background image

Product Description

MD15-HE, MD15-R-HE

Q

Page 6 / 14

3.09-20.125-01-EN | 2019-08-19

Rxx and RWxx two-way/three-way valves for MD15-HE and MD15-R-HE small actuators

Types

PN10 gunmetal two-way valve for water up to 120 °C 

PN10 gunmetal three-way valve for water up to 120 °C

Technical data: Rxx and RWxx valves

Type

DN

PN

Kvs

R

Straight-through flow

R10D

10

10

1.25

3/8"

R15D

15

10

1.35

1/2"

R20D

20

10

2.5

3/4"

Flow through 90°

R10E

10

10

1.25

3/8"

R15E

15

10

1.35

1/2"

R20E

20

10

2.5

3/4"

Straight-through flow

R10DV

10

10

0.86

3/8"

with Kvs setting

R15DV

15

10

0.86

1/2"

R20DV

20

10

0.86

3/4"

Flow through 90°

R10EV

10

10

0.86

3/8"

with Kvs setting

R15EV

15

10

0.86

1/2"

R20EV

20

10

0.86

3/4"

Type

DN

PN

Kvs

R

Connection left

RW15L

10

10

1.45

1/2"

Connection right

RW15R

15

10

1.45

1/2"

Nominal diameter

DN10 - 20

Pressure rating

PN10

Connection

Pipe screw connections in accordance with DIN EN 2115

Actuating stroke

2 mm

Temperature of 
medium

Water up to 120 °C

Housing

Gunmetal; nickel-plated

Cone

EPDM

Valve spindle

Stainless steel

Spindle seal

EPDM

Maintenance

Maintenance-free

R10..20D, R10..20DV

R10..20E, R10..20EV

RW15L

RW15R

Содержание MD15-HE

Страница 1: ...sition or continuous control systems for zone post treatment devices for heating ventilation and air conditioning systems Content Page Important Information Regarding Product Safety 2 MD15 HE and MD15...

Страница 2: ...r to comply with local regulations Mounting installation and commissioning work on the devices may only be carried out by qualified technicians Qualified technicians are persons who are familiar with...

Страница 3: ...5 mm2 Motor switch off Actuator spindle when extending load dependent when retracting path dependent Display LED display for operating voltage Actuating noise 28 dB A Positioning stroke 3 mm Position...

Страница 4: ...09 20 125 01 EN 2019 08 19 Dimensions Connection 86 5 48 5 60 51 75 M30x1 5 DIN 13 Continuous control M GY 24 V AC DC BU BN 0 V AC DC Y 0 2 10 V DC 1 2 3 MD15 HE GY 24 V AC DC BU BN 0 V AC DC Y 0 2 10...

Страница 5: ...HE MD15 R HE Product Description Q Page 5 14 3 09 20 125 01 EN 2019 08 19 Three point control Two point control GY 24 V AC DC BU BN 0 V AC DC M 1 2 3 MD15 HE GY 24 V AC DC BU BN 0 V AC DC M 1 2 3 MD1...

Страница 6: ...1 2 R20E 20 10 2 5 3 4 Straight through flow R10DV 10 10 0 86 3 8 with Kvs setting R15DV 15 10 0 86 1 2 R20DV 20 10 0 86 3 4 Flow through 90 R10EV 10 10 0 86 3 8 with Kvs setting R15EV 15 10 0 86 1 2...

Страница 7: ...The maximum flow rate Kvs value m h can be selected by using the settings 1 2 3 4 5 6 7 or 8 delivery setting 8 corresponds to a Kvs value 0 86 The setting can be made using a Z29 socket key accessor...

Страница 8: ...ce of 10 times the nominal diameter is recommended between the valve flange and manifold or other similar parts The installation location is to be selected so that the ambient temperature at the actua...

Страница 9: ...rential pressure builds up in the valve body before beginning work If necessary close the gate valve and turn off pumps After the pipeline has cooled off the actuator can be installed Be sure to compl...

Страница 10: ...ten hand tight using the union nut Establish the electrical connection After the line power has been switched on an automatic initialization run takes place The actuator first travels to the upper end...

Страница 11: ...ose the gate valve and turn off pumps After the pipeline has cooled off you can begin removing the actuator CAUTION Before beginning to remove the unit move the actuator to the uppermost position Remo...

Страница 12: ...ket 4 mm can be used to move the actuator into any position CAUTION If you manually adjust until the slip clutch responds turn the hexagon key half a turn in the opposite direction after the manually...

Страница 13: ...ing commissioning Valve exercise prevents the cone from jamming when the valve is not moved for a long period of inactivity e g for heating systems during the summer If valve exercise is activated the...

Страница 14: ...Product Description MD15 HE MD15 R HE Q Page 14 14 3 09 20 125 01 EN 2019 08 19...