19
Electricalinstallation
Type 8615500120-000 / 8615500130-000
Pilot air
port
Label: 1
Exhaust air
port
Label: 3
Additional exhaust
air port
Label: 3.1
(only with pilot-controlled control system for a high air flow rate from
actuator size ø 125 / 130)
Fig. 9:
Pneumatic connection
procedure:
→
Connect the control medium to the pilot air port (1)
(3 ... 7 bar; instrument air, free of oil, water and dust).
→
Mount the exhaust air line or a silencer on the exhaust air port (3)
and, if present, on the exhaust air port (3.1).
11 elecTrical insTallaTion
There are 2 connection options for Type 8615500120-000 /
8615500130-000:
• Multi-pole with circular plug-in connector
• Cable gland with connection terminals
signal values
Operating voltage:
24 V DC
Set-point value
(process/position controller):
0 ... 20 mA; 4 ... 20 mA
0 ... 5 V; 0 ... 10 V
Actual value
(only process controller):
4 ... 20 mA;
frequency;
Pt 100
11.1 safety instructions
Danger!
risk of injury due to electrical shock!
▶
Before reaching into the system, switch off the power supply
and secure to prevent reactivation!
▶
Observe applicable accident prevention and safety regulations
for electrical equipment!
English