5
Pulse output
0~100KHz pulse output.
Analog output
1 channels analog output(0/4~20mA or 0/2~10V).
Operation
panel
LED Display
Display setting frequency, output frequency , output voltage, output current and so
on, about 20 parameters.
Parameters copy
Copy parameters by operation panel.
Keys lock and
function selection
Lock part of keys or all the keys. Define the function of part of keys
Protection function
Open phase protection (optional), overcurrent protection, overvoltage protection,
undervoltage protection, overheat protection, overload protection and so on.
Environment
Operating site
Indoor , installed in the environment free from direct sunlight, dust, corrosive gas,
combustible gas, oil mist, steam and drip.
Altitude
Derated above 1000m, the rated output current shall be decreased by 10% for
every rise of 1000m
Ambient
temperature
-10
℃
~40
℃
, derated at 40
℃
~ 50
℃
Humidity
5%~95%RH, non-condensing
Vibration
Less than 5.9m/s2 (0.6g)
Storage
temperature
-
40
℃~+
70
℃
Structure
Protection class
IP20
Cooling method
Air cooling, with fan control.
Installation method
Wall-mounted
Effeciency
≥9
0%
2.2 Introduction of product series
Table 2-1 Series of Kinco VFD
Model of VFD
Rated capacity(kVA)
Rated input
current(A)
Rated output
current(A)
Motor power(kW)
CV100-1S-0002G
0.6
6.0
1.3
0.2
CV100-1S-0004G
1.0
9.0
2.5
0.4
CV100-1S-0007G
1.5
18.0
4
0.75
CV100-1S-0011G
2.2
25.0
6
1.1
2.3 Structure of VFD
The structure of VFD is as following figure.