manualshive.com logo in svg
background image

P/N 3101780-EN • REV 03 • ISS 16FEB16 

 

1 / 2 

 

VM-ELEC Chassis Electronics 

Assembly Installation Sheet 

 

Description 

The VM-ELEC Chassis Electronics Assembly provides the mounting, 

internal power, and audio and data distribution for the VM-CPU main 

board, user interface, and supporting cards. 

Installation 

WARNING: 

Electrocution hazard. To avoid personal injury or death 

from electrocution, remove all sources of power and allow stored 

energy to discharge before installing or removing equipment. 

Caution: 

Circuit boards are sensitive to electrostatic discharge (ESD). 

To avoid damage, follow ESD handling procedures. 

Note: 

Install the PS10-4B power supply board and any cabinet 

backbox-mounted options before installing the VM-ELEC. 

To install the VM-ELEC: 

1.  Connect one end of the data ribbon cable to J17 on the VM-CPU. 

Refer to Figure 2 for the VM-CPU location on the assembly. 

Refer to the 

VM-CPU Main Board Installation Sheet

 (P/N 3101798-

EN) received in the instruction sheet bag with the VM-ELEC for 

additional information.  

2.  Connect one end of the power supply cable to J15 on the  

VM-CPU. 

3.  Connect the other end of the data ribbon cable to J1 on the  

PS10-4B. See Figure 1. 

Refer to the 

PS10-4B Power Supply Board Installation Sheet

  

(P/N 3101774-EN) received with the board for additional 

information. 

4.  Connect the other end of the power supply cable to J2 on the 

PS10-4B. 

5.  Attach the VM-ELEC to the four screws on the backbox using the 

hardware provided. See Figure 1. 

Wiring 

Connect VM-CPU field wiring as described on the 

VM-CPU Main 

Board Installation Sheet

 (P/N 3101798-EN).  

Maintain 0.25 in. (6 mm) separation between power-limited and 

nonpower-limited wiring at all times. Keep nonpower-limited wiring in 

the shaded area shown in Figure 3. Secure the wiring to the cabinet 

using nylon cable ties. 

 

Figure 1: Installing the VM-ELEC assembly 

 

(1)  PS10-4B power supply protective cage is installed here for ULC applications 

(2)  Data ribbon cable (P/N 250189-01) 

 

(3)  Power supply cable (P/N 250187-01) 

(4)  #8-32 K-nuts (4X) 

(4)

PS10-4B

(1)

(2)

(3)

Отзывы: