electrical  mfg. company

9131 - 10th Avenue South  Seattle Washington 98108

INSTALLATION & MAINTENANCE MANUAL

WARNING

Model: KBP2406 is 240 volt. It is important that you 
verify the power supply voltage is the same as the 
nameplate voltage of the heater.  Improper installation 
or failure to follow the procedures as outlined in this 
manual can result in damage to the heater.  Note that 
the KBP2406 will operate at 208 volt but will produce 
25% less wattage and draw 13% less Amps.  Discon-
nect all power from the heater at the main service 
panel before attempting to install or service this unit.  
All electrical wiring must conform to local electrical 
codes. Heater circuit must be properly protected.

Unpack & Inspect Your New Heater

Remove heater from box and inspect it for any damage. Verify 
you have received the mounting bracket and accessories.

Tools Needed

You will need the following tools to install your unit heater:
  -Screwdriver - (Phillips & Slotted)
  -Wire Cutters
  -Pliers
  -Adjustable Wrench
  -Electric Drill

Hardware Needed

You will  need the following hardware:
  -Adequate gauge & length of wire for your application
  -Proper size fuses or breakers to handle amperage
  -Proper wire connectors for your application
  -Appropriate size fasteners to mount heater.

In  certain applications conduit may be required by code.  
Check local electrical codes. If you want to be able to turn the 
heater be sure to use flexible conduit.

Mounting Height

When the air flow of the heater is directed vertically or 
horizontally the minimum mounting height is 6 feet in USA 
and 8 feet in Canada. Mounting heights depend upon building 
utilization and heater kW capacity.

Distance From Walls

Maintain 6" minimum clearance to side walls and 2" to ceiling 
in back of the heater (air intake side). Maintain 18" clearance in 
front of the heater (discharge side).

Mounting Heater 

Locate a stud in ceiling or wall and securely fasten bracket with a 
minimum of two #12 fasteners 1-1/4" long.  Attach heater to bracket 
with 3/8" x 1" wingnut & lock washer supplied. Install the lock washer 
between the bracket and heater. Do not put lock washer on the plastic 
wingnut. After desired air discharge position has been determined 
tighten wingnut so heater will not pivot.

Location of Heater

The heater should be installed out-of-reach of persons.  The direction 
of airflow should not be restricted by machinery, beams, etc. and 
the airflow should wipe exposed walls, rather than blowing directly 
at them. When more than one heater is used in an area the heaters 
should be arranged so that the air discharge of each heater supports 
the airflow of the others to provide best circulation of warm air. 

(see 

airflow chart)

Model: 

 KBP2406 

 

240V-1phase Unit Heater

2007KBP2406.indd : 3/08