JMNC Operating Instructions
4 Technical Data
4.4
Input Data
4.5
Output Data
Indicator input/pulse input
Terminals 1, 2
Indicator type
all 2-wire pulse indicators according to NAMUR (EN 50227), e. g. Kiepe type DG or DK
or 3-wire pulse indicator (npn), z. B. Kiepe type EOG.
Min. pulse duration of the indicator
≥
1.5 ms
Pulse ranges (adjustable)
pulses/minute
switch-off delay in s (excl. relay dropping time)
I
8 … 120
7.5 … 0.5
II
80 … 1200
0.75 … 0.05
III
800 … 12000
0.075 … 0.005
Relay output
Terminals 8,9,10
Type of contact
1 change-over contact
Max. switching voltage (AC/DC)
250 V (AC) / 250 V (DC)
Max. switching current (AC/DC)
5 A (AC) / 1 A (DC)
Max. switching capacity (AC/DC)
1000 VA (AC) / 30 W (DC)
Triggering time of the relay
200 ms (after applying supply voltage)
Pulse output
Terminal 4
I
L
≤
1 mA
DC output
Terminal 5
Output voltage
24 V (DC)