background image

EN54-3
Fire Alarm Device – Sounder
Type B: For indoor or outdoor use
18-980544/555/556/660/662/589/622/623/664/665/666
Technical Data: Document 18-186529

0832

07

0832-CPD-0618 (Sounder-LED Beacon)
0832-CPD-0619 (Sounder-Xenon Beacon)
0832-CPD-0620 (Sounder)

Nexus 110 DC Sounder & Sounder-Beacon

Installation Instructions

Klaxon Signals Ltd, Oldham, OL4 1HW, UK

Phone +44 161 287 5555

Fax +44 161 287 5511

E-mail [email protected]

Issue 6 (January 2008) 18-186458

Copyright © Klaxon Signals Ltd

www.klaxonsignals.com

Tone

Tone Type

Tone Description / Application

Dip Switch

3rd Stage

Peak Sound

Sounder

(S1/S2)

Tone

Level (dBA@1m) Current (mA Avg)

1.

970Hz (BS5839-1:2002)

O-O-O-O-O-O

18

110

45

2.

800Hz/970Hz @ 2Hz (BS5839-1:2002)

O-O-O-O-O-I

1

110

44

3.

800Hz – 970Hz @ 1Hz (BS5839-1:2002)

O-O-O-O-I-O

1

110

43

4.

970Hz 1s OFF/1s ON (Apollo Fire Systems Alert Tone, BS5839-1:2002)

O-O-O-O-I-I

1

110

25

5.

970Hz, 0.5s/ 630Hz, 0.5s (Apollo Fire Systems Evacuate Tone, BS5839-1:2002)

O-O-O-I-O-O

1

110

39

6.

554Hz, 0.1s/ 440Hz, 0.4s (France – AFNOR NF S 32 001 )

O-O-O-I-O-I

1

107

24

7.

500 – 1200Hz, 3.5s/ 0.5s OFF (Netherlands – NEN 2575:2000)

O-O-O-I-I-O

1

110

28

8.

420Hz 0.625s ON/0.625s OFF (Australia AS1670 Alert tone)

O - O - O - I - I - I

1

105

9

9.

500 – 1200Hz, 0.5s/ 0.5s OFF x 3/1.5s OFF (Australia AS1670 Evacuation tone)

O-O-I-O-O-O

1

110

13

10.

550Hz/440Hz @ 0.5Hz

O-O-I-O-O-I

19

107

26

11.

970Hz, 0.5s ON/0.5s OFF x 3/ 1.5s OFF (ISO 8201 Low tone)

O-O-I-O-I-O

1

110

19

12.

2850Hz, 0.5s ON/0.5s OFF x 3/1.5s OFF (ISO 8201 High tone)

O - O - I - O - I - I

1

112

16

13.

1200Hz – 500Hz @ 1Hz (DIN 33 404)

O-O-I-I-O-O

1

110

34

14.

400Hz

O - O - I - I - O - I

18

105

21

15.

550Hz, 0.7s/1000Hz, 0.33s

O - O - I - I - I - O

1

111

33

16.

1500Hz – 2700Hz @ 3Hz (Vandal Alarm)

O - O - I - I - I - I

1

116

46

17.

Simulated Bell

O-I-O-O-O-O

1

112

26

18.

840Hz

O-I-O-O-O-I

1

113

34

19.

660Hz

O-I-O-O-I-O

10

109

31

20.

660Hz 1.8s ON/1.8s OFF

O - I - O - O - I - I

19

108

16

21.

660Hz 0.15s ON/0.15s OFF

O-I-O-I-O-O

19

107

17

22.

510Hz, 0.25s/ 610Hz, 0.25s

O - I - O - I - O - I

1

107

28

23.

800/1000Hz 0.5s each (1Hz)

O - I - O - I - I - O

1

111

44

24.

250Hz – 1200Hz @ 12Hz

O - I - O - I - I - I

1

105

24

25.

500Hz – 1200Hz @ 0.33Hz.

O-I-I-O-O-O

1

110

31

26.

2400Hz – 2900Hz @ 9Hz

O - I - I - O - O - I

1

116

45

27.

2400Hz – 2900Hz @ 3Hz

O - I - I - O - I - O

1

116

45

28.

800Hz – 970Hz @ 100Hz

O - I - I - O - I - I

1

110

42

29.

800Hz – 970Hz @ 9Hz

O - I - I - I - O - O

1

110

43

30.

800Hz – 970Hz @ 3Hz

O - I - I - I - O - I

1

110

43

31.

800Hz, 0.25s ON/1s OFF

O - I - I - I - I - O

1

108

10

32.

500Hz – 1200Hz, 3.75s/0.25s OFF (AS2220)

O - I - I - I - I - I

1

110

29

33.

340Hz

I-O-O-O-O-O

1

106

18

34.

1000Hz

I-O-O-O-O-I

18

111

47

35.

1400Hz – 1600Hz, 1s/1600Hz – 1400Hz, 0.5s (NF 48-265)

I-O-O-O-I-O

1

110

44

36.

660Hz 6.5s ON/13s OFF

I - O - O - O - I - I

19

108

31

37.

1000Hz/2000Hz, 1s each

I-O-O-I-O-O

1

113

41

38.

720Hz, 0.7s ON/0.3s OFF

I - O - O - I - O - I

1

106

26

39.

970Hz, 0.25s ON/OFF

I - O - O - I - I - O

1

110

25

40.

2800Hz, 1s ON/OFF

I - O - O - I - I - I

1

113

22

41.

2800Hz 0.25s ON/OFF

I-O-I-O-O-O

1

113

21

42.

2400/2900 @ 2Hz

I - O - I - O - O - I

1

115

43

43.

Chime, 554Hz/440Hz Single shot ‘ding dong’

I - O - I - O - I - O

1

104

15

44.

Chime, 554Hz/440Hz Repeating ‘ding dong’

I - O - I - O - I - I

1

107

15

45.

Chime, 970Hz/800Hz Single shot ‘ding dong’

I- O - I - I - O - O

1

106

36

46.

Chime, 970Hz/800Hz Repeating ‘ding dong’

I - O - I - I - O - I

1

106

36

47.

Hooter, Repeating

I - O - I - I - I - O

1

107

13

48.

Gentle alarm - Tone 2, rises slowly to full volume over 30s

I - O - I - I - I - I

1

109

44

49.

Time-Out Alarm – As Tone 2, cuts off after 10 mins

I-I-O-O-O-O

1

109

44

50.

Time-Out Alarm – As Tone 2, cuts off after 2 mins

I - I - O - O - O - I

1

109

44

51.

750Hz 0.33s ON/0.51s OFF

I - I - O - O - I - O

1

106

12

52.

750Hz 0.51s ON/0.33s OFF

I - I - O - O - I - I

1

107

25

53.

550Hz, 0.33s/1000Hz, 0.7s

I - I - O - I - O - O

1

111

41

54.

600Hz – 900Hz/ 0.9s

I - I - O - I - O - I

1

109

37

55.

660Hz – 680Hz/ 0.9s

I - I - O - I - I - O

1

105

33

56.

670Hz – 725Hz/ 0.9s

I - I - O - I - I - I

1

107

33

57.

920Hz – 750Hz/ 0.9s

I - I - I - O - O - O

1

110

41

58.

700Hz - 900Hz, 0.3s/0.6s OFF

I - I - I - O - O - I

1

109

15

59.

900Hz - 760Hz, 0.6s/0.3s OFF

I - I - I - O - I - O

1

110

28

60.

750Hz

I - I - I - O - I - I

18

107

39

61.

Power Only – Use with Stage 3 control for manual/intermittent chime triggering

I - I - I - I - O - O

43

62.

Power Only – Use with Stage 3 control for manual/intermittent chime triggering

I - I - I - I - O - I

43

63.

Power Only – Use with Stage 3 control for manual/intermittent horn triggering

I - I - I - I - I - O

47

64.

Reserved for future use

I - I - I - I - I - I

EN

DE

FR

NL

ES

Содержание Nexus 110 DC

Страница 1: ...O 1 111 44 24 250Hz 1200Hz 12Hz O I O I I I 1 105 24 25 500Hz 1200Hz 0 33Hz O I I O O O 1 110 31 26 2400Hz 2900Hz 9Hz O I I O O I 1 116 45 27 2400Hz 2900Hz 3Hz O I I O I O 1 116 45 28 800Hz 970Hz 100Hz O I I O I I 1 110 42 29 800Hz 970Hz 9Hz O I I I O O 1 110 43 30 800Hz 970Hz 3Hz O I I I O I 1 110 43 31 800Hz 0 25s ON 1s OFF O I I I I O 1 108 10 32 500Hz 1200Hz 3 75s 0 25s OFF AS2220 O I I I I I ...

Страница 2: ...te 3rd Stage Alarm Control Connect to 0V to activate Beacon Positive Supply 10 to 60V DC Beacon Negative Supply 0V Line Terminal Marking S2 S3 XENON BEACON LED BEACON Switch Off On Off On 1 60 flashes per min 30 flashes per min Single Flash Double Flash 2 Single Flash Double Flash Flashing Static Technical Specification Supply Voltage Range 10 60V DC Current Sounder 10 50mA Typ 45mA 24V Tone 1 Cur...

Страница 3: ...äden durch Elektro und Elektronik Altgeräte so gering wie möglich zu halten Um diese Richtlinie einzuhalten dürfen Elektrogeräte die mit diesem Symbol gekennzeichnet sind nicht in den öffentlichen europäischen Entsorgungssystemen entsorgt werden Europäische Benutzer von Elektrogeräten müssen ab sofort Altgeräte zur Entsorgung zurückgeben Nähere Informationen hierzu finden Sie auf der folgenden Web...

Страница 4: ...g a Toonselectie De eerste en tweede fase alarmtonen worden onafhankelijk ingesteld door gebruik van 6 weg dimschakelaars S1 en S2 De vereiste instellingen worden in de tabel op de ommezijde weergegeven De derde fase alarmtoon is preset als aanvulling de geselecteerde eerste fase toon zoals weergegeven op de tabel b Volumeregeling De geluidsuitvoer van het apparaat kan tot 20dBA verminderd worden ...

Отзывы: