If checked, the device will send a message to the authorized number when DIN returns to normal.
[DIN Current Status]
Click read to display DIN current status.
8.6.3. AIN - Analog Input Settings
[Sampling Period]
Range 2-65535, unit 100ms (0.1 second), by default 10, indicating that the AIN value is collected
every 1000 milliseconds (1 second). In low power mode, it is recommended to extend the sampling period
according to actual needs, which can reduce power consumption.
[Alarm/Recovery Verify Time]
Range 0~65535 seconds, by default 2, indicates that the value exceeds the threshold for 2 seconds
before it is confirmed as alarm or recovery, it can prevent misreporting. Set to 0 means that, if the value of
AIN exceeds the threshold, the alarm will be made immediately.
[Minimum],[Maximum]
The sensor’s maximum & minimum measure range. E.g.:0~100 Celsius degree. Usually it can be
found out at the sensor’s specification.
Note: Measuring range minimum and maximum, are integer, it is 10 times the real value.
Such as, the specification of the sensor shows that the range of the sensor is -40 to 200, and then you
need to set the range minimum to -400, set the range maximum to 2000.
[Current Value]
Click read to display AIN current value.
[Threshold High], [Threshold Low]
When the current value is between these two values, it is normal; otherwise there will be alarm;