3.2.3.1 Operation Modes and Inputs of the High-speed Counters
Input signals of high-speed counter include: clock (input impulse), direction, start and reset.
In different operation modes input signals is different. Please see below:
HSC
0
Mod
e
Description
I0.1
I0.0
I0.5
0
Single-phase up/down counter
with internal direction control:
SM37.3
Clock
1
Reset
2
Reset
Start
3
Single-phase up/down counter
with external direction control
Clock
Direction
4
Reset
Direction
6
Two-phase counter with up/down
clock inputs
Clock
Down
Clock Up
9
A/B phase quadrature counter
Clock A
Clock B
HSC1
Mode
Description
I0.4
I0.6
I0.3
I0.2
0
Single-phase up/down counter
with internal direction control:
SM47.3
Clock
1
Reset
2
Reset
Start
3
Single-phase up/down counter
with external direction control
Clock
Direction
4
Reset
Direction
6
Two-phase counter
with up/down clock inputs
Clock
Down
Clock Up
7
Reset
9
A/B phase quadrature counter
Clock A
Clock B
10
Reset
HSC 2
Mode
Description
I0.4
I0.5
0
Single-phase up/down counter
with internal direction control:SM57.3
Clock
9
A/B phase quadrature counter
Clock A
Clock B
Содержание HP043-20DT
Страница 8: ...Kinco HP User Manual 8 1 4 4 Dimension Dimension 132 102 40 1mm Cutout size 119 93mm...
Страница 22: ...Kinco HP User Manual 22...
Страница 23: ...Kinco HP User Manual 23...
Страница 25: ...Kinco HP User Manual 25...
Страница 26: ...Kinco HP User Manual 26 2 It will show settings when mouse at the right side of Window then click settings...
Страница 27: ...Kinco HP User Manual 27 3 Click update and recovery in the PC settings...
Страница 28: ...Kinco HP User Manual 28 4 Click restart now at advanced startup 5 Click advanced options...
Страница 29: ...Kinco HP User Manual 29 6 click startup settings 7 Click restart...
Страница 31: ...Kinco HP User Manual 31 10 Figure as below after successful...