background image

 

Technical Data Sheet 2.50-35.021-01-en Rev

FSM21 Front Switch Module

For connection to the FBM38 fieldbus module. 

 

D e v i ce   De s c ri p ti on  

A

LED Settings 

The green signal LEDs can be switched off individually (optional). 
The setting is made using a DIP switch behind the front panel of the FSM21. The corresponding DIP switches are 
arranged next to the LEDs. 
 

 

 

ON

12

Ein

Aus

 

LEDs can be 
switched 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Commissioning 

 

 

Commissioning may only be carried out by qualified personnel, e.g. a commissioning 
technician. The power must be disconnected from the switchboard. 

Danger 

 
 

  Check the mounting, installation and device connections with the power disconnected from the FBM38 fieldbus 

module and FSM21 front switch module. 

 

 

Settings on the FBM38 fieldbus module

 

The device description of the FBM38 fieldbus module must be observed here (Technical Data Sheet 2.50-30.038-
01-en). 

 

– Assign macro 21 using the FSM selector switch .

2

.. 

 

- Adjust the macro functions using DIP switches .

3

., .

4

. and .

6

.. 

 

  Switch on the power supply and check the switching functions with the messaging and acknowledgement 

functions of the FSM21 and FBM38 operating unit.  

 

Page 9 / 12 

Содержание FSM21

Страница 1: ...FSM21 front switch module is used for the direct operation of 1 or 2 stage unit or device switches The module functions through macro assignments on the FBM38 fieldbus module A load rolling switch wit...

Страница 2: ...be carried out by qualified technicians See the Qualified Technicians section Each person who uses the devices must have read and understood the descriptions on the technical data sheet If the device...

Страница 3: ...Power is supplied over the QB interface Connection Terminal connection to QB interface 4 wire maximum cable length 200 m Controls Two manual automatic switches for the Automatic Off Position1 Positio...

Страница 4: ...ilable as an accessory for wall mounting Mounting on a switchboard or in a 19 KA rack may only be carried out by qualified technicians The power must be disconnected from the switchboard Switchboard e...

Страница 5: ...ackbone Anschluss an max 63 FBM38 und max 16 SBM21 41 37 37 33 32 34 33 35 34 L N Ger t Aggregat 1 41 42 44 K4 Die bin ren Eing nge 55 IN 58 IN k nnen als Schlie er oder ffner angeschlossen werden Ums...

Страница 6: ...de on the FBM38 fieldbus module The FBM settings and a detailed macro description are found in technical data sheets 2 50 30 038 01 en and 2 50 30 038 02 en Both of these are included with the FBM38 f...

Страница 7: ...4 in automatic and manual mode each lock against each other or switch together The switching delays apply in the same way when the load rolling switch is switched on in automatic and manual operation...

Страница 8: ...the operating message input and control signal match Green signal LED 1 1 1 2 2 1 2 2 with Local operating mode activated Two signal LEDs are found to the right of each manual automatic switch They a...

Страница 9: ...onnel e g a commissioning technician The power must be disconnected from the switchboard Danger Check the mounting installation and device connections with the power disconnected from the FBM38 fieldb...

Страница 10: ...or On 6 s Off 3 s Malfunction message inversion Yes No Operating mode Remote Local Control of unit 1 Control of unit 2 _____________________________ _____________________________ Mechanical limitation...

Страница 11: ...Technical Data Sheet 2 50 35 021 01 en Rev FSM21 Front Switch Module For connection to the FBM38 fieldbus module Device Description A Other setting notes Page 11 12...

Страница 12: ...Page 12 12 Technical Data Sheet 2 50 35 021 01 en Rev Device Description FSM21 Front Switch Module For connection to the FBM38 fieldbus module A...

Отзывы: