22 / 82
83000602.Ke
3.6.
Tank heating with thermostatic pump start
The tank heating is used to maintain a minimum temperature in the tank. The pump circulates the
cold water while the tank heating controls the temperature in the system. We recommend a
hydraulic installation as shown in
Figure 4
. Any bypass valves must therefore always be installed
frost-free. In order for the heating to be active the chiller must not be disconnected from the power
supply. Even if the external release is deactivated (
Chapter
8.3 External release)
, the pump remains
active.
Figure 4: C6856 thermostatic pump start with overflow valve (installation recommendation)
3.7.
Overflow valve for standby operation
The overflow valve option should be installed if there is a possibility of the application severely
reducing or completely preventing flow of the cold water while the machine is running. The internal
overflow valve ensures the minimum flow rate through the chiller and therefore prevents the pump
from switching off.
Figure 5
shows the position of the internal overflow valve.
Figure 5: C6863 overflow valve for standby operation
vBoxX
Frost-free area
Application
Application
vBoxX
Содержание vBoxX 10
Страница 1: ...Vario Line vBoxX 6 vBoxX 8 vBoxX 10 vBoxX 12 vBoxX 15 vBoxX 18 vBoxX 24 vBoxX 28 Instruction Manual ...
Страница 16: ...16 82 83000602 Ke ...
Страница 65: ...65 82 83000602 Ke I Overview of the menu levels Main structure ...
Страница 66: ...66 82 83000602 Ke Status ...
Страница 67: ...67 82 83000602 Ke Parameters ...
Страница 68: ...68 82 83000602 Ke ...
Страница 69: ...69 82 83000602 Ke hidden ...
Страница 70: ...70 82 83000602 Ke ...
Страница 71: ...71 82 83000602 Ke ...
Страница 82: ...82 82 83000602 Ke V EC Declaration of Conformity ...