PWX
19
1
Inst
allation
and Prep
aratio
n
Load Cables
The cables’ allowable current depends on the insulation’s maximum allow-
able temperature.
A cable’s temperature is determined by the resistive loss based on the current, the ambient
temperature, and the cable’s external thermal resistance. The following table shows the cur-
rent capacity of heat-resistant vinyl wires that have a maximum allowable temperature of
60°C, assuming that a wire is stretched out horizontally in air in an ambient temperature of
30°C. The current capacity must be reduced under certain conditions, such as when vinyl
cables that have a low heat resistance are used, when the ambient temperature is 30 °C or
greater, or when cables are bundled together and little heat is radiated.
Taking measures against noise
When connecting wires that have the same heat resistance, separating the wires as much as
possible to increase heat radiation enables a greater amount of current to flow. However, wir-
ing the + (positive) and - (negative) output wires of the load cable side by side or bundling
them together is more effective against unwanted noise. The Kikusui-recommended currents
shown in the above table are allowable currents that have been reduced in consideration of
the potential bundling of load cables. Use these values as a guideline when connecting load
cables.
Limitations of the remote sensing function
All wires have resistance. As the wire becomes longer or the current becomes larger, the volt-
age drop in the wire becomes greater. This results in a smaller voltage being applied at the
load end. The PWX series has a sensing function that compensates for this voltage drop up
to approximately 4 V for a single line. If the voltage drop exceeds this level, use wires that
have a greater cross-sectional area.
WARNING
Risk of fire.
• Use load cables whose capacity is adequate for the PWX series rated output current.
• The output connector and its surrounding area become hot. Use cables whose cov-
ers have heat resistance at 85 °C and higher.
Risk of electric shock.
• Use load cables whose rated voltage meets or exceeds the PWX series isolation volt-
age.
Nominal cross-sectional
area [mm
2
]
AWG (reference cross-
sectional area) [mm
2
]
Allowable current
1
[A]
(Ta = 30 °C)
1
Excerpt from Japanese laws related to electrical equipment.
Kikusui-recommended
current [A]
2
14
(2.08)
27
10
3.5
12
(3.31)
37
-
5.5
10
(5.26)
49
20
8
8
(8.37)
61
30
14
6
(13.3)
88
50
22
4
(21.15)
115
80
30
2
(33.62)
139
-
38
1
(42.41)
162
100
50
1/0
(53.49)
190
-
60
2/0
(67.43)
217
-
80
3/0
(85.01)
257
200
100
4/0
(107.2)
298
-
125
-
-
344
-
150
-
-
395
300
200
-
-
469
-
Содержание PWX1500H
Страница 10: ...10 PWX This page is intentionally blank...
Страница 26: ...26 PWX This page is intentionally blank...
Страница 88: ...88 PWX This page is intentionally blank...
Страница 89: ...Maintenance This chapter explains how to perform cali bration DELETE...
Страница 92: ...92 PWX This page is intentionally blank...
Страница 93: ...Specifications This chapter contains the specifications and gives the dimensions of the PWX series...
Страница 120: ...120 PWX This page is intentionally blank...
Страница 121: ...Appendix A Options B Troubleshooting...
Страница 128: ...128 PWX This page is intentionally blank...