Intelligent Suppression Control/Fire Alarm System
PEGAsys
August 1999
76-100016-001
2-15
for further details on RCU registration.
1: Alarm
Active input initiates an alarm at the central control
panel and is latched in the EOC until the system is
reset after alarm has cleared.
2: Trouble
Active input initiates a trouble at the central control
panel, but does not latch EOC programming and will
self restore upon deactivation.
3: Abort
Active input initiates an abort condition at the central
control panel. This will delay agent release if count-
down has begun. It does not latch EOC program and
will self restore upon deactivation. There are 4 styles
of abort available for the device.
4: Waterflow
Active input initiates a waterflow alarm condition at the
central control panel and is latched in EOC program
until reset. Signal outputs will be inhibited from being si-
lenced.
5: Manual Alarm
Active input initiates a manual alarm condition at the
central control panel, latches in EOC program until
reset.
6: Manual Release
Active input initiates a manual release condition at the
central control panel, causes instant release of pro-
grammed output, latches in EOC program until reset
7: Normal
Active input initiates a momentary display but does not
latch in EOC program, self restores.
8: Supervisory
Active input initiates a supervisory trouble at the cen-
tral control panel, but does not latch the EOC, and will
self-restore upon deactivation.
The 40 character owner location message cannot be entered
using the system keypad. The owners location message can
only be entered by use of the PCS program and uploaded into
system memory.
2-8.7.3 REMOTE RELAY REGISTRATION
The addressable contact output device is registered in the
same fashion as the previous RCU's.
Contact Output RCU’s can also be registered into the system
by using the PCS program. The installer would specify each
Contact Output RCU to be connected to the system and then
upload the system configuration file to the system and then the
system would supervise each device specified. Refer to the PCS
user’s guide (76-014) for further details on RCU registration.
The 40-character owner location message cannot be entered
using the system keypad. The owners location message can
only be entered by use of the PCS program and uploaded into
system memory.
2-8.7.4 LISTING ALL REGISTERED RCUs
All RCUs registered on the system can be listed using either the
owners or installers menu function. To list all registered RCUs
a.
Access the
PEGAsys
system menus by:
(1) Press 0 (zero) key. Verify that the display reads:
PLEASE ENTER PASSWORD
(2) Type in the Level 1 or Level 2 password.
(3) Press the return (
↵
) key. Verify that the display reads:
1:ISOLATE
2:LIST
3:SET
4:TEST
b.
Select the List RCU address function by typing the function
formula, 2-6-1. Verify that the display and any attached print-
ers list all registered RCU addresses.
2-8.7.5 UN-REGISTERING RCUs
The system provides the capability to remove a single device or
group of devices from the system configuration. This function
removes the device address from the system memory but leaves
the address in the device intact. Performing this operation will
cause the system to generate a trouble NR (Not Registered) for
any devices which remain connected to the RX/TX PC line.
Removal or disconnection of the device(s) from the PC line will
clear the trouble condition(s) on the system.
This function would be used during a system retrofit where some
devices may be desired to be removed from the system tempo-
rarily during a building renovation and then reattached after reno-
vations are complete. This feature is very efficient because the
device maintains its address information which speeds device
reregistering after the renovations.
To perform the device un-registering operation perform the fol-
lowing:
a.
Access the
PEGAsys
system menus by:
(1) Press 0 (zero) key. Verify that the display reads:
PLEASE ENTER PASSWORD
(2) Type in the Level 1 or Level 2 password.
(3) Press the return (
↵
) key. Verify that the display reads:
1:ISOLATE
2:LIST
3:SET
4:TEST
b.
Select the set RCU De-Registration function by typing the
function formula, 3-3-4. Verify that the display reads:
DEVICE DE-REGISTRATION
DEVICE FROM_ _ _ _TO_ _ _ _
c.
Enter the desired RCU address(s) and press return. The
display will read the following in response to verify the de-
vice de-registration:
DEVICE DE-REGISTRATION
XX DEVICES DE-REGISTERED
d.
Verify that the display changes to the device menu after 5
seconds. The backspace key can be pressed to return to
the main menu.
e.
To reregister RCU devices, perform the procedure which is out-
lined in the RCU registration paragraph in this chapter.