Sirius Capacitor Module
–
User Manual
Model Number -7100-48-B-2C-M-SD-A-G
This manual is subject to change without notice and at the sole discretion of Kilowatt Labs, Inc.
Kilowatt Labs, Inc. |
28
6.
Sirius Module has advanced algorithm to control Module in safest way. This algorithm can be upgraded by
user with updating firmware of Sirius Module over
SiriusVIEW
Monitoring.
7.
Sirius Module firmware can be customized easily based on user needs.
8.
Sirius Module has
RS 232
interface to communicate with Host PC for:
•
Measurement Monitoring
•
Alarm Monitoring
•
System Configuration
•
Measurement Calibration
•
Manual/Auto Data Logging\Module firmware updating
•
Internal SD card reading/refreshing
•
Statistical Analyzing/ Graphical result
10.
Shelf Life:
Shelf life is the life of the Module in years from the date it is manufactured to the time it is first operated. The
shelf life of supercapacitor cell is 10 years.
11.
Maintenance:
The Sirius Module does not require periodic maintenance.
12.
Disposal:
Dispose according to local regulation.
13.
Test Procedures:
13.1 Round Trip Efficiency Test:
Round Trip efficiency test is performed to evaluate the performance of the Module. There are three factors to
be considered in the design of the test cycle for round trip efficiency.
•
How to charge and discharge the Sirius Module.
•
At what voltage to start and end the charge/discharge?
•
At which points to do the measurement.
Considering the efficiency and cost involved in the production line, we used constant current load test method
for Round trip efficiency characterization.
Test Equipment:
•
DC Charger test system or any other test system which can be used to charge and discharge Module with