Kinco FD5
系列伺服驱动器使用手册
第五章
KincoServo
上位机使用指南
65
Figure
5-9
Digital input
Function
:
Click
to select Din function setting click
to
delete the DIN function
Real
:
Shows the real digital input hardware status.
1
means “active”, logic status of the digital input is 1.
0
means “inactive”, logic status of the digital input is
0.
Simulate: Simulates the digital input active hardware
signal.
1
means the digital input is simulated as “active”,
logic status 1.
0
means no impact on the digital input logic status.
Polarity: Inverts the logic status of the digital input.
1
means Internal is set to 1 by “active” signal.
0
means Internal is set to 1 by “inactive”
Internal: This is the result of Simulate, Real and Polarity via
the logic formula: Internal=(Real OR Simulate) XOR (NOT
Polarity)
1
means “active”, logic status of the selected function
is 1.
0 means
“inactive”, logic status of the selected
function i
s 0.
Table
5-2
Digital input functions
DIN function
Description
Enable
Controller enabling
1: Enable controller = Din control word selection(2020.0F)
0: Disable controller = 0x06
Reset errors
Set the Controlword to reset errors, active edge
(
bit7
)
= 1
Operationg
mode
Operation_mode selection
1:Operation_mode = EL.Din_Mode1 (2020.0E)
,
Defult value=-4
0:Operation_mode = EL.Din_Mode 0 (2020.0D)
,
Defult value =-3