Remote Sense Connections
Remote sensing improves the voltage regulation at the load by monitoring the voltage there instead of
at the output terminals. This allows the power supply to automatically compensate for the voltage
drop in the load leads. Remote sensing is especially useful for CV operation with load impedances that
vary or have significant lead resistance. It has no effect during CC operation. Because sensing is
independent of other power supply functions, remote sensing can be used regardless of how the
power supply is programmed.
Connect the unit for remote sensing by first removing the local sense cable between the sense and
load terminals. Then make your connections as shown in the following figure.
Connect the output terminals to the load using separate connecting wires. Keep the wire-pair as short
as possible and twist or bundle it to reduce lead inductance and noise pickup.
2 Installing the Instrument
72
Keysight RP7900 Series Operating and Service Guide
Содержание RP7900 Series
Страница 1: ...Keysight Regenerative Power System RP7900 Series Operating and Service Guide ...
Страница 2: ......
Страница 51: ...Dimensions RP793xA and RP794xA Keysight RP7900 Series Operating and Service Guide 51 1 Quick Reference ...
Страница 60: ...Dimensions RP795xA and RP796xA 1 Quick Reference 60 Keysight RP7900 Series Operating and Service Guide ...
Страница 100: ......
Страница 244: ...Status Diagram 5 SCPI Programming Reference 244 Keysight RP7900 Series Operating and Service Guide ...
Страница 246: ...Trigger Diagram 5 SCPI Programming Reference 246 Keysight RP7900 Series Operating and Service Guide ...
Страница 262: ......
Страница 314: ......