Design and Installation
October 2014
4-6
06-236115-001
Table 4-5. HFC-227ea Total Flooding Concentration Factors (W/V), Metric
Temp
a
(°C)
C
Specific
Vapor
Volume
(m
3
/kg)
d
Weight Requirements of Hazard Volume,
(kg/m
3
)
b
Design Concentrations (% by Volume)
e
6.25
6.70
7
8
9
10
11
12
13
14
15
0
0.1268
0.5258
0.5659
0.5936
0.6858
0.7800
0.8763
0.9748
1.0755
1.1785
1.2839
1.3918
5
0.1294
0.5152
0.5550
0.5816
0.6719
0.7642
0.8586
0.9550
1.0537
1.1546
1.2579
1.3636
10
0.1320
0.5051
0.5444
0.5700
0.6585
0.7490
0.8414
0.9360
1.0327
1.1316
1.2328
1.3364
15
0.1347
0.4949
0.5343
0.5589
0.6457
0.7344
0.8251
0.9178
1.0126
1.1096
1.2089
1.3105
20
0.1373
0.4856
0.5246
0.5483
0.6335
0.7205
0.8094
0.9004
0.9934
1.0886
1.1859
1.2856
25
0.1399
0.4765
0.5151
0.5382
0.6217
0.7071
0.7944
0.8837
0.9750
1.0684
1.1640
1.2618
30
0.1425
0.4678
0.5061
0.5284
0.6104
0.6943
0.7800
0.8676
0.9573
1.0490
1.1428
1.2388
35
0.1450
0.4598
0.4973
0.5190
0.5996
0.6819
0.7661
0.8522
0.9402
1.0303
1.1224
1.2168
40
0.1476
0.4517
0.4888
0.5099
0.5891
0.6701
0.7528
0.8374
0.9230
1.0124
1.1029
1.1956
45
0.1502
0.4439
0.4807
0.5012
0.5790
0.6586
0.7399
0.8230
0.9000
0.9950
1.0840
1.1751
50
0.1527
0.4366
0.4728
0.4929
0.5694
0.6476
0.7276
0.8093
0.8929
0.9784
1.0660
1.1555
55
0.1553
0.4293
0.4651
0.4847
0.5600
0.6369
0.7156
0.7960
0.8782
0.9623
1.0484
1.1365
60
0.1578
0.4225
0.4577
0.4770
0.5510
0.6267
0.7041
0.7821
0.8410
0.9469
1.0316
1.1183
65
0.1604
0.4156
0.4505
0.4694
0.5412
0.6167
0.6929
0.7707
0.8504
0.9318
1.0152
1.1005
70
0.1629
0.4092
0.4436
0.4621
0.5338
0.6072
0.6821
0.7588
0.8371
0.9173
0.9994
1.0834
75
0.1654
0.4031
0.4368
0.4550
0.5257
0.5979
0.6717
0.7471
0.8243
0.9033
0.9841
1.0668
80
0.1679
0.3971
0.4303
0.4482
0.5178
0.5890
0.6617
0.7360
0.8120
0.8898
0.9694
1.0509
85
0.1704
0.3912
0.4239
0.4416
0.5102
0.5803
0.6519
0.7251
0.800
0.8767
0.9551
1.0354
90
0.1730
0.3854
0.4178
0.4351
0.5027
0.5717
0.6423
0.7145
0.7883
0.8638
0.9411
1.0202
a The minimum design temperature in the flooded space.
b
[agent weight requirements (
kg/m
3
)] = Kilograms of agent required per cubic meter of protected volume
to produce indicated concentration at the temperature specified.
c [temperature (°C)] = The design temperature in the hazard area.
d [specific volume
(m
3
/kg)
] = Specific volume of superheated HFC-227ea vapor can be approximated by the formula:
where = temperature (°C)
e
[concentration (%)] = Volumetric concentration of HFC-227ea in air at the temperature indicated.
t
s
W V
W V
W
V s
c
100
c
–
=
t
s
s
0.1269
0.0005
t
+
=
t
C
Содержание ECS
Страница 3: ......
Страница 9: ...THIS PAGE INTENTIONALLY LEFT BLANK October 2014 vi 06 236115 001 ...
Страница 19: ...October 2014 xvi 06 236115 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 25: ...October 2014 1 6 06 236115 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 63: ...Component Description October 2014 3 36 06 236115 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 103: ...Design and Installation October 2014 4 40 06 236115 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 137: ...Post Discharge Maintenance October 2014 6 18 06 236115 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 148: ...P N 06 236115 001 A 1 October 2014 APPENDIX A MATERIAL SAFETY DATASHEETS ...
Страница 167: ...October 2014 A 2 P N 06 236115 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 168: ......
Страница 171: ......
Страница 173: ...July 2016 ii 06 236115 003 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 186: ......
Страница 189: ......
Страница 191: ...August 2016 ii 06 237553 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 198: ......
Страница 201: ......
Страница 203: ...May 2016 ii 06 236115 004 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 211: ...May 2016 8 06 236115 004 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 212: ......