0208 681 0097
13
Operating & Maintenance
SEM & SE200ES Pressurisation
Set
10). Operation
➢
The control of the system is by the use of pressure transducers interfacing with a pre-
programmed intelligent relay.
➢
As the pressure in the system falls below the pre-set fill pressure, the pressure will be
detected by the transducer which will enable the duty pump to operate under the dictates of
the settings within the intelligent relay.
➢
The pump will then deliver water to the system thereby raising the pressure until the cut-out
pressure is reached at which point the pump will stop.
➢
The duty pump will automatically rotate per operation in an attempt to achieve even wear on
the pumps.
➢
Should the duty pump fail for any reason, the secondary pump will start as the duty pump.
➢
If the pressure within the system goes beyond the pre-set limits, the system pressure alarm
will activate, illuminating the fault codes displayed on the ‘Zelio’, and operating a volt-free
contact (which is usually connected to shut down the burner/chiller).
11). Product Specific Manuals
For further details please refer to the specific manufacturer product manual available via QR code(s)
below or via
https://kgnpillinger.co.uk/download-centre/
Manufacturers/ products are identifiable by their product name plates located on the individual
product
Lowara PSAM70 pumps
Scan the code with your smart device camera (or click the code) to
be directed to the product specific operating manual for in-depth
details.