21 of 56
Revision 4
KiloVault
®
LLC • 330 Codman Hill Road, Boxborough, MA 01719 • +1 (888) 218-5924 •
• www.kilovault.com
Note:
Prior to installing your KiloVault® HAB™ V4, take pictures of
the label on the left side, including the serial number, serial
number barcode, QR code, and MAC address. Store this
information for your records, it is valuable and may be
necessary for system configuration or troubleshooting.
Finding this information after installation may be difficult.
The KiloVault® HAB™ V4 should be installed high enough above the floor to
allow the battery cables to bend without kinking and allow easy access to the
knockouts on the bottom of the KiloVault® HAB™ V4. There should be about 8
inches (approx. 200 mm) of clearance on both sides.
Observe the following:
•
Install indoors in a cool, dry, ventilated space
•
Do not install near a heat source, and keep away from direct sunlight;
this prevents the KiloVault® HAB™ V4 from derating its output or
shutting down due to overheating
•
Keep away from fire, flammable, or explosive items
•
The KiloVault® HAB™ V4 must be out of the reach of children and
animals
•
Do not install near a transformer or any other strong electromagnetic
field. Strong electromagnetic fields can disrupt the KiloVault® HAB™ V4
communication system
Choose a wall capable of supporting the full weight of the KiloVault® HAB™ V4
(over 230 lb) with one or more of the following characteristics: wood studs at
regular intervals, plywood sheeting at least ¾ inch thick, solid concrete or
masonry, or metal studs of at least 18 gauge.
The KiloVault® HAB™ V4 communication and power cable entries are located at
the bottom right corner of the unit. There must be enough clearance for the
conduit and fittings.
4.5.
Install the KiloVault® HAB™ V4 Wall Mounting
Plate