Nexus 105 DC Sounder & Sounder-Beacon
Installation Instructions
EN
DE
FR
NL
ES
PT
IT
PL
SE
DK
Texecom Ltd (Incorporating Klaxon Signals)
St Crispin Way, Haslingden, BB4 4PW, UK
Tel: +44 (0)1706 233879
(June 2013) 18-186456-9
Copyright © Texecom Ltd
email: [email protected] www.klaxonsignals.com
Tone
Tone Type
Tone Description /Application
Dip Switch
(S1/S2)
3rd Stage
Tone
Peak Sound
Level
(dBA @1m, 24-V DC)
Sounder
Current
(mA Avg, 24V DC)
1.
970Hz (BS5839-1:2002)
O-O-O-O-O-O
18
105
31
2
800Hz/970Hz @ 2Hz (BS5839-1:2002)
O-O-O-O-O-I
1
105
28
3
800Hz – 970Hz @ 1Hz (BS5839-1:2002)
O-O-O-O-I-O
1
104
25
4
970Hz 1s OFF/1s ON (Apollo Fire Systems Alert Tone, BS5839-1:2002)
O-O-O-O-I-I
1
105
17
5
970Hz, 0.5s/ 630Hz, 0.5s (Apollo Fire Systems Evacuate Tone, BS5839-1:2002)
O-O-O-I-O-O
1
105
27
6
554Hz, 0.1s/ 440Hz, 0.4s (France – AFNOR NF S 32 001 )
O-O-O-I-O-I
1
103
20
7
500 – 1200Hz, 3.5s/ 0.5s OFF (Netherlands – NEN 2575:2000 Dutch Slow Whoop)
O-O-O-I-I-O
1
108
19
8
420Hz 0.625s ON/0.625s OFF (Australia AS1670 Alert tone)
O - O - O - I - I - I
1
102
10
9
500 – 1200Hz, 0.5s/ 0.5s OFF x 3/1.5s OFF (Australia AS1670 Evacuation tone)
O-O-I-O-O-O
1
106
13
10
550Hz/440Hz @ 0.5Hz
O-O-I-O-O-I
19
104
21
11
970Hz, 0.5s ON/0.5s OFF x 3/ 1.5s OFF (ISO 8201 Low tone)
O-O-I-O-I-O
1
105
13
12
2850Hz, 0.5s ON/0.5s OFF x 3/1.5s OFF (ISO 8201 High tone)
O - O - I - O - I - I
1
107
16
13
1200Hz – 500Hz @ 1Hz (DIN 33 404)
O-O-I-I-O-O
1
109
22
14
400Hz
O - O - I - I - O - I
18
101
16
15
550Hz, 0.7s/1000Hz, 0.33s
O - O - I - I - I - O
1
105
25
16
1500Hz – 2700Hz @ 3Hz (Vandal Alarm)
O - O - I - I - I - I
1
113
32
17
Simulated Bell
O-I-O-O-O-O
1
107
18
18
2130Hz
O-I-O-O-O-I
1
110
26
19
660Hz
O-I-O-O-I-O
10
102
25
20
660Hz 1.8s ON/1.8s OFF
O - I - O - O - I - I
19
102
14
21
660Hz 0.15s ON/0.15s OFF
O-I-O-I-O-O
19
102
14
22
510Hz, 0.25s/ 610Hz, 0.25s
O - I - O - I - O - I
1
103
24
23
800/1000Hz 0.5s each (1Hz)
O - I - O - I - I - O
1
106
25
24
250Hz – 1200Hz @ 12Hz
O - I - O - I - I - I
1
101
23
25
500Hz – 1200Hz @ 0.33Hz.
O-I-I-O-O-O
1
108
21
26
2400Hz – 2900Hz @ 9Hz
O - I - I - O - O - I
1
113
39
27
2400Hz – 2900Hz @ 3Hz
O - I - I - O - I - O
1
111
39
28
800Hz – 970Hz @ 100Hz
O - I - I - O - I - I
1
104
23
29
800Hz – 970Hz @ 9Hz
O - I - I - I - O - O
1
104
27
30
800Hz – 970Hz @ 3Hz
O - I - I - I - O - I
1
105
28
31
800Hz, 0.25s ON/1s OFF
O - I - I - I - I - O
1
103
8
32
500Hz – 1200Hz, 3.75s/0.25s OFF (AS2220)
O - I - I - I - I - I
1
108
20
33
340Hz
I-O-O-O-O-O
1
101
17
34
1000Hz
I-O-O-O-O-I
18
106
25
35
1400Hz – 1600Hz, 1s/1600Hz – 1400Hz, 0.5s (NF 48-265)
I-O-O-O-I-O
1
104
34
36
660Hz 6.5s ON/13s OFF
I - O - O - O - I - I
19
102
9
37
1000Hz/2000Hz, 1s each
I-O-O-I-O-O
1
108
25
38
720Hz, 0.7s ON/0.3s OFF
I - O - O - I - O - I
1
104
16
39
970Hz, 0.25s ON/OFF
I - O - O - I - I - O
1
105
17
40
2800Hz, 1s ON/OFF
I - O - O - I - I - I
1
106
20
41
2800Hz 0.25s ON/OFF
I-O-I-O-O-O
1
106
19
42
2400/2900 @ 2Hz
I - O - I - O - O - I
1
113
38
43
Chime, 554Hz/440Hz Single shot ‘ding dong’
I - O - I - O - I - O
1
100
15
44
Chime, 554Hz/440Hz Repeating ‘ding dong’
I - O - I - O - I - I
1
102
15
45
Chime, 970Hz/800Hz Single shot ‘ding dong’
I- O - I - I - O - O
1
101
36
46
Chime, 970Hz/800Hz Repeating ‘ding dong’
I - O - I - I - O - I
1
100
36
47
Hooter, Repeating
I - O - I - I - I - O
1
102
13
48
Gentle alarm - Tone 2, rises slowly to full volume over 30s
I - O - I - I - I - I
1
105
28
49
Time-Out Alarm – As Tone 2, cuts off after 10 mins
I-I-O-O-O-O
1
105
28
50
Time-Out Alarm – As Tone 2, cuts off after 2 mins
I - I - O - O - O - I
1
105
28
51
750Hz 0.33s ON/0.51s OFF
I - I - O - O - I - O
1
103
8
52
750Hz 0.51s ON/0.33s OFF
I - I - O - O - I - I
1
103
15
53
550Hz, 0.33s/1000Hz, 0.7s
I - I - O - I - O - O
1
106
25
54
600Hz – 900Hz/ 0.9s
I - I - O - I - O - I
1
104
31
55
660Hz – 680Hz/ 0.9s
I - I - O - I - I - O
1
101
28
56
670Hz – 725Hz/ 0.9s
I - I - O - I - I - I
1
104
25
57
920Hz – 750Hz/ 0.9s
I - I - I - O - O - O
1
104
30
58
700Hz - 900Hz, 0.3s/0.6s OFF
I - I - I - O - O - I
1
104
11
59
900Hz - 760Hz, 0.6s/0.3s OFF
I - I - I - O - I - O
1
105
19
60
750Hz
I - I - I - O - I - I
18
103
22
61
Power Only – Use with Stage 3 control for manual/intermittent chime triggering
I - I - I - I - O - O
43
62
Power Only – Use with Stage 3 control for manual/intermittent chime triggering
I - I - I - I - O - I
43
63
Power Only – Use with Stage 3 control for manual/intermittent horn triggering
I - I - I - I - I - O
47
EN54-3:2001+A1
Fire Alarm Device – Sounder
Type B: For indoor or outdoor use
PNS-0001/PNC-0001/02/20/41/43/24/28/45/46/47
Technical Data: Document 18-186528