![Keysight Technologies N6900 Series Скачать руководство пользователя страница 322](http://html1.mh-extra.com/html/keysight-technologies/n6900-series/n6900-series_operating-and-service-manual_1962217322.webp)
Test Record Forms
N6950A/N6970A
N6950A/N6970A Test Record
Report Number ______
Date__________
Test Description
Model
Min. Specs
Results
Max. Specs
Voltage Programming & Readback
Minimum voltage (Vout):
Voltage measured over interface:
High voltage (Vout):
Voltage measured over interface:
Both
Both
Both
Both
+ 7.5 mV
Vout – 1.5 mV
8.9958 V
Vout – 4.2 mV
_______
_______
_______
_______
+ 10.5 mV
Vout + 1.5 mV
9.0042 V
Vout + 4.2 mV
CV Load Effect:
Both
– 0.5 mV
_______
+ 0.5 mV
CV Ripple and Noise
peak-to-peak:
rms:
Both
Both
N/A
N/A
_______
_______
+ 9 mV
+ 1 mV
Transient response @ 100 µs:
Both
– 150 mV
_______
+ 150 mV
Current Programming & Readback
Minimum current (Iout):
Current measured over interface:
High current (Iout):
Current measured over interface:
N6950A
N6970A
N6950A
N6970A
N6950A
N6970A
N6950A
N6970A
– 30 mA
– 60 mA
Iout – 30 mA
Iout – 60 mA
99.87 A
199.74 A
Iout – 0.13 A
Iout – 0.26 A
_______
_______
_______
_______
_______
_______
_______
_______
+ 30 mA
+ 60 mA
Iout + 30 mA
Iout + 60 mA
100.13 A
200.26 A
Iout + 0.13 A
Iout + 0.26 A
CC Load Effect:
N6950A
N6970A
– 8 mA
– 15 mA
_______
_______
+ 8 mA
+ 15 mA
Current Sink Tests
10% of current rating:
100% of current rating:
N6950A
N6970A
N6950A
N6970A
– 10.04 A
– 20.08 A
– 100.13 A
– 200.26 A
_______
_______
_______
_______
– 9.96 A
– 19.92 A
– 99.87 A
– 199.74 A
N6950A Settings
N6970A Settings
Voltage Programming & Readback Min:
Voltage Programming & Readback High:
CV Load Effect, CV Ripple and Noise:
Transient Response:
Current Programming & Readback Min:
Current Programming & Readback High:
CC Load Effect:
10% of current rating (Isink):
100% of current rating (Isink):
Voltage priority: 9 mV, 100 A
Voltage priority: 9 V, 100 A
Voltage priority: 9 V, 100 A
Voltage priority: 9 V, 50 A to 100 A
Current priority: 9 V, 0 A
Current priority: 9 V, 100 A
Current priority: 9 V, 100 A
Current priority: 9 V, - 10 A
External supply: 9 V, 11 A
Current priority: 9 V, - 100 A
External supply: 9 V, 110 A
Voltage priority: 9 mV, 200 A
Voltage priority: 9 V, 200 A
Voltage priority: 9 V, 200 A
Voltage priority: 9 V, 100 A to 200 A
Current priority: 9 V, 0 A
Current priority: 9 V, 200 A
Current priority: 9 V, 200 A
Current priority: 9 V, - 20 A
External supply: 9 V, 22 A
Current priority: 9 V, - 200 A
External supply: 9 V, 220 A
7 Verification and Calibration
322
Keysight N6900/N7900 Series Operating and Service Guide
Содержание N6900 Series
Страница 1: ...Keysight Advanced Power System N6900 N7900 Series Operating and Service Guide...
Страница 2: ......
Страница 63: ...1 kW Models Keysight N6900 N7900 Series Operating and Service Guide 63 1 Quick Reference...
Страница 64: ...2 kW Models 1 Quick Reference 64 Keysight N6900 N7900 Series Operating and Service Guide...
Страница 78: ...2 Installing the Instrument 78 Keysight N6900 N7900 Series Operating and Service Guide...
Страница 90: ...Rack Mounting 2 Installing the Instrument 90 Keysight N6900 N7900 Series Operating and Service Guide...
Страница 289: ...Status Diagram 6 SCPI Programming Reference 289 Keysight N6900 N7900 Series Operating and Service Guide...
Страница 354: ...Cover screws 8 Service and Maintenance 354 Keysight N6900 N7900 Series Operating and Service Guide...