Kinco FD5
系列伺服驱动器使用手册
第十章
通讯连接
161
10.2.2
RS485
communication parameters
Table
10-3 RS485
communication parameters setting
LED display
Internal
address
Name
Meaning
Default
d5.01
100B0010
ID_Com
Station No.
Station No., to change this
parameter, you need to save
it with the address d5.00
and restart it later
。
The
station number can be
changed by the DIP switch
under the panel. Details
refers to Chapter 3.8
1
d5.18
2FE20010
RS485
baud rate
Used to set the baud
rate of RS485
value
baud rate
1080
————
9600
540
————
19200
270
————
38400
90
————
115200
Note: need to save and restart.
540
d5.19
65100C08
RS485
protocol
selection
0
:
use
Modbus
communication protocol
1
:
use
RS232
communication
protocol
Note: need to save and
restart
。
0
65100E10
RS485
Mod
0008
:
data bit
=8
, stop
bit
=1
,
No parity check
0009
:
data bit
=8
, stop bit
=2
,
No parity check
0008