29
If you go outside of the alarm limit values:
• The value in the indicator for the related parameter starts blinking.
• Alarm icon or alarm LED is enabled on the display at the end of the delay time.
• If nothing has been assigned to the digital output, related output is enabled
at the end of the alarm delay time.
Alarm example:
Time
Upper limit
Hysteresis
Lower limit
Hysteresis
Amplitude
Fig. 3-6 Alarm Example(Alarm delay is set to be zero)
• Low limit alarm occurs at the A point
• Alarm disappears at the B point.
• High limit alarm occurs at the C point
• Alarm disappears at the D point.
3.11 Demand Time Setting (Demand)
This menu enables to set the demand time. See table 4 for the menu tree, table 6 for the setting
range.
The demand values calculated by the device is calculated throughout the time set in this menu
and this activity continuous periodically.
3.12 RS485 Setting (RS485)
(ATTENTION! : This menu is only valid for devices with RS485 output)
This menu enables to set baudrate, slave ID and parity control used in RS485 communication.
See table 4 for the menu tree and table 6 for the setting ranges.
SECTION 3 MENUS
Содержание POWYS 1012
Страница 1: ...1 USER MANUAL Energy Analyzer...
Страница 4: ...4 SECTION 1 GENERAL INFORMATION Enerji Analiz r...
Страница 14: ...14 SECTION 2 INSTALLATION Energy Analyzer...
Страница 17: ...17 SECTION 2 INSTALLATION 2 4 Dimensions mm Fig 2 3 Dimensions...
Страница 18: ...18 SECTION 3 MENUS Energy Analyzer...
Страница 34: ...34 SECTION 4 RS485 COMMUNICATION Energy Analyzer...
Страница 42: ...42 SECTION 5 FACTORY PREVALUES AND SETT NG RANGES Energy Analyzer...
Страница 47: ...47 SECTION 6 TECHNICAL SPECIFICATIONS Energy Analyzer...