11
The fourth (grounding) conductor must be identified by a green or
green/yellow cover and the neutral conductor by a white cover.
Cord should be Type SRD or SRDT with a UL listed strain relief
and be at least 4 ft (1.22 m) long.
4-wire receptacle (14-50R)
The minimum conductor sized for the copper 4-wire power cord
are:
40 A circuit
2 No.-8 conductors
1 No.-10 white neutral
1 No.-10 green grounding
Electrical Requirements - Canada
Only
WARNING
Electrical Shock Hazard
Electrically ground appliance.
Failure to do so could result in death, fire, or electrical
shock.
If codes permit and a separate ground wire is used, it is
recommended that a qualified electrical installer determine that
the ground path is adequate and wire gauge are in accordance
with local codes.
Be sure that the electrical connection and wire size are adequate
and in conformance with CSA Standard C22.1, Canadian
Electrical Code, Part 1 - latest edition, and all local codes and
ordinances.
A copy of the above code standards can be obtained from:
Canadian Standards Association
178 Rexdale Blvd.
Toronto, ON M9W 1R3 CANADA
�
Check with a qualified electrical installer if you are not sure the
range is properly grounded.
Range Rating*
Specified Rating
of Power Supply
Cord kit and
Circuit Protection
120/240 V
120/208 V
Ampere
8.8-16.5 kW
7.8-12.5 kW
40 or 50**
16.6-22.5 kW
12.6-18.5 kW
50
*The NEC calculated load is less than the total connected load
listed on the model/serial/rating plate.
**If connecting to a 50 A circuit, use a 50 A rated cord with kit. For
50 A rated cord kits, use kits that specify use with a nominal 1
3
/
8
"
(3.5 cm) diameter connection opening.
�
A circuit breaker is recommended.
�
This range is equipped with a CSA International Certified
Power Cord intended to be plugged into a standard 14-50R
wall receptacle. Be sure the wall receptacle is within reach of
range’s final location.
�
Do not use an extension cord.
�
The tech sheet is available online and the wiring diagram is
located on the back of the range in a plastic bag.
Gas Supply Requirements
WARNING
Explosion Hazard
Use a new CSA International approved gas supply line.
Install a shut-off valve.
Securely tighten all gas connections.
If connected to propane, have a qualified person make
sure gas pressure does not exceed 14
ʺ
(36 cm) water
column.
Examples of a qualified person include: licensed heating
personnel, authorized gas company personnel, and
authorized service personnel.
Failure to do so can result in death, explosion, or fire.
Observe all governing codes and ordinances.
IMPORTANT:
This installation must conform with all local codes
and ordinances. In the absence of local codes, installation must
conform with the National Fuel Gas Code ANSI Z223.1/NFPA 54
or, in Canada, the National Gas and Propane Installation Code,
CSA B149.1 - latest edition.
IMPORTANT:
Leak testing of the range must be conducted
according to the manufacturer’s instructions. See the "Make Gas
Connection" section for leak testing instructions.
Type of Gas
Natural Gas:
�
This range is factory set for use with Natural gas. If converting
to propane gas, see “Gas Conversions” section. The model/
serial/rating plate located behind the control panel has
information on the types of gas that can be used. If the types of
gas listed do not include the type of gas available, check with
the local gas supplier.
Propane Gas Conversion:
Conversion must be done by a qualified service technician.
No attempt shall be made to convert the appliance from the gas
specified on the model/serial/rating plate for use with a different
gas without consulting the serving gas supplier. See “Gas
Conversions” section.