SECTION 2 INSTALLATION

SECTION 2 INSTALLATION

2.1  Preparing for Installation

The purchased product may not include all hardware options referred in this document. This 

situation does not constitute an impediment to the electrical installation.

Assembly and related connections of the product, must be implemented by 

authorized persons in accordance with the instructions of user manual. 

The device must not be put into service if the operator is not sure that all connections 

are correctly accomplished.

2.2  Mounting

POWYS 10xx and POWYS 11xx are replaced onto 35mm standart rail.

Before wiring up voltage and current ends to POWYS, you must be sure that the 

power is cut.

The product is  connected to current transformer(s). Before disconnecting current 

transformer leads, be sure that they are short circuited elsewhere or connected to 

a parallel load which has sufficiently low impedance. Otherwise dangerously high 

voltages will be induced at the current transformer leads. Same phenomena also 

apply for putting into service. 

2.3  Connection Diagrams

2.3.1  Connections

POWYS 10xx and POWYS 11xx are replaced onto 35mm standart rail.

Содержание POWYS 1012

Страница 1: ...1 USER MANUAL Energy Analyzer...

Страница 2: ...Minimum and Demand Values 19 3 3 Energy Meters Energy Menu 20 3 4 Prevalue Assignme 21 3 5 Saving Procedure 21 3 6 Counters Menu 22 3 7 Settings Menu 23 3 8 Value Changing 28 3 9 Main Settings Basic...

Страница 3: ...f demand page Active power 20 Fig 3 3 Example of Import Active Energy Meter Display 21 Fig 3 4 Save Prosedure 22 Fig 3 5 Counters Menu 23 Fig 3 6 Alarm Example Alarm delay is set to be zero 29 Fig 3 7...

Страница 4: ...4 SECTION 1 GENERAL INFORMATION Enerji Analiz r...

Страница 5: ...and stores in its memory the maximum and minimum values reached by current voltage frequency cos power factor THDV THDI active reactive and apparent powers Assigns alarms for current voltage frequenc...

Страница 6: ...ections should be established in accordance with the instructions set out in the manual by authorized persons Unless the connection is built properly device should not be operated Before wiring the de...

Страница 7: ...nts that arise out of the failure to follow the above cautions 1 3 Connection Types POWYS 1110 POWYS 1120 POWYS 1012 POWYS 1022 POWYS 1023 Fig 1 1 Connections 1 4 General View Definitions Supply termi...

Страница 8: ...ted when giving pulse from the 1st pulse output activated when giving pulse from the 2nd pulse output activated during RS485 communication activated if the value shown is inductive activated if the va...

Страница 9: ...ect Switches between menus No effect Changes value No effect Changes value No effect UP Switches between menus No effect Switches between menus No effect Changes value No effect Changes value No effec...

Страница 10: ...NT max min demand FREQ max min COSQ max min PF max min POWER P max min demand POWER Q max min demand POWER S max min demand THD V max min THD I max min Table 1 2 Instantaneous measurements and submenu...

Страница 11: ...AP d AP tHdU H t U L t U tHdI H t I L t I Table 1 3 Instantaneous measurements and submenus 7 Segment devices Energy meters counters odd harmonics between 1 31 and menus showing the settings are provi...

Страница 12: ...EXPORT REACTIVE COUNTERS RUN HOUR ON HOUR POWER INT COUNTER HARMONICS V HARM V HARM 1 V HARM 3 V HARM 31 I HARM I HARM 1 I HARM 3 I HARM 31 SETTINGS SETTINGS MENU TREE Table 1 4 Energy counter harmon...

Страница 13: ...acitive Cos capacitive PF positive QUADRANT 3 P negative Q negative inductive Cos inductive PF negative S P Q Fig 1 5 Four Quadrant Representation NOTE If the signs of active and reactive power are ex...

Страница 14: ...14 SECTION 2 INSTALLATION Energy Analyzer...

Страница 15: ...l connections are correctly accomplished 2 2 Mounting POWYS 10xx and POWYS 11xx are replaced onto 35mm standart rail Before wiring up voltage and current ends to POWYS you must be sure that the power...

Страница 16: ...2 INSTALLATION Current Voltage Fig 2 1 Connection Diagram 2 3 2 Digital Output Connection Diagram External DC Power Supply must be connected 5 30VDC y k DO DO Fig 2 2 Digital Output Connection Diagram...

Страница 17: ...17 SECTION 2 INSTALLATION 2 4 Dimensions mm Fig 2 3 Dimensions...

Страница 18: ...18 SECTION 3 MENUS Energy Analyzer...

Страница 19: ...shown in 9 999 999 9 kWh kVArh format 3 2 Maximum Minimum and Demand Values Minimum and maximum values of the voltage current frequency Cos power factor active power reactive power apparent power THD...

Страница 20: ...demand page Active power icon appearing in the menus which shows minimum values refer to the fact that no value has yet to be saved as a minimum value 3 3 Energy Meters Energy Menu Under the ENERGY me...

Страница 21: ...nue to count after being resetted subsequent to the 99 999 999 kWh kVArh value For Powys1023 all the meters continue to count after being resetted subsequent to the 9 999 999 9 kWh kVArh value Fig 3 3...

Страница 22: ...exit the menu without saving the changes made Fig 3 4 Save Prosedure 3 6 Counters Menu The following counters are valid under the COUNTERS menu ON HOUR The total on hour of the device is counted and...

Страница 23: ...9 999 999 and then continue to count Value assignment and resetting only apply to the RUN HOUR meter In order to assign any value to the meter prevalue assigning procedure is applied See Prevalue Assi...

Страница 24: ...nsformer ratio ALARMS ALr V ALM Uolt Alarm settings HI Voltage alarm settings LO Voltage alarm upper limit hYSt Voltage alarm lower limit dlY t Voltage alarm hysteresis value I ALM Curr Current alarm...

Страница 25: ...t cos alarm delay time PF ALM PF Power factor alarm settings HI Power factor alarm upper limit LO Power factor alarm lower limit hYSt Power factor alarm hysteresis value dlY t Power factor alarm dela...

Страница 26: ...meter setting OFF Off IMP ACT I Act Assign to the import active energy meter EXP ACT E Act Assign to the export active energy meter IMP REA I rEA Assign to the import reactive energy meter OUT2 Out2 E...

Страница 27: ...Homepage apparent power THD V tHdU Homepage THD Voltage THD I tHdI Homepage THD Current BACKLGHT Display backlight setting ATTENTION This menu is only valid for devices with LCD oPt Display backlight...

Страница 28: ...he number of your choice press the left button to complete the selection If a change is made in the settings when you return to the SETTINGS menu saving procedure is enabled asking whether or not to s...

Страница 29: ...curs at the A point Alarm disappears at the B point High limit alarm occurs at the C point Alarm disappears at the D point 3 11 Demand Time Setting Demand This menu enables to set the demand time See...

Страница 30: ...elect the type of the digital outputs See the menu tree for table 4 and table 6 for the step ranges Digital output type tYPE Option to assign to the pulse output PULSE In order to use the related outp...

Страница 31: ...is up This duration of time may be adjusted via the related menu See table 4 for the menu tree and table 6 for the setting ranges If no button is pressed after entering the password or no setting cha...

Страница 32: ...and lighting LEDS with longer shelf life CONTINOUSLY ON CONT ON The display backlight stays continously on CONTINOUSLY OFF CONT OFF The display backlight stays continuously off Display backlight on ti...

Страница 33: ...into YES Then press the left button to confirm the activity Press the right button so that NO sign starts blinking Pressing the left button confirm the NO option and exit the menu without clearing any...

Страница 34: ...34 SECTION 4 RS485 COMMUNICATION Energy Analyzer...

Страница 35: ...float RO 40005 Frequency float RO 40007 Cos float RO 40009 Power factor float RO 40011 Active power float RO 40013 Reactive power float RO 40015 Apparent power float RO 40017 THDV float RO 40019 THDI...

Страница 36: ...40087 Max Current float RO 40089 Max Frequency float RO 40091 Max Cos float RO 40093 Max Power Factor float RO 40095 Max Active Power float RO 40097 Max Reactive Power float RO 40099 Max Apparent Powe...

Страница 37: ...2 bit integer RO 40139 Power interruption meter 32 bit integer RO 40141 Import Active Energy 32 bit integer R W If the password protection is enabled enter your password in the Settings Protection add...

Страница 38: ...R W 40173 RESERVE 32 bit integer R W 40175 RESERVE 32 bit integer R W 40177 RESERVE 32 bit integer R W 40179 RESERVE 32 bit integer R W 40181 RESERVE 32 bit integer R W 40183 Menu Browsing On Off 32...

Страница 39: ...37 Setting Protection 32 bit integer R W The address to enter the device password While reading via the 03H function it shows the enabled disabled status of the password protection COMMANDS 41001 Rese...

Страница 40: ...ld enter 2222 in this address If you write 0 in this address it turns off the meter assignment Table 4 1 MODBUS table 4 1 Applying Multiple Option Settings With Modbus Modbus addresses values that may...

Страница 41: ...15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Reserve I OFF V OFF Freq Low Freq High PF Low PF High Cos Low Cos High I Low I High V Low V High bit description 31 12 Reserve 11 I OFF No current in the current...

Страница 42: ...42 SECTION 5 FACTORY PREVALUES AND SETT NG RANGES Energy Analyzer...

Страница 43: ...0 hYSt Voltage alarm hysteresis value 5 0 V 0 0 1500000 0 dlY t Voltage alarm delay time 5 sn 0 60 I ALM Curr HI Current alarm upper limit 0 0 A 0 0 30000 0 LO Current alarm lower limit 0 0 A 0 0 300...

Страница 44: ...65 0 hYSt Frequency alarm hysteresis value 2 0 Hz 0 0 20 0 dlY t Frequency alarm delay time 5 sn 0 60 DEMAND dEd dEd t Demand time setting 15 dk 1 60 RS485 485 bAud Baud rate options 38400 Baud 1200...

Страница 45: ...2nd pulse output step range 1 Wh Varh Powys1023 kWh kVarh 1 99 999 999 SECURITY PIn Act Enable disable password protection NO NO YES Pin t Password protection timeout duration 10 min 1 60 Pin Passwor...

Страница 46: ...46 CLEAR CLr CLr Clear menu OFF OFF ALL ENERGY COUNTERS MAX VALS MIN VALS DEMANDS SETTINGS ALARMS Table 5 1 Factory Prevalu SECTION 5 FACTORY PREVALUES AND SETTING RANGES...

Страница 47: ...47 SECTION 6 TECHNICAL SPECIFICATIONS Energy Analyzer...

Страница 48: ...nt 10mA 6A AC Frequency 45 65Hz DIGITAL OUTPUT Output Type Transistor Switching Voltage 5 30V DC Maximum Switching Current 50mA Isolation 3750V RMS 50mA COMMUNICATION Baudrate Setting 1200 2400 4800 9...

Страница 49: ...SA Total Apparent Power 0 5 10 Ib I Imax 0 5 Ind to 0 8 Cap EA 0 5 IEC 62053 22 Class 0 55 ErV 2 IEC 62053 23 Class 2 f Frequecy 0 1 45 65 Hz I Phase Current 0 5 20 Ib I Imax INc Neatral Current Meas...

Страница 50: ...50 Revision No 23022017 www klemsan com info klemsan com tr K z l z m Mahallesi Kemalpa a K z l z m Cad No 15 35730 Kemalpa a zmir TURKEY Tel 90 232 877 08 00 Fax 90 232 877 08 06...

Отзывы: