Basic Terms and Definitions
Basic terms related to the general measurement
L1, L2 and L3 represent the values of the L1 phase, L2 phase and L3 phase.
Zsys4[ohm]
Permissible system impedance value calculated after converting the measured value
of Plt with a set impedance
Zmax
Calculated value of the maximum permissible system impedance.
Calculated minimum values of Zsys1, Zsys2, Zsys3 and Zsys4.
Maximum permissible system impedance of a power supply to which equipment is
connected (power receiving point). Value to be declared as the condition for
connection.
Voltage
Vrms
Single-phase three-wire: (L1 Vrms +L2 Vrms) /2
Three-phase three-wire, Three-phase four-wire: (L1 Vrms +L2 Vrms +L3 Vrms) /3
Current
Arms
Single-phase three-wire: (L1 A rms +L2 Arms) /2
Three-phase three-wire, Three-phase four-wire: (L1 Arms +L2 Arms +L3 Arms) /3
Apparent power
VA
Single-phase three-wire: L1 VA +L2 VA
Three-phase three-wire:
(L1 VA +L2 VA +L3 VA) × (
/3)
Three-phase four-wire: (L1 VA +L2 VA +L3 VA) /3
Real power
W
Single-phase three-wire: L1 W +L2 W
Three-phase three-wire: L1 W +L3 W
Three-phase four-wire: L1 W +L2 W +L3 W
Reactive power
var
Single-phase three-wire: L1 var +L2 var
Three-phase three-wire: L1 var +L3 var
Three-phase four-wire: L1 var +L2 var +L3 var
3
Scaling
When any external current sensor or external PT (potential transformer) is used to
input current or voltage signals, the associated conversion factor or ratio is set for the
signal to determine the current or voltage range of this product and this operation is
called scaling.
Current scaling
Applying scaling to the current signal of an external current sensor.
Voltage scaling
Applying scaling to match the voltage ratio of an external PT (potential transformer).
CT Ratio
The scaling factor of CT (current transformer)
PT Ratio
The scaling factor of PT (potential transformer)
Содержание KHA3000
Страница 20: ...20 KHA3000...
Страница 35: ...Overview This chapter provides an overview of this product and explains the options for the product 1...
Страница 42: ...42 KHA3000 Options...
Страница 49: ...Wiring Measurement Circuits This chapter explains the wiring of measurement circuits and the control circuit 3...
Страница 70: ...70 KHA3000 Connecting Communication Cables...
Страница 71: ...System Setup This chapter explains how to turn on the power and how to set up the system 4...
Страница 91: ...Setting the Harmonic Test This chapter explains how to set the test conditions for the harmonic current test 5...
Страница 120: ...120 KHA3000 Controlling the AC Power Supply...
Страница 182: ...182 KHA3000 Checking the AC Power Supply and Repeatability...
Страница 247: ...Other Measurements This chapter explains basic measurement FFT analyzer and in rush current measurement 11...
Страница 349: ...Maintenance This chapter explains how to clean and inspect this product 14...
Страница 352: ...352 KHA3000 Cleaning and Checking...
Страница 353: ...Specifications This chapter explains the specifications of this product 15...
Страница 390: ...390 KHA3000...
Страница 391: ......