual 

22 

installation manual 

19 

installation manual 

21 

installation manual 

23 

installation manual 

Fig.10-7

Fig.10-9

Fig.10-10

7.1  Length and drop height permitted of the
       refrigerant piping

7. REFRIGERANT PIPE(the unit with the

twins function)

Note: Reduced length of the branching tube is the 0.5m of
the equivalent length of the pipe. 

Table.7-1 

Permitted value 

Piping

Total pipe length (Actual)

Indoor unit to indoor unit drop height

(farthest from the line
pipe branch) 

(farthest from the line
pipe branch) 

   Pipe length

   Drop height

Indoor unit-outdoor unit
drop height

30m 

18K+18K 

24K+24K/ 
30K+30K 

50m 

15m 

10m 

   20m 

    0.5m 

L+L1+L2 

L1,L2 

L1-L2 

H1 

H2 

Fig.7-1

L

L

Outdoor unit  

The line branch pipe 

Drop height between indoor 

wpkv"cpf"qwvfqqt"wpkv"Jœ42o"

 Indoor unit to intdoor unit  

"ftqr"jgkijv"Jœ207o"

Indoor unit 

Note: All used branch pipe must be produced by Midea,otherweise it causes malfunction. 
The indoor units should be installed equivalently at the both side of the U type branch pipe.

Fig.7-2

10° 
10° 

Fig.7-3

The branching pipe must be installed horizontally, error angle 
of it should not large than 10°. Otherwise, malfunction will be 
caused. 

Correct 

Wrong 

U-shaped branching pipe

Horizontal surface 

A direction view  

Use the vacuum pump which vacuum level lower than  
-0.1MPa and the air discharge capacity above 40L/min.

The outdoor unit is not necessary to vacuum, don’t open the 
outdoor unit gas and liquid pipe shut-off valves. 

Make  sure  the  vacuum  pump  could  result  as  -0.1MPa  or 
below after 2 hrs or above operation. If the pump operated 3 
hrs or above could not achieve to -0.1MPa or below, please 
check whether water mix or gas leak inside of the pipe. 

7.2   Vacuum with vacuum pump 

1) 

2) 

3) 

CAUTION

7.3  Refrigerant amount to be added 

Don’t  mix  up  the  different  refrigerants  or  abuse  the  tools  and 
measurements which directly contact with refrigerants. 

Don’t adopt refrigerant gas for air vacuuming. 

If vacuum level could not get to -0.1MPa, please check whether 
resulted  by  leakage  and  confirm  the  leakage  site.If  no  leakage, 
please operate the vacuum pump again 1 or 2 hrs.  

Connect with vacuum pump 

Perform the pump (last for 2 hrs or above) 

When get the vacuum level 
-0.1MPa, the pump should
keep running for 20-60 mins

Shut down the  
vaccun pump 

Place the vaccum state unused (1 hrs or above) 

1. Close-off the valve of
vacuum meter.
2. Cut off the connection
between pressure meter
and vacuum pump.
3. Close the vacuum
pump. 

Fig.10-6

Ground wiring

Ground wiring

Power supply

Switch/Fuse 

(Available locally)

Power wiring (indoor)

Power linking wiring (Outdoor)

Weak elec-signal link wiring

Indoor

Unit

Out door

Unit

Power supply

Ground the air conditioner properly in case to affect its
anti-interference function

CAUTION

the power of new fan motor is less than or equal to 200W 

the power of new fan motor is more than 200W 

QSQ4I-016AEN 

202000192390 

20140304 

The design and specifications are subject to change without prior notice for product 
improvement.Consult with the sales agency or manufacturer for details.      

QUANTITY

Tubing & Fittings 

Remote controller & Its Frame 

Drainpipe Fittings 

Installation Fittings 

SHAPE

NAME

13. Expansible hook

3. Out-let pipe sheath

4. Out-let pipe clasp

5. Drain joint(on some models)

6. Seal ring(on some models)

11. Owner's manual

12. Installation manual

7. Remote controller

8. Remote controller holder

9. Mounting screw(ST2.9×10-C-H)

10. Alkaline dry batteries (AM4)

14. Installation hook

1. Installation paper board

(on some models)

(on some models)

(on some models)

(on some models)

2. Soundproof / insulation sheath

15 .Orifice 

Installation accessory

(The product you have might not be

 provided the following accessory)

(The product you have might not be

 provided the following accessory)

80mm

80mm

Ø75mm

MODLE  (18-60) 

852  582  368  390  328 

660 

340 

760  530  290  315  270 

590 

285 

760  530  290  315  270 

590 

285 

MODEL

A

B C D E 

H F 

24

18

30

36

845  560  335  360  312 

700 

320 

900  590  333  355  302 

860 

315 

990  624  366  396  340 

965 

345 

990  624  366  396  340 

965 

345 

990  624  366  396  340 

965 

345 

990  624  366  396  340 

965 

345 

990  624  366  396  340 

965 

345 

590  378  400  330 

1170 

350 

900 

42

48

60

12

Fig.6-2

Fig.6-2

Fig.6-2

Fig.6-2

Fig.6-2

900  590  333  355  302 

860 

315 

Fig.6-2

Fig.6-2

Fig.6-2

Fig.6-2

Fig.6-2

Fig.6-2

Fig.6-3

590  378  400  330 

1170 

350 

900 

Fig.6-3

Fig.6-3

634  404  448  368 

1369 

392 

938 

634  404  448  368 

1369 

392 

938 

634  404  448  368 

1369 

392 

938 

634  404  448  368 

1369 

392 

938 

Fig.6-3

Fig.6-3

Fig.6-3

Fig.6-7

3. Centrifugal fan outdoor unit

A

1394 

1174 

B

1338 

1120 

C

783 

680 

D

820 

720 

E

850 

750 

F

568 

475 

G

398 

300 

H

574 

430 

I

342 

265 

J

463 

1394  1338  783  820  850  568  398  574  342  463 

1338  783  820  850  568  398  574  342  463 

393 

MODEL

36

48

60

18

1174  1120  680  720  750  475  300  430  265  393 

24

1394 

1. Split type outdoor unit

Fig.6-11

ß"

ß"

ß"

a)

In case that suspending in the ceiling

3. Centrifugal fan outdoor unit

Fig.6-12

ß"

ß"

ß"

b)In case that installing on the floor

6.4  Available configuration  

NOTE

Four different configuration are available for oudoor unit only  

changing the panels and fan position. 

Keep in mind that fan unit weight is aprox 30kg ,the unit as  

well as relevant equipment covered with the vinyl cover  

during installation work. 

To change air inlet is only necessary to interchange the  

indicated panels position. Both panels  

use 

 screws to be fixed 

to unit chas 

is. 

Air inlet modification 

Change Panel 

Fig6-13

All  the  figures in  this  manual  are  for  explanation
purpose only. They may be slightly different from the air  

The actual unit shall prevail.  

NOTE

conditioner you purchased. 

To change air outlet is necessary to interchange panels too. 

Fan outlet panel is attached to fan structure, which must be 

mounted as  

follow 

Fig.6-14

Foundation could be on flat and is recommended be 100-300mm 
higher than ground level. 
Install a drainage around foundation for smooth drain 
When installing the outdoor unit fix the unit by anchor bolts of 
M10. 
When installing the unit on a roof or a veranda,drain water 
sometimes turns to ice on a cold morning. Therefore, avoid 
draining in an area that people often use because it is slippery. 


Concrete Foundation 

1. Suspend the unit as the drawing indicates.

NOTE: Make sure 3-4 degree of angel is kept between the unit and  
            the floor when the unit is installed in the low temperauture 
            and humid environment. 
            Make sure the ice on the chassis of the outdoor unit can be 
            dealt with when the unit is installed in the low temperature 
            and humid enviroment. 
            The outdoor unit should be installed in mounting rack 30cm 
             high.The enviroment temperature should be above 0°. 
            The machine must be installed indoor

.

2. Ensure that ceiling can resist the Outdoor unit weight indicated

in specification label plate.

Suspended unit 

No 

    Description 

 1      Outdoor Unit 

 2 

Vibration-proof rubber 

 3      Anchor Bolt M10 

 4      Drainage (Wide 100×Depth 150) 

 5      Drainage 

ROHĭî'HSWK

Sling Bolt 

Outfall 

Suspension Bracket 

Table 6-4 

Table 6-5 

mm 

 Model Unit 

B

1120

720 

1338

820 

1338

820 

18~24 

30~36 

48 

Fig.6-16

Fig.6-17

Fig.6-18

ß322"

0 0 1

0 0 3

Drainage test 

Drainage test 

Check whether the drainpipe is unhindered. 

New built house should have this test done before paving 
the ceiling. 

The unit with pump. 

Remove  the  test  cover,  and  stow  about  2000ml  water  to  the 
water pan. 

Operate the air conditioner in "COOLING" mode. The sound of 
the  drain pump  shall  be  heard.  Check  whether  the  water  is 
discharged well (1 min lag is possible, according to the length of 
the  drain pipe),  and  check  whether  the  water  leaks  from  the 
joints. 

Power off the air conditioner and recover the cap. 

Table 10-1 

Table 10-2 

The Specification of Power(indoor power supply) 

The Specification of Power(outdoor power supply) 

20/16

40/25

50/30

60/45

60/50

40/30

60/40

70/55

70/60

MODEL

POWER 

CIRCUIT BREAKER/FUSE(A) 

PHASE 

FREQUENCY AND VOLT 

18 

24 

60

30~36

42~48

208-240V

208-240V

1Phase

1Phase

208-240V

1Phase

208-240V

1Phase

208-240V

1Phase

MODEL

POWER 

CIRCUIT BREAKER/FUSE(A) 

PHASE 

FREQUENCY AND VOLT 

30~36

30~36

42~60

42~60

380-420V
25/20 

25/20  40/25 45/35 

208-240V

3Phase

380-420V

3Phase

3Phase

208-240V

3Phase

Table 10-3 

Table 10-4 

MODEL

POWER 

CIRCUIT BREAKER/FUSE(A) 

PHASE 

FREQUENCY AND VOLT 

24 

60

30~36

42~48

208-240V

1Phase

208-240V

1Phase

208-240V

1Phase

208-240V

1Phase

MODEL

POWER 

CIRCUIT BREAKER/FUSE(A) 

PHASE 

FREQUENCY AND VOLT 

30~36

30~36

42~60

42~60

380-420V
25/20 

25/20  40/25 45/35 

208-240V

3Phase

380-420V

3Phase

3Phase

208-240V

3Phase

The Specification of Power(independence power supply) 

The Specification of Power for the invert type air conditioner(independence power supply) 

20/16

40/25

50/30

60/45

60/50

208-240V

208-240V

1Phase

1Phase

208-240V

1Phase

208-240V

1Phase

208-240V

1Phase

MODEL

POWER 

(indoor) 

POWER 
(outdoor) 

POWER 

(indoor) 

POWER 
(outdoor) 

CIRCUIT BREAKER/FUSE(A) 

CIRCUIT BREAKER/FUSE(A) 

PHASE 

FREQUENCY AND VOLT 

PHASE 

FREQUENCY AND VOLT 

18 

24 

60

30~36

42~48

208-240V

208-240V

1Phase

1Phase

208-240V

1Phase

208-240V

1Phase

208-240V

1Phase

20/16  20/16 20/16  20/16  20/16

208-240V

1Phase

208-240V

1Phase

208-240V

1Phase

208-240V

1Phase

20/16

20/16  20/16 20/16 

MODEL

CIRCUIT BREAKER/FUSE(A) 

CIRCUIT BREAKER/FUSE(A) 

PHASE 

FREQUENCY AND VOLT 

30~36

30~36

42~60

42~60

380-420V
25/20

25/20  40/25 45/35 

208-240V

3Phase

380-420V

3Phase

3Phase

208-240V

3Phase

Table 10-5 

Table 10-6 

PHASE 

FREQUENCY AND VOLT 

POWER 

(indoor) 

POWER 
(outdoor) 

30/20 30/20

40/30

40/35

50/40

208-240V

208-240V

1Phase

1Phase

208-240V

1Phase

208-240V

1Phase

208-240V

1Phase

MODEL

POWER 

(indoor) 

POWER 
(outdoor) 

POWER 

(indoor) 

POWER 
(outdoor) 

CIRCUIT BREAKER/FUSE(A) 

CIRCUIT BREAKER/FUSE(A) 

PHASE 

FREQUENCY AND VOLT 

PHASE 

FREQUENCY AND VOLT 

18 

24 

60

30~36

42~48

220-240V

220-240V

1Phase

1Phase

220-240V

1Phase

220-240V

1Phase

220-240V

1Phase

15/10  15/10 15/10  15/10  15/10

220-240V

1Phase

220-240V

1Phase

220-240V

1Phase

220-240V

1Phase

15/10

15/10 15/10 15/10 

MODEL

CIRCUIT BREAKER/FUSE(A) 

CIRCUIT BREAKER/FUSE(A) 

PHASE 

FREQUENCY AND VOLT 

30~36

30~36

42~60

42~60

380-420V
30/20

30/25 50/40 50/40 

208-240V

3Phase

380-420V

3Phase

3Phase

208-240V

3Phase

Table 10-7 

Table 10-8 

PHASE 

FREQUENCY AND VOLT 

POWER 

(indoor) 

POWER 
(outdoor) 

The power supply is included in the power supply above mentioned can be applied to the table. 

CAUTION

Wiring figure 

Fig.10-3

Fig.10-4

Ground wiring 

Ground wiring

Power supply

Switch/Fuse
(Available locally) 

Power wiring (indoor)

Power linking wiring (Outdoor)

Strong elec-signal link wiring

Weak elec-signal link wiring

Indoor 

Unit 

Outdoor 

Unit 

Ground the air conditioner properly in case to affect its anti-interference function

Ground wiring 

Ground wiring

Power supply

Switch/Fuse

(Available locally) 

Power wiring (outdoor)

Power linking wiring (indoor)

Strong elec-signal link wiring

Weak elec-signal link wiring

Indoor 

Unit 

Outdoor 

Unit 

Ground the air conditioner properly in case to affect its anti-interference function

Fuse

AC CONTACTOR

DC RELAY/

L

N

220-240V~ 

INDOOR UNIT 

NEW FAN  
MOTOR 

NEW FAN 

NEW FAN 

220-240V~ 

INDOOR UNIT 

NEW FAN  
MOTOR 

Fig.10-5

Ground wiring 

Ground wiring

Power supply

Switch/Fuse

(Available locally) 

Power wiring (outdoor)

Strong elec-signal link wiring

Weak elec-signal link wiring

Indoor 

Unit 

Outdoor 

Unit 

Ground the air conditioner properly in case to affect its anti-interference function

Fig.10-8

Ground wiring 

Ground wiring

Power supply

Switch/Fuse

(Available locally) 

Power wiring (outdoor)

Power linking wiring (indoor)

Weak elec-signal link wiring

Indoor 

Unit 

Outdoor 

Unit 

Ground the air conditioner properly in case to affect its anti-interference function

Fig.6-5

Table 6-2

unit

˖

mm 

Fig.6-6

2. Vertical discharge type outdoor unit

633 

554 

554 

633 

554 

554 

759 

759 

554 

554 

633 

600 

600 

710 

710 

843 

710 

710 

MODEL

DIMENSIONS   

36 

48 

60 

36 

24 

18 

Refore to  

Fig.6-5
Fig.6-6

REMARK

>30cm

>30cm

>200cm

>60cm

(Wall or obstacle)

Maintain channel

Air outlet

Air inlet

Air inlet

>120cm

Air Outlet

(Wall or obstacle)

Fig.6-9

Fig.6-8

6.3   Space of installation and maintenance 

6.2   Figure of body size 

1.

Split type

 outdoor unit

2. Vertical discharge type outdoor unit

>30cm

>30cm

>30cm

>30cm

Air inlet

Air inlet

Air inlet

Air inlet

Fig.6-10

(Wall or obstacle)

Fig.10-1b

Protection Board

Vertical discharge type outdoor unit

Fig.10-1c

Protection Board

Centrifugal fan outdoor unit 

EMC & Its Fitting 
(on some models) 

16. Magnetic ring

(twist the electirc wires P&Q&E around  
the magnetic ring to two circles) 

K

TIM

Содержание KTIM series

Страница 1: ...ur way Cassette Type INSTALLATION MANUAL Thank you very much for purchasing our air conditioner Before using your air conditioner please read this manual carefully and keep it for future reference KTI...

Страница 2: ...door Unit Installation 11 a Outdoor Unit Installation Instructions 11 b Outdoor Unit Types and Specifications 12 c Notes on Drilling Hole in Wall 13 Drainpipe Installation 14 Table of Contents Install...

Страница 3: ...efrigerant Piping Connection Instructions 17 Wiring 19 a Outdoor Unit Wiring 19 b Indoor Unit Wiring 20 c Power Specifications 21 d Wiring Diagram 22 Air Evacuation 23 a Evacuation Instructions 23 b N...

Страница 4: ...lation sheath some models 1 Drainpipe Fittings Outlet pipe sheath some models 1 Outlet pipe clasp some models 1 Drain joint some models 1 Seal ring some models 1 Installation Accessory some models Cei...

Страница 5: ...ong winds typhoons and earthquakes that might affect your unit and locate it accordingly Failure to do so could cause the equipment to fail After installation ensure there are no refrigerant leaks and...

Страница 6: ...7 8 Install the indoor unit Page 7 INSTALLATION ORDER Install the outdoor unit Page 11 Install the drainpipe Page 14 Evacuate the refrigeration system Page 23 Connect the wires Page 19 Connect the ref...

Страница 7: ...property damage or death Install the indoor unit at a height of more than 2 5m 8 above the floor DO NOT install the indoor unit in the bathroom or laundry room as excessive moisture can short the unit...

Страница 8: ...cations In areas with oil drilling or fracking In coastal areas with high salt content in the air In areas with caustic gases in the air such as near hot springs In areas with power fluctuations such...

Страница 9: ...rom ceiling relative to height of indoor unit MODEL Length of A mm inch Length of H mm inch 18 205 8 235 9 3 24 205 8 235 9 3 30 205 8 235 9 3 30 48 245 9 6 275 10 8 48 60 287 11 3 317 12 5 Step 2 Han...

Страница 10: ...board Main body 10 18mm 0 4 0 7 L NOTE Ensure that the indoor unit is level The unit is equipped with a built in drain pump and float switch If the unit is tilted against the direction of condensate...

Страница 11: ...length between the outdoor and indoor unit may not exceed the maximum allowable pipe length If possible DO NOT install the unit where it is exposed to direct sunlight If possible make sure the unit i...

Страница 12: ...ble 5 2 Fig 5 7 Fig 5 8 Fig 5 9 Outdoor Unit Installation Fig 5 6 Fig 5 5 A B D W H W H Fig 5 4 Outdoor Unit Dimensions W x H x D Mounting Dimensions Distance A Distance B 760x590x285 29 9x23 2x11 2 5...

Страница 13: ...int 90 until it clicks in place facing the front of the unit 4 Connect a drain hose extension not included to the drain joint to redirect water from the unit during heating mode NOTE Make sure the wat...

Страница 14: ...ation may cause unit and property damage CAUTION Insulate all piping to prevent condensation which could lead to water damage If the drainpipe is bent or installed incorrectly water may leak and cause...

Страница 15: ...Wall Indoor Outdoor 12mm 0 5 inch Fig 6 5 NOTE When drilling the wall hole make sure to avoid wires plumbing and other sensitive components 4 Pass the drain hose through the wall hole Make sure the wa...

Страница 16: ...rant leakage after completing the installation work Notes On Pipe Length and Elevation Ensure that the length of the refrigerant pipe the number of bends and the drop height between the indoor and out...

Страница 17: ...while cutting Be extra careful not to damage dent or deform the pipe while cutting This will drastically reduce the heating efficiency of the unit 1 Make sure that the pipe is cut at a perfect 90 angl...

Страница 18: ...ue wrench to tighten the flare nut according to the torque values in table 7 5 NOTE Use both a spanner and a torque wrench when connecting or disconnecting pipes to from the unit Fig 7 8 CAUTION Ensur...

Страница 19: ...t 3mm 0 118 DO NOT modify the length of the power cord or use an extension cord CAUTION Connect the outdoor wires before connecting theindoor wires Make sure you ground the unit The grounding wire sho...

Страница 20: ...onnection a Using wire strippers strip the rubber jacket from both ends of signal cable to reveal about 15cm 5 9 of the wires inside b Strip the insulation from the ends of the wires c Using wire crim...

Страница 21: ...420V 208 240V 208 240V CIRCUIT BREAKER FUSE A 25 20 32 25 32 25 45 35 Independent Power Supply Specifications MODEL Btu h 18K 19K 24K 25K 36K 37K 48K 49K 60K POWER indoor PHASE 1 Phase 1 Phase 1 Phase...

Страница 22: ...e 1 Phase 1 Phase 1 Phase 1 Phase FREQUENCY AND VOLT 220 240V 220 240V 220 240V 220 240V 220 240V CIRCUIT BREAKER FUSE A 15 10 15 10 15 10 15 10 15 10 POWER outdoor PHASE 1 Phase 1 Phase 1 Phase 1 Pha...

Страница 23: ...he manifold gauge Keep the High Pressure side closed 4 Turn on the vacuum pump to evacuate the system 5 Run the vacuum for at least 15 minutes or until the Compound Meter reads 76cmHG 1x105Pa 6 Close...

Страница 24: ...The additional refrigerant to be charged can be calculated using the following formula Liquid Side Diameter 6 35 1 4 9 52 3 8 12 7 1 2 R22 orifice tube in the indoor unit Total pipe length standard p...

Страница 25: ...d drain sides Hang the four latches of the decorative panel to the hooks of the indoor unit Tighten the panel hook screws evenly at the four corners See Fig 10 3 NOTE Tighten the screws until the thic...

Страница 26: ...e height of the indoor unit needs to be adjusted you can do so through the openings at the panel s four corners Make sure that the internal wiring and drainpipe are not affected by this adjustment CAU...

Страница 27: ...rature is being registered correctly d Ensure the indicators on the remote control and the display panel on the indoor unit work properly e Ensure the manual buttons on the indoor unit works properly...

Страница 28: ...t improvement Consult with the sales agency or manufacturer for details 2190 NW 89 Place Doral FL 33172 USA Tel 305 594 4972 Fax 305 675 2212 www klimaire com sales klimaire com The Klimaire logo is a...

Отзывы: