Keyscan Inc. A Member of the Kaba Group
2
Operating Modes
The IOCB1616 has the following modes that are set from the Client software.
Mode
Output
Input
01 – Delayed Output
If the input remains in alarm past
the specified output time, the
output is triggered. The output
remains triggered until the input is
secured or closed.
Alarm immediately
02-Timed Output
If the input goes into alarm, the
output is triggered. The output
remains on for the duration of the
specified output time.
Alarm immediately
03-Pulsed Output
If the input goes into alarm, the
output is triggered. The output
pulses off and on for the specified
output time. The output remains
triggered until the input is secured
or closed.
Alarm immediately
04-Input\RTE Mode
When an RTE device triggers, the
associated input is shunted. The
shunt time is the associated input
time. The assigned output is
triggered for the duration of the
specified output time. When the
associated input is closed or
secured, all timers are reset.
Alarm immediately sent
if the RTE input is not
used as a shunt for the
associated input. Alarm if
input for the door contact
is left open after the
associated input time has
expired.
05-Delayed Input &
Delayed Output
If the input is triggered, the alarm
is delayed. The input is delayed by
the specified input time. The output
is triggered at the end of the
cumulative input and output times.
The output remains triggered until
the input is secured or closed.
The input's alarm is
delayed until the input
timer expires. Then it is
sent to software.
06-Delayed Input &
Timed Output
If the input is triggered, the alarm
is delayed. The input is delayed by
the specified input time. The output
remains on for the duration of the
specified output time. The output
remains triggered until the input is
secured or closed.
The input's alarm is
delayed until the input
timer expires. Then it is
sent to software.
07- Delayed Input &
Pulsed Output
If the input is triggered, the alarm
is delayed. The input is delayed by
the specified input time. The output
pulses off and on for the specified
output time. The output remains
triggered until the input is secured
or closed.
The input's alarm is
delayed until the input
timer expires. Then it is
sent to software.
11 – Manual Pulse
Control
Client enabled pulse option for an
output. (Primarily for use with the
active mapping module)
The output is pulsed for
the specified output time.