PBZ
141
5
Ext
ernal Co
ntrol, Pa
rallel
Operation, an
d Synchronizat
ion
Signal Output
Status signals
Status signal output that enables you to externally monitor the PBZ’s operating state. Each
signal is an open-collector output from a photocoupler. STATUS COMMON is isolated from
ANALOG COMMON and DIGITAL COMMON. The maximum ratings for each signal terminal
are as follows:
•
Maximum voltage: 30 V. Maximum current (sink): 8 mA.
Monitor signals
Voltage output that enables you to externally monitor the output voltage and output current.
Monitor signals during parallel operation
Option output
General-purpose digital output that can only be set by communication commands
(OUT:PORT). Each signal is an open-collector output from a photocoupler. STATUS
COMMON is isolated from ANALOG COMMON and DIGITAL COMMON. The maximum
ratings for each signal terminal are as follows:
•
Maximum voltage: 30 V. Maximum current (sink): 8 mA.
Pin no.
Signal name
Operation (photocoupler output)
Circuit
8
CV STATUS
On in CV mode.
6
CC STATUS
On in CC mode.
4
OUTPUT ON
STATUS
On when output is on.
2
ALARM STATUS
On when an alarm (OVP, OCP, or OHP) is occurring.
1
STATUS COMMON
Common for status outputs (pins 2, 4, 6, and 8) and
option output (pin 5); isolated from the photocoupler
emitter, ANALOG COMMON, and DIGITAL COMMON.
Pin no.
Signal name
Description
13
CV MONITOR
Voltage output that is proportional to the output voltage measured at
the load end of the sensing cable. For an output voltage of 0 V to ±the
rated value, this pin generates a voltage of 0 V to approximately ±2 V.
9
CC MONITOR
Voltage output that is proportional to the current that the PBZ
generates. For an output current of 0 A to ±the rated value, this pin
generates a voltage of 0 V to approximately ±2 V.
11, 12
ANALOG COMMON
Monitor output common; connected to the OUTPUT terminal’s COM.
Pin no.
Signal name
Master unit
Slave unit
13
CV MONITOR
Voltage output that is proportional to the output voltage measured at
the load end of the sensing cable. For an output voltage of 0 V to ±the
rated value, this pin generates a voltage of 0 V to approximately ±2 V.
9
CC MONITOR
Voltage output that is proportional to
the current that the PBZ generates
(the sum of the currents produced by
all units operating in parallel). For an
output current of 0 A to ±(the rated
value x the number of units in parallel
operation), this pin generates a
voltage of 0 V to approximately ±2 V.
Voltage output that is
proportional to the current
that the PBZ slave unit
generates. For an output
current of 0 A to ±the
rated value, this pin
generates a voltage of 0 V
to approximately ±2 V.
11, 12
ANALOG COMMON
Monitor output common; connected to the OUTPUT terminal’s COM.
Pin no.
Signal name
Operation (photocoupler output)
Circuit
5
OPTION
Set to on by an OUT:PORT ON (1) command.
1
STATUS COMMON
Common for status outputs (pins 2, 4, 6, and 8) and
option output (pin 5); isolated from the photocoupler
emitter, ANALOG COMMON, and DIGITAL COMMON.
1
2
4
6
8
1
5
Содержание PBZ20-20
Страница 11: ...PBZ 11 ...
Страница 18: ...18 PBZ ...
Страница 75: ...Memory Response and Configuration This chapter explains preset memory setup memory response and configura tion ...
Страница 95: ...Sequences This chapter explains sequences ...
Страница 153: ...Maintenance This chapter describes how to clean and inspect the PBZ ...
Страница 156: ...156 PBZ Maintenance ...
Страница 157: ...Appendix A List of Factory Default Settings B Troubleshooting C List of Error Messages D Options ...