![Kilowatt Labs 30-2012 Скачать руководство пользователя страница 13](http://html1.mh-extra.com/html/kilowatt-labs/30-2012/30-2012_user-manual_1967129013.webp)
CENTAURI ENERGY SERVER
User Manual - Model 30-2017/12/18-VERSION 1.0
13
BYP FAULT
Bypass fault
Bypass input is
Bypass fault
abnormal
AC FAULT
Rectifier fault
Rectifier input is
Rectifier fault
abnormal
SYS FAULT
System fault
System is normal
System fault
Table 10 Description of Output Signal at System Dry Contract
1.6
Product Specifications
Rated capacity(KVA)
10
20
30
40
50
60
Rated power (kW)
9
18
27
36
45
54
Rated current (A)
15
30
45
60
76
91
Output power factor
0.9
Rated input voltage
380V ±20%
Rated output voltage
380V ±1%
Battery pack voltage
360Vdc
The number of ESDs 12V/2V
30/180
Working mode
The PV and AC are complementary to PV and AC
Maximum voltage
0 V - 750Vdc
range (Voc)
Best working voltage
450 - 550Vdc
(Vmp)
Maximum
≥98%
conversion efficiency
Float charging
414 V± 1%
voltage
Equal charging
428V± 1%
pressure
PV Input
Maximum
40
60
120A
180A
charging current
Maximum working
40
60
120A
180A
current
Maximum power of
16
24
2*24
3*24
polar plate (KW)
1+1
PV input channels
(Reserve
2+1 (Reserved)
3+1 (Reserved)
d)
1+1
(Reserve
2+1 (Reserved)
3+1 (Reserved)
MPPT module
d)
Range of input
Three-phase 380V ±20%
voltage
Rated frequency
50 Hz / 60Hz (Background Setting)
AC rectifier
Frequency range
50 Hz / 60Hz ± 5Hz
Soft start
0-100% 10s
Power factor
PF = 0.8
Float charging voltage
410V±1%