PLC Data acquisition protocol conversion gateway
-D225
Operation instructions: (1) Add new collected data points, which can be added single or multiple,
(2) Name the collected data points, (3) The slave address is the ID of the D225 device, the defaults
to "1" , (4) Select the register type according to the value type of the data point to be collected.
For details,
Appendix Mapping address of PLC register
. (5) The register address is to fill in the
mapping address of D225. For details,
see
Appendix Mapping address of PLC register
(6) According
to Fill in the data format of the data to be collected. (7) The storage order of 16-bit data bytes
processed by the D225 device is AB, and the byte order of 32-bit data is ABCD. Choose the byte
order according to how many bits of data are collected. (8) You can freely choose whether To collect
this data point, (9) fill in the collection period according to your needs, (10) if you don
’
t need this
collected data point, you can click Delete to delete this collected data point, (11) The decimal point
is based on the data type and how many decimal places you need to fill in. The data unit is filled in
according to your own needs. The data bit is the data that is read and written by bit. The minimum,
maximum, minimum original value and maximum original value are used for sensor data
amplification or Zoom out, configure the configuration of the data points you want to collect, and
click "confirm".
5.4.2.2
Monitor D225 equipment to collect PLC data points
Click the "Device List" in the "Monitoring Center" or click the "Total Device Icon" in the
"Homepage" to check whether the D225 device is connected to the Golden Pigeon 3.0 platform,
as shown below