Содержание 8101P120-60

Страница 1: ...e information in regard to installation of range see figures 1 and 2 on page 2 For SAFETY CONSIDERATIONS do not install a range in any combustible cabinetry which is not in accord with the installation clearances shown in figure 1 on page 2 CAUTION SOME CABINETS AND BUILDING MATERIALS ARE NOT DE SIGNED TO WITHSTAND THE HEAT PRODUCED BY THE NORMAL SAFE OPERATION OF A LISTED APPLIANCE DISCOLORATION ...

Страница 2: ...HE USE OF THE LOCAL ELEC TRICAL INSPECTOR A 30 inches minimum clearance between the top of the cooking surface and the bottom of an unprotected wood or metal cabinet or A 24 inches minimum when bottom of wood or metal cabinet is protected by not less than 1 4 inch thick flame retar jant millboard covered with not less than No 28 MSG sheet steel 0 015 inch thick stainless steel 0 024 inch thick alu...

Страница 3: ...formerly the Federal Standard for Mobile Home Construction and Safety Title 24 HUD Part 280 or when such standard is not applicable the Standard for Manufactured Home Installations 1982 Manufactured Home Sites Communities and Set Ups ANSI A225 1 1984 or with local codes Place range where it will be well lighted Do not set range over holes in the floor or other locations where it may be subject to ...

Страница 4: ...n you will be using CAUTION Damage to the range may occur if range is moved or lifted by grasping the main top or backguard c D All free standing ranges with a glass top have a non lift up top Coil tops are lift up For SAFETY CONSIDERATIONS as well as optimum performance adjust the range so that it is level This may be checked by placing a spirit level or a large pan of water on the cooktop or the...

Страница 5: ...TE 1 4 MlN SlIDEINTOSECURE 1 ART A219 761B ART 21 20 A USE A MINIMUM OF TWO 2 10d x 3 LONG NAILS O LONG SCREWS TO ANCHOR SPACER TO WALL PLATE FIGURE 8 FIGURE 7 5 3 8 SPACER BLOCK WILL REQUIRED BEHIHD THE AHTI BRACKET NAI L DR SCREW WJOOEN sPACER BLOCK CNOT PROVIDED L TO WALL STRUCTURE rL 2 NAILS OR SCREWS 8 LOOR ATTACH TIE oO BRACKET WITH LDNG SCREWS OLES FORWALL EVEL I NG FOOT WOODEN SPACER RANGE...

Страница 6: ...le continuous armored conduit must be used from main entrance panel to the terminal box on the rear of the range Others will permit the termination of the range circuit at a polarized three orfou r On models not provided with a service cord and models having a conduit connection to the power supply is necessary REMEMBER mobile homes and some LOCAL CODES DO NOT PERMIT GROUNDING THROUGH NEUTRAL Henc...

Страница 7: ...must be connected to the white service wire 4 The uninsulated bare wire from the conduit must be connected either to a green or bare service wire 3 WIRE SERVICE CORD INSTAllATION FIGURE 10A 1 Insure that the copper ground strap IS CONNECTED between the middle post of the main terminal connection block and the range chassis 2 The middle wire of the service cord MUST connect to the neutral middle po...

Страница 8: ...NECTOR RED WHITE APPROVED CONNECTORS ACK A APPROVED BOX L1 RED V NEUTRAL GROUND 2 BLACK ART 9219 749 A CIRCUIT POWERSUPPLY WIRING METHOD IF CODE DOES NOT PERMIT GROUNDING THROUGH NEUTRAL CONDUCTOR ALSO REQUIRED IN MOBILE HOMES FIGURE 10D MOBILE HOME 4 WIRE CONDUIT FIGURE 10C MOBILE HOME 4 WIRE PLUG 8 ...