KING-GAGE

KING ENGINEERING CORPORATION

Effective: March. 1998 

 (replaces January, 1998)

EX-1803

LevelPRO

  

Multiple Tank Level Processor

Installation and Operations

Manual

Models:

• 5252-21-xx
• 5252-31-xx

7

8

9

4

5

6

1

2

3

0

.

Menu

Select

Edit

Enter

Reset

GALS

1.019

9982

TANK 1

Содержание LevelPRO 5252-21 Series

Страница 1: ...PORATION Effective March 1998 replaces January 1998 EX 1803 LevelPRO Multiple Tank Level Processor Installation and Operations Manual Models 5252 21 xx 5252 31 xx 7 8 9 4 5 6 1 2 3 0 Menu Select Edit Enter Reset GALS 1 019 9982 TANK1 ...

Страница 2: ...rmity of these goods shall be repair and or replacement of the nonconforming goods or parts LevelPRO Multiple Tank Level Processor EX 1803 Seller will not be liable for consequential damages resulting from breach of this agreement The term consequential damages shall include but shall not be limited to damage to all machines equipment and goods other than the goods sold hereby interruption of prod...

Страница 3: ...ions Model 5252 21 xx page 5 Specifications Model 5252 31 xx page 6 Installation Requirements page 8 Installing Updated Datapack SRAM page 9 Using the Operator Interface Keypad page 10 Troubleshooting Checklist page 12 Network Communications RS 485 page 13 Addendum Communications Specifications and Protocol page 14 ...

Страница 4: ... tional 4 20 mA output from the liquid level transmitter The sensor used to detect hydrostatic pressure created by liquid depth can be either electronic or pneumatic With the latter an electronic pressure transmitter is used to convert the sensor s pneumatic signal into a 4 20 mA output This can be done with a KING GAGE D P Module or D P Transmitter Pneumatic Sensor D P Module 4 20 mA Signal 4 20 ...

Страница 5: ... 24 Vdc excitation available at Signal terminal 0 5 Amp max Readout Alphanumeric 0 3173 in 8 mm 16 character x 2 line LCD numeric 8 digit 0 9999999 maximum Resolution 0 024 FS 0 004 mA Accuracy 0 048 FS 0 024 FS typical Keypad Membrane numeric keypad five 5 function keys positive tactile response Temperature Range 30 F to 120 F 1 C to 49 C operating environment Communications RS 485 two wire multi...

Страница 6: ...e channel inputs Memory SRAM 8k x 8 100 ns Input Impedance 120 Ohm nominal resistance 2 4 Vdc drop 20 mAdc Power Output 24 Vdc excitation available at Signal terminal 0 5 Amp max Readout Alphanumeric 0 3173 in 8 mm 16 character x 2 line LCD numeric 8 digit 0 9999999 maximum Resolution 0 024 FS 0 004 mA Accuracy 0 048 FS 0 024 FS typical Keypad Membrane numeric keypad five 5 function keys positive ...

Страница 7: ...iple Tank Level Processor EX 1803 Internal User Details 1 Datapack SRAM 2 1 2 Amp Fuse 120 250 Volt Fast Blo Order No 7469 21 0 5 pack 3 Terminal Power Communication 4 Terminal Signal Input 5 Status LEDs Signal Input Terminal 1 2 3 1 2 3 TMP 4 20 mA Signal Power Communications Terminal 1 2 3 4 5 6 7 8 9 1 N C 2 N C 3 A 4 B 5 Shield 6 N C 7 HOT 8 NEU 9 GND RS485 422 115 Vac Status LED Indicators Po...

Страница 8: ...tions Transmitter Signal Loop Typical transmitter provides a 4 20 mA output over a dc powered two wire current loop circuit This normally requires at least a 24 Vdc power source to provide excitation voltage to the transmitter The power require ments should be calculated to accommodate the total resistive load residing on the circuit e g cabling imped ance input impedance of receivers etc Refer to...

Страница 9: ...tions link and ASCII command protocol see Addendum to change specific gravity value from a remote terminal or PLC Installing Updated Datapack SRAM Non addressable application parameters i e tank name network polling address tank capacity profile require updated datapack programmed at the factory Use caution when accessing the datapack internal circuitry and electrical connections should not be exp...

Страница 10: ...00 Scanning Tank Channels To view each tank sequentially by its channel assignment 1 8 merely press SELECT Repeat to view the next channel and so on through all the active channels 19990 GALS TANK ST1 1 000 SELECT 855 GALS TANK ST2 1 032 SELECT 11120 GALS TANK ST3 1 012 SELECT 100 GALS TANK ST4 1 028 SELECT 35870 GALS TANK ST5 1 008 Direct Access Tank Selection For direct or random access enter th...

Страница 11: ...h the readout units selections When the desired readout unit is displayed press the ENTER key to accept the selection 41420 GALS TANK ST1 1 000 MENU SP GRAVITY TANK ST1 1 000 MENU UNITS GALS TANK ST1 SELECT UNITS TANK ST1 SELECT UNITS LBS TANK ST1 ENTER 345029 LBS TANK ST1 1 000 41420 GALS TANK ST1 1 000 MENU SP GRAVITY TANK ST1 1 000 EDIT SP GRAVITY 1 TANK ST1 1 000 0 1 000 3 1 030 3 1 033 ENTER ...

Страница 12: ...e may sometimes exceed venting capacity creating internal pressure in the tank Specific gravity of liquid in tank may be greater than that programmed into tank processor Datapack PROM Check that the specific gravity value lower right hand corner being displayed for that tank is correct Use keypad to enter corrected value if necessary Communications Troubleshooting Using LED Status Indicators GREEN...

Страница 13: ...tions Loss of communications to all devices in the network Check connections at RS 485 terminals at each device If one processor has been disconnected from the network make certain that cabling has continuity Check that power is being supplied to the LevelPRO processors There will be no communications if individual devices suffer loss of power No Communications Response Individual Failure of queri...

Страница 14: ...onse NNN_S SSS_XLLLLLLLL_UUUU_CCCC CR LF NNN 3 character ASCII polling address 001 256 _ Space character 20 Hex S SSS 5 character specific gravity includes decimal 2E Hex character _ Space character 20 Hex X Status code B blank F full R reserve empty C calibration mode LLLLLLLL 8 character level value leading zeros required if applicable _ Space character 20 Hex UUUU 4 character units abbreviation...