Hotwire thermo-anemometer 

VT110 - VT115

      

DESCRIPTION OF THE DEVICE

Backlight key

Hold/min/max key

Select key

On/Off/Esc key

OK key

Airflow direction

Red point : 
landmark

Protective tube of the 
sensitive element (1)

Sensitive element (velocity) 

Sensitive element
(temperature)

Bottom of the 

hotwire probe

Airflow direction

White point : 
landmark

Tube de protection de 
l'élément sensible (1)

Sensitive element (velocity) 

Sensitive element
(temperature)

Bottom of the telescopic 

hotwire probe 

Turn on the device by pressing on « 

On/Off/Esc

 ».

The device displays its name  « 

VT110

 » or « 

VT115 

» then the measured values.

Put the probe to the required location.

The device displays the measurements of velocity or airflow and of temperature.

PERFORM A MEASUREMENT

VT110 : Standard hotwire probe

VT115 : Telescopic hotwire probe

Before any device usage with the standard  or telescopic hotwire probe standard, please lower the protective tube (1) 
of the sensitive element.

Always use the hotwire probe with the red point in front of the flow.

Always use the telescopic hotwire probe with the white point in front of the flow.