P/N 3102359-EN • REV 002 • ISS 21OCT20 

 

3 / 3 

Specifications 

 
Operating voltage 

 

Riser 

 

SLC 

 

16 to 33 VDC 

15.2 to 19.95 VDC 

Current 

 

Standby 

 

Alarm TC3 

 

Alarm TC4 

 

60 µA 

380 µA 

550 µA 

SLC wiring 

 

Resistance 

 

Capacitance 

 

Ground fault impedance 

 

66 Ω, max.

 

0.5 µF, max. 

0 to 5 kΩ

 

T3T4 riser wiring 

Supervised and power-limited 

Class B 

Output rating 

3.5 A max. Actual value limited by 

system power outputs 

Wire size 

12 to 18 AWG (0.75 to 2.50 mm²) 

Circuit designation 

Signaling line circuits (SLC) are Style 4 

(Class B) or Style 6 (Class A) 

Compatible sounder bases  KI-ABDT, KI-ABST, KI-ABLT 
Compatible electrical box  

4 in. square box, 1-1/2 in. (38 mm) deep 

Operating environment

 

Temperature 

 

Relative humidity 

 

32 to 120°F (0 to 49°C) 

0 to 93% noncondensing 

Storage temperature 

−4 to 140°F (−20 to 60°C)

 

 

Regulatory information 

 
UL rating 

Regulated 24 DC 

Environmental 

class 

Indoor, dry 

FCC compliance 

This device complies with part 15 of the FCC 

Rules. Operation is subject to the following two 

conditions: (1) This device may not cause harmful 

interference, and (2) this device must accept any 

interference received, including interference that 

may cause undesired operation. 

Industry Canada 

compliance 

This Class A digital apparatus complies with 

Canadian ICES-003. 

Contact information 

For contact information, see www.kidde-esfire.com. 