Chiller type:
Serial no.
Menu
Menu
Menu
Menu
Parameter
Parameter
Parameter
Parameter
Def.
Def.
Def.
Def.
Min.
Min.
Min.
Min.
Max.
Max.
Max.
Max.
Unit
Unit
Unit
Unit
Project
Project
Project
Project
Time delay
15
3
45 min
Outlet max stop
32,0
-20,0
60,0 °C
Outlet max warning
30,0
-20,0
60,0 °C
Outlet min stop
-20,0
-20,0
60,0 °C
0,0
Limit container pressure
Limit container pressure
Limit container pressure
Limit container pressure
Max level
125
20
150 mbar
Min level warning
105
20
150 mbar
Min level STOP
80
20
150 mbar
Hysteresis
2
1
10 mbar
Limit pressure evaporator
Limit pressure evaporator
Limit pressure evaporator
Limit pressure evaporator
Min warning
0,5
0,0
30,0 bar
0,2
Min stop
0,1
0,0
30,0 bar
Outlet max stop
2,0
0,0
30,0 bar
Limit pressure pump 1
Limit pressure pump 1
Limit pressure pump 1
Limit pressure pump 1
Outlet max stop
10,0
0,0
40,0 bar
Outlet min warning
2,5
0,0
40,0 bar
0,8
Outlet min stop
2,0
0,0
40,0 bar
0,5
Limit pressure pump 2
Limit pressure pump 2
Limit pressure pump 2
Limit pressure pump 2
Outlet max stop
10,0
0,0
40,0 bar
Outlet min warning
2,5
0,0
40,0 bar
Outlet min stop
2,0
0,0
40,0 bar
Conductivity
Conductivity
Conductivity
Conductivity
conduc. max. alert
50
0
2000 µS/cm
conduc. max. warning
30
0
2000 µS/cm
Control
Control
Control
Control
Thermostatic pump start
Thermostatic pump start
Thermostatic pump start
Thermostatic pump start
Intervall
15
5
10000 min
Runtime
5
0
60 min
Time delay
60
5
180 sek
Minimum
Minimum
Minimum
Minimum
Setpoint
8,0
0,0
30,0 °C
Hysteresis
1,0
1,0
10,0 K
Maximum
Maximum
Maximum
Maximum
Setpoint
28,0
0,0
40,0 °C
Hysteresis
1,0
1,0
10,0 K
Control coolant outlet temperature
Control coolant outlet temperature
Control coolant outlet temperature
Control coolant outlet temperature
Setpoint (Water)
20,0
8,0
30,0 °C
Setpoint (Glycol 20)
20,0
-4,0
30,0 °C
5,0
Setpoint (Glycol 30)
20,0
-10,0
30,0 °C
Setpoint (Glycol 40)
20,0
-10,0
30,0 °C
Hysteresis
2,0
0,5
20,0 K
Relaise extern
Relaise extern
Relaise extern
Relaise extern
Maximum
27
-10
40 °C
Minimum
20
-10
40 °C
Control coolant valve
Control coolant valve
Control coolant valve
Control coolant valve
Setpoint
32,0
0,0
40,0 °C
15,0
Control tank heater
Control tank heater
Control tank heater
Control tank heater
Setpoint
8,0
0,0
30,0 °C
Hysteresis
2,0
0,5
20,0 K
Control fan / cooling water
Control fan / cooling water
Control fan / cooling water
Control fan / cooling water
Construction
Eco
setpoint economic
31,5
10,0
35,0 bar
25,0
Setpoint comfort
35,0
10,0
35,0 bar
31,0
Control ESS / free cooling
Control ESS / free cooling
Control ESS / free cooling
Control ESS / free cooling
Free cooler
Auto
Diff.temp.ambiente-return
3,0
1,0
10,0 K
Hysteresis
0,5
0,5
5,0 K
Min delimiter
Min delimiter
Min delimiter
Min delimiter
Setpoint
10,0
-10,0
40,0 °C
Control automatic water feed
Control automatic water feed
Control automatic water feed
Control automatic water feed
Valve open
110
20
150 mbar
Valve closed
120
20
150 mbar
Control conductivity
Control conductivity
Control conductivity
Control conductivity
Valve open
20
0
2000 µS/cm
Valve closed
16
0
2000 µS/cm
Compact-Line
Compact-Line
Compact-Line
Compact-Line
Parameterlist
cBoxX 100
91002557