43
SECTION 5 Factory Prevalues and Setting Ranges
Menu
Submenu 1
Submenu 2
Description
Prevalue
Unit
Setting Range
BASIC
(bSc)
Ctr
Current
transformer
ratio
1
-
1 - 5000
Utr
Voltage
transformer
ratio
1.0
-
0.1 - 5000.0
ALARMS
(ALr)
V ALM
(Uolt)
HI
Voltage
alarm upper
limit
0.0
V
0.0 - 1500000.0
LO
Voltage
alarm lower
limit
0.0
V
0.0 - 1500000.0
hYSt
Voltage
alarm
hysteresis
value
5.0
V
0.0 - 1500000.0
dlY.t
Voltage
alarm delay
time
5
sn
0 - 60
I ALM
(Curr)
HI
Current
alarm upper
limit
0.0
A
0.0 - 30000.0
LO
Current
alarm lower
limit
0.0
A
0.0 - 30000.0
hYSt
Current
alarm
hysteresis
value
0.1
A
0.0 - 30000.0
dlY.t
Current
alarm delay
time
5
sn
0 - 60
COSQ ALM
(coSQ)
HI
cos φ alarmv
upper limit
0.00
-
0.00 - 1.00
LO
cos φ alarm
lower limit
0.00
-
0.00 - 1.00
hYSt
cos φ alarm
hysteresis
value
0.01
-
0.00 - 1.00
dlY.t
cos φ alarm
delay time
5
sn
0 - 60
SECTION 5 FACTORY PREVALUES AND SETTING RANGES
Содержание POWYS 1012
Страница 1: ...1 USER MANUAL Energy Analyzer...
Страница 4: ...4 SECTION 1 GENERAL INFORMATION Enerji Analiz r...
Страница 14: ...14 SECTION 2 INSTALLATION Energy Analyzer...
Страница 17: ...17 SECTION 2 INSTALLATION 2 4 Dimensions mm Fig 2 3 Dimensions...
Страница 18: ...18 SECTION 3 MENUS Energy Analyzer...
Страница 34: ...34 SECTION 4 RS485 COMMUNICATION Energy Analyzer...
Страница 42: ...42 SECTION 5 FACTORY PREVALUES AND SETT NG RANGES Energy Analyzer...
Страница 47: ...47 SECTION 6 TECHNICAL SPECIFICATIONS Energy Analyzer...