Centauri Energy Server
–
User Manual
Model Number - GF-20000-360Vdc-380Vac-3/3
This manual is subject to change without notice and at the sole discretion of Kilowatt Labs, Inc.
Kilowatt Labs, Inc. |
24
proper ventilation to avoid the generation of explosive hydrogen and oxygen mixed gas.
→
The battery switch should be installed close to the battery as much as possible and ensure that
the distance between the battery and the Energy Server is shortest as much as possible.
•
Sirius Module:
→
Do not charge the Module when the temperature is below -30
o
C.
→
Do not charge the Module when temperature is above 80
o
C.
→
All Modules must be at 100% SOC or same voltage level before connecting in Series or in Parallel.
→
Modules cannot be connected in Series-Parallel combination under any circumstance.
4.7 Incoming Line Way of System:
The incoming lines of this product series are the lower wiring pattern. When making connection of
wires, open the front door of the Energy Server, unpack the downside baffle, you will see the
connection bar connected with the power cable.
4.8 Requirements of External Distribution:
•
Make sure that the power of the external power supply should be more than 1.5 times of the
equipment
’
s rated power and the rated current of the power circuit breaker supply nearby the
supply equipment should be more than 1.2 times (not the switch with one grade higher than the
breaker) of that of the air switch of the equipment itself (RECTIFIER or BYPASS).
•
The
“
BYPASS INPUT
”
and
“
AC INPUT
”
power supply system of the equipment should be equipped
with the separate
“
Circuit Breaker
”
or
“
Over-
current Protection Switch” in order to improve the
reliability of equipment.
•
The external power switch should be installed near the equipment so as to cut off the power
supply in the emergency situation.
Note!
There is the filter capacitor of the RFI filters to earth, which may generate some
leakage current, therefore the leakage protection switch should not be used for
the inverter power supply in this system in case of the false triggering protection
of the device.